User Manual

42
Setting the Set Point (SP) Section 3-6
3-6 Setting the Set Point (SP)
3-6-1 Changing the SP
The set point cannot be changed when the “operation/adjustment protect”
parameter is set to 3. For details, refer to 4-9 Using the Key Protect Level.
To change the set point, press the U or D key in the “process value/set
point” parameter (in the operation level), and set the desired set value.
The new set point is selected two seconds after you have specified the
new value.
Multi-SP is used to switch between two or four set points. For details, refer
to 4-5 Using Event Inputs for details.
Operating Procedure In this example, the set point is changed from 0
°C to 200°C.
Advanced Function Setting Level
10. Select the “alarm 1 assignment” parameter by pressing the M key.
11. Press the U or D key to set alm1.
(The default is alm1.)
Advanced Function Setting Level
12. Select the “alarm 2 assignment” parameter by pressing the M key.
13. Press the U or D key to set alm2.
(The default is alm2.)
Initial Setting Level
14. Press the O key for at least one second to move from the advanced func-
tion setting level to the initial setting level.
Operation Level
15. Press the O key for at least one second to move from the initial setting
level to the operation level.
Operation Level
The operation level is displayed when the power is turned ON. The process
value (PV) is at the top of the display, and the set point (SP) is at the bottom.
alm1
alm1
Control output 1
assignment
alm1
alm1
alm2
alm2
Control output 2
assignment
alm2
alm2
in-t
5
Input type
C
25
100
PV/SP
C
20
0
Operation Level
1. Normally, the “process value/set point” parameter is displayed. The set
point is 0
°C.
C
30
0