Setting Level Configuration and Key Operations Section 1-3
1-3 Setting Level Configuration and Key Operations
Parameters are divided into groups, each called a “level. Each of the set val-
ues (setting items) in these levels is called a “parameter. The parameters on
the E5CN/CN-U/AN/EN are divided into the following eight levels.
When the power is turned ON, all of the display lights for approximately one
second.
Note (1) Operation level entered for software reset.
(2) You cannot move to other levels by operating the keys on the front panel
from the calibration level. You must turn OFF the power supply.
(3) From the manual control level, key operations can be used to move to the
operation level only.
(See
note
3.)
(See
note 1.)
(See
note 2.)
Power ON
Started in manual mode.
Manual
mode
Press the O Key
for at least 1 s.
Press the O Key
for at least 1 s;
display will flash.
Press the O Key
for at least 3 s while
a-m is displayed.
Manual Control
Level
Operation Level
Press the
O Key for
at least 1 s.
Initial Setting Level
Press the O Key
for at least 1 s.
Advanced Function
Setting Level
Calibration Level
Input password.
Set value 1201
Input password.
Set value 169
Press the
O Key less than 1 s.
Communi-
cations Set-
ting Level
Press the O Key for at
least 1 s; display will flash.
Press the O Key for at
least 3 s.
Control stops.
Press the
O Key for less than 1 s.
Adjustment Level
Press the O+
M Keys for at
least 1 s.
Press the O +
M keys; display
will flash.
Press the O +
M Keys for at
least 3 s. (See
note.)
Protect level
Note: The time taken to move
to the protect level can
be adjusted by chang-
ing the "Move to pro-
tect level time" setting.
Control in progress
Level change
Not displayed for some models
Control stopped
Started in automatic mode.
a-m
C
25
100
C
25
100
C
Level Control in progress Control stopped
Protect level Can be set. ---
Operation level Can be set. ---
Adjustment level Can be set. ---
Manual control level Can be set. ---
Initial setting level --- Can be set.
Advanced function setting level --- Can be set.
Calibration level --- Can be set.
Communications setting level --- Can be set.