User Manual
214
Appendix A
Event input assign-
ment 2
ev-2 NONE: None
STOP: RUN/STOP
MANU: Auto/manual switch
PRST: Program start (See
note 5.)
none,
stop,
manu, prst
STOP None
Multi-SP uses mspu OFF, ON off, on OFF None
SP ramp time unit spru S: EU/second
M: EU/minute
s, m MNone
Standby sequence
reset
rest Condition A, condition B a, b Condition A None
Alarm 1 close in
alarm
al1n N-O: Open in alarm
N-C: Close in alarm
n-o, n-c N-O None
Alarm 1 hysteresis alh1 Multi-input: 0.1 to 999.9 0.2 °C or °F
(See note
6.)
Analog input: 0.01 to 99.99 0.02 %FS
Alarm 2 close in
alarm
al2n N-O: Open in alarm
N-C: Close in alarm
n-o, n-c N-O None
Alarm 2 hysteresis alh2 Multi-input: 0.1 to 999.9 0.2 °C or °F
(See note
6.)
Analog input: 0.01 to 99.99 0.02 %FS
Alarm 3 close in
alarm
al3n N-O: Open in alarm
N-C: Close in alarm
n-o, n-c N-O None
Alarm 3 hysteresis alh3 Multi-input: 0.1 to 999.9 0.2 °C or °F
(See note
6.)
Analog input: 0.01 to 99.99 0.02 %FS
HB ON/OFF hbu OFF, ON off, on ON None
Heater burnout latch hbl OFF, ON off, on OFF None
Heater burnout hys-
teresis
hbh 0.1 to 50.0 0.1 A
ST stable range st-b 0.1 to 999.9 15.0 °C or °F
α alfa 0.00 to 1.00 0.65 None
Input digital filter inf 0.0 to 999.9 0.0 Second
Additional PV display pvad OFF, ON off, on OFF None
MV display o-dp OFF, ON off, on OFF None
Automatic display
return time
ret OFF or 1 to 99 off, 1 to
99
OFF Second
Alarm 1 latch a1lt OFF, ON off, on OFF None
Alarm 2 latch a2lt OFF, ON off, on OFF None
Alarm 3 latch a3lt OFF, ON off, on OFF None
Move to protect level
time
prlt 1 to 30 3 Second
Input error output sero OFF, ON off, on OFF None
Cold junction com-
pensation method
cjc OFF, ON off, on ON None
MB command logic
switching
rlrv OFF, ON off, on OFF None
Parameters Characters Setting (monitor) value Display Default Unit Set value