User Manual
218
Appendix A
Note (1)
(1.1) Initialized when the transfer output type is changed.
Initialized if the input type, temperature unit, scaling upper/lower limit, or SP upper/
lower limit is changed when the transfer output type is SP, ramp SP, or PV.
(When initialized by the initializing settings, it is initialized to 100.0/0.0.)
(2) The setting range depends on whether control output 1 is a linear output or pulse output.
(3) When setting CWF, either CompoWay/F or SYSWAY can be used as the communications protocol.
(CompoWay/F and SYSWAY are automatically identified by the command frames.)
(4) P.END (program end output) can be set when the program pattern is not set to 0 (OFF).
(5) PRST (program start) can be set when the program pattern is not set to 0 (OFF).
(6) Set “none” as the unit for Controllers with Analog Inputs.
Transfer output
type
Setting (monitor) range Default (transfer output
upper/lower limits) (See
note 1.1.)
Unit
Set point SP lower limit to SP upper limit SP upper limit/lower limit EU
Set point during SP
ramp
SP lower limit to SP upper limit SP upper limit/lower limit EU
PV Temperature: Sensor setting
range lower limit to sensor set-
ting range upper limit
Sensor setting range upper/
lower limit
EU
Analog: Scaling lower limit to
scaling upper limit
Scaling upper/lower limit EU
MV monitor (heating) Standard: −5.0 to 105.0
Heating/cooling: 0.0 to 105.0
100.0/0.0 %
MV monitor (cooling) 0.0 to 105.0 100.0/0.0 %