User Manual

29
Wiring Terminals Section 2-2
RS-232C (E5AN/EN Only)
When communications are to be used with the E5AN/EN-@@@01@, con-
nect communications cable across terminals 11 to 13.
A 1:1 connection is used. The maximum cable length is 15 m. To extend
the transmission path, use the OMRON Z3R RS-232C Optical Interface.
Use AWG24 (cross-sectional area: 0.205 mm
2
) to AWG14 (cross-sec-
tional area: 2.081 mm
2
) shielded twisted-pair cable.
External Power Supply for
ES1B
Connect terminals 11 and 12 when using the E5CN-@@PH as the exter-
nal power supply for the ES1B.
Connect terminals 14 and 15 when using the E5CN-@@PB as the exter-
nal power supply for the ES1B.
Connect terminals 14 and 15 when using the E5AN/EN-@@P as the
external power supply for the ES1B.
The following table provides the specifications of the external power sup-
ply for ES1B.
SD
RD
SG
RS-232C
RD (RXD)
SD (TXD)
ER (DTR)
SG
DR (DSR)
RS (RTS)
CS (CTS)
3
4
5
6
7
2
8
11
No.
12
13
SD
RD
SG
1
FG
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
DR (DSR)
SG
ER (DTR)
3
4
5
6
7
20
2
11
No.
12
13
SD
RD
SG
E5AN/EN-@@@01@
Host computer
RS-232C: 25-pin
E5AN/EN
RS-232C
Host computer (DOS/V)
RS-232C: 9-pin
E5AN/EN
RS-232C
Cross-sectional area of
conductor
AWG24: 0.205 mm
2
AWG14: 2.081 mm
2
Output voltage 12 VDC ±10%
Output current 20 mA max.
11
E5CN-@@PH E5CN-@@PB
12
()
(+)
14
15
()
(+)
E5AN/EN-@@P
14
15
()
(+)