Setting the Input Type Section 3-2
List of Input Types
The default is 5.
If a platinum resistance thermometer is mistakenly connected while a set-
ting for other than a platinum resistance thermometer is in effect, S.ERR
will be displayed. To clear the S.ERR display, check the wiring and then
turn the power OFF and back ON.
The default is 0.
Input type Specifications Set value Input temperature setting range
Controllers
with Ther-
mocouple/
Resistance
Thermome-
ter Multi-
input
Platinum resistance
thermometer
Pt100 0 200 to 850 (°C)/300 to 1,500 (°F)
1 199.9 to 500.0 (°C)/199.9 to 900.0 (°F)
2 0.0 to 100.0 (°C)/0.0 to 210.0 (°F)
JPt100 3 199.9 to 500.0 (°C)/199.9 to 900.0 (°F)
4 0.0 to 100.0 (°C)/0.0 to 210.0 (°F)
Thermocouple K
5 200 to 1,300 (°C)/300 to 2,300 (°F)
6 20.0 to 500.0 (°C)/0.0 to 900.0 (°F)
J7100 to 850 (°C)/100 to 1,500 (°F)
8 20.0 to 400.0 (°C)/0.0 to 750.0 (°F)
T9200 to 400 (°C)/300 to 700 (°F)
10 199.9 to 400.0 (°C)/199.9 to 700.0 (°F)
E 11 0 to 600 (°C)/0 to 1,100 (°F)
L12100 to 850 (°C)/100 to 1,500 (°F)
U13200 to 400 (°C)/300 to 700 (°F)
14 199.9 to 400.0 (°C)/199.9 to 700.0 (°F)
N15200 to 1,300 (°C)/300 to 2,300 (°F)
R 16 0 to 1,700 (°C)/0 to 3,000 (°F)
S 17 0 to 1,700 (°C)/0 to 3,000 (°F)
B 18 100 to 1,800 (°C)/300 to 3,200 (°F)
Infrared temperature
sensor ES1B
10 to 70°C 19 0 to 90 (°C)/0 to 190 (°F)
60 to 120°C 20 0 to 120 (°C)/0 to 240 (°F)
115 to 165°C 21 0 to 165 (°C)/0 to 320 (°F)
140 to 260°C 22 0 to 260 (°C)/0 to 500 (°F)
Analog input 0 to 50 mV 23 Either of the following ranges, by scaling:
1,999 to 9,999
199.9 to 999.9
Input type Specifications Set value Input temperature setting range
Models with
analog
input
Current input 4 to 20 mA
0 Either of the following ranges, by scaling:
1,999 to 9,999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
0 to 20 mA 1
Voltage input 1 to 5 V 2
0 to 5 V 3
0 to 10 V 4