Setting Output Specifications Section 3-5
Operating Procedure The following example sets the following control and alarm assignments.
Control output 1: Control output (heating); Control output 2: Control output
(cooling); Alarm output 1: Alarm 1; Alarm output 2: Alarm 2
Operation Level
1. Press the O key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
Initial Setting Level
2. Select the “standard or heating/cooling” parameter by pressing the M
key.
Initial Setting Level
3. Press the U key to set the parameter to h-c.
Note The following output assignments do not need to be set because they
are set automatically by changing the control mode, but they are
shown here as a reference for checking the assignments for each out-
put.
4. Select the “move to advanced function setting level” parameter by press-
ing the M key.
Advanced Function Setting Level
5. Press the D key to enter the password (“−169”), and move from the initial
setting level to the advanced function setting level.
Advanced Function Setting Level
6. Select the “alarm 1 assignment” parameter by pressing the M key.
7. Press the U or D key to set o.
(The default is o.)
Advanced Function Setting Level
8. Select the “control output 2 assignment” parameter by pressing the M
key.
9. Press the U or D key to set c-o.
(When h-c is selected for the “standard or heating/cooling” parameter,
the setting will be c-o.)
C
25
100
PV/S
P
in-t
5
Input type
5-hc
stnd
Standard or
heating/cooling
5-hc
h-c
amov
0
Move to ad-
vanced function
setting level
init
off
Parameter
initialization
out1
o
Control output 1
assignment
out1
o
out2
c-o
Control output 2
assignment
out2
c-o