User Manual

23
Wiring Terminals Section 2-2
2-2-3 Wiring
In the connection diagrams, the left side of the terminal numbers represents
the inside of the Controller and the right side represents the outside.
Power supply With the E5CN, connect to terminals 9 and 10; with the E5CN-U, connect
to pins 10 and 11; with the E5AN and E5EN, connect pins 1 and 2. The
following table shows the specifications.
Standard insulation is applied between the input power supply and the I/O
sections. If reinforced insulation is required, connect the input and output
terminals to a device without any exposed current-carrying parts or to a
device with standard insulation suitable for the maximum operating volt-
age of the power supply I/O section.
In models that have an “R” at the end of the lot number, reinforced insula-
tion is applied between the input power supply, the relay outputs, and
other terminals.
Input Make the connections as shown below, using terminals 3 to 5 for the
E5CN, pins 1 to 3 for the E5CN-U, and pins 16 and 18 for the E5AN/EN,
and matching the input types.
Control Output 1 Outputs are sent from terminals 1 and 2 with the E5CN, from pins 4 to 6
with the E5CN-U, and from pins 3 and 4 with the E5AN/EN. The following
diagrams show the available outputs and their internal equalizing circuits.
Input power supply E5CN E5CN-U E5AN/EN
100 to 240 VAC, 50/60 Hz 7.5 VA 6 VA 11 VA/10 VA
24 VAC, 50/60 Hz 5 VA 3 VA 5.5 VA
24 VDC (no polarity) 3 W 2 W 4 W
E5CN
E5CN-U
+
5
4
3
5
4
3
5
4
3
+
V
1
2
3
+
1
2
3
1
2
3
Thermocouple
Platinum resistance
thermometer
Analog input Thermocouple
Platinum resistance
thermometer
Analog input
+
+
V
mA
+
+
mA
V
+
E5AN/EN
Thermocouple
Platinum resistance
thermometer
Analog input