User Manual

219
Appendix A
Sensor Input Setting Range, Indication Range, Control Range
Input type Specifications Set value Input temperature range Input indication range
Control-
lers with
Thermo-
couple/
Resis-
tance
Ther-
mome-
ter Multi-
inputs
Resistance ther-
mometer
Pt100 0 200 to 850 (°C)/300 to
1,500 (°F)
220 to 870 (°C)/340 to
1,540 (°F)
1 199.9 to 500.0 (°C)/199.9
to 900.0 (°F)
199.9 to 520.0 (°C)/199.9
to 940.0 (°F)
2 0.0 to 100.0 (°C)/0.0 to 210.0
(°F)
20.0 to 120.0 (°C)/40.0 to
250.0 (°F)
JPt100 3 199.9 to 500.0 (°C)/199.9
to 900.0 (°F)
199.9 to 520.0 (°C)/199.9
to 940.0 (°F)
4 0.0 to 100.0 (°C)/0.0 to 210.0
(°F)
20.0 to 120.0 (°C)/40.0 to
250.0 (°F)
Thermocouple K
5 200 to 1,300 (°C)/300 to
2,300 (°F)
220 to 1,320 (°C)/340 to
2,340 (°F)
6 20.0 to 500.0 (°C)/0.0 to
900.0 (°F)
40.0 to 520.0 (°C)/40.0 to
940.0 (°F)
J7100 to 850 (°C)/100 to
1,500 (°F)
120 to 870 (°C)/140 to
1,540 (°F)
8 20.0 to 400.0 (°C)/0.0 to
750.0 (°F)
40.0 to 420.0 (°C)/40.0 to
790.0 (°F)
T9200 to 400 (°C)/300 to 700
(°F)
220 to 420 (°C)/340 to 740
(°F)
10 199.9 to 400.0 (°C)/199.9
to 700.0 (°F)
199.9 to 420.0 (°C)/199.9
to 740.0 (°F)
E 11 0 to 600 (°C)/0 to 1,100 (°F) 20 to 620 (°C)/40 to 1,140
(°F)
L12100 to 850 (°C)/100 to
1,500 (°F)
120 to 870 (°C)/140 to
1,540 (°F)
U13200 to 400 (°C)/300 to 700
(°F)
220 to 420 (°C)/340 to 740
(°F)
14 199.9 to 400.0 (°C)/199.9
to 700.0 (°F)
199.9 to 420.0 (°C)/199.9
to 740.0 (°F)
N15200 to 1,300 (°C)/300 to
2,300 (°F)
220 to 1,320 (°C)/340 to
2,340 (°F)
R 16 0 to 1,700 (°C)/0 to 3,000
(°F)
20 to 1,720 (°C)/40 to
3,040 (°F)
S 17 0 to 1,700 (°C)/0 to 3,000
(°F)
20 to 1,720 (°C)/40 to
3,040 (°F)
B 18 100 to 1,800 (°C)/300 to
3,200 (°F)
0 to 1,820 (°C)/0 to 3,240
(°F)
ES1B Infrared
Temperature
Sensor
10 to 70°C 19 0 to 90 (°C)/0 to 190 (°F) 20 to 130 (°C)/40 to 270
(°F)
60 to 120°C 20 0 to 120 (°C)/0 to 240 (°F) 20 to 160 (°C)/40 to 320
(°F)
115 to 165°C 21 0 to 165 (°C)/0 to 320 (°F) 20 to 205 (°C)/40 to 400
(°F)
140 to 260°C 22 0 to 260 (°C)/0 to 500 (°F) 20 to 300 (°C)/40 to 580
(°F)
Analog input 0 to 50 mV 23 Any of the following ranges,
by scaling:
1,999 to 9,999
199.9 to 999.9
5% to 105% of setting
range. The display shows -
1999 to 9999 (numeric range
with decimal point omitted).