Setting Output Specifications Section 3-5
3-5-3 Assigned Output Functions
• Function assignments can be changed by changing the settings for con-
trol and alarm assignments.
• The default function assignments for each output are shown below.
• Each output is automatically initialized as shown below by changing the
control mode.
Example: E5CN
Note (1) There is no control output 2 and no parameter assignment is displayed
for that output.
(2) Alarm 1 becomes the program END output unless the program pattern is
set to OFF.
(3) For the E5AN/EN, alarm 3 is assigned for control output (cooling) (alarm
output 2 is assigned for alarm 2).
In this manual, assigned control outputs and alarm outputs are indicated as
follows: “Control output 1 must be assigned” or “Alarm 1 must be assigned.”
5. Select the “direct/reverse operation” parameter by pressing the M key.
The default is or-r (reverse operation). To select or-d (direct opera-
tion), press the U key.
Operation Level
6. To return to the operation level, press the O key for at least one second.
orev
or-r
Direct/reverse
operation
C
30
0
PV/SP
Parameter name Symbol Initial status
Control output 1 assignment out1 Control output (heating)
Control output 2 assignment out2 Not assigned.
Alarm 1 assignment alm1 Alarm 1
Alarm 2 assignment alm2 Alarm 2
Alarm 3 assignment (E5AN/EN
only)
alm3 Alarm 3
Parameter name Symbol With control output 2 Without control output 2
Standard Heating/cooling Standard Heating/cooling
Control output 1
assignment
out1 Control output
(heating)
Control output
(heating)
Control output
(heating)
Control output
(heating)
Control output 2
assignment
out2 Not assigned. (See
note 1.)
Not assigned. (See
note 1.)
Not assigned. Control output
(cooling)
Alarm 1 assignment alm1 Alarm 1 (See note
2.)
Alarm 1 (See note
2.)
Alarm 1 (See note
2.)
Alarm 1 (See note
2.)
Alarm 2 assignment alm2 Alarm 2 (See note
3.)
Control output
(cooling) (See note
3.)
Alarm 2 Alarm 2