User Manual

220
Appendix A
The default is 5 (°C/°F) for Controllers with Thermocouple/Resistance Thermometer Multi-Inputs and 0 for
Controllers with Analog Inputs.
The applicable standards for each of the above input ranges are as follows:
K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
Control Range
Resistance thermometer and thermocouple input
Temperature lower limit
20°C to temperature upper limit + 20°C, or temperature lower limit 40°C to
temperature upper limit + 40
°C
ES1B input:
Same as input indication range
Analog input
5% to +105% of scaling range
Control-
lers with
Analog
Inputs
Current input 4 to 20 mA
0 Any of the following ranges,
by scaling:
1,999 to 9,999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
5% to 105% of setting
range. The display shows
1999 to 9999 (numeric
range with decimal point
omitted).
0 to 20 mA 1
Voltage input 1 to 5 V 2
0 to 5 V 3
0 to 10 V 4
Input type Specifications Set value Input temperature range Input indication range