Appendix A
Manual Control Level
Advanced Function Setting Level
Alarm 2 type alt2 0: Alarm function OFF
1: Upper and lower-limit
alarm
2: Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit
range alarm
5: Upper and lower-limit
alarm with standby
sequence
6: Upper-limit alarm with
standby sequence
7: Lower-limit alarm with
standby sequence
8: Absolute-value upper-limit
alarm
9: Absolute-value lower-limit
alarm
10: Absolute-value upper-limit
alarm with standby
sequence
11: Absolute-value lower-limit
alarm with standby
sequence
2None
Alarm 3 type alt3 Same settings as the alarm 2
type
2None
Transfer output type tr-t OFF: OFF
SP: Set point
SP-M: Ramp set point
PV: Process value
MV: Manipulated variable
(heating)
C-MV: Manipulated variable
(cooling)
off
sp
sp-m
pv
mv
c-mv
OFF None
Transfer output
upper limit
tr-h See note 1. See note 1. See note 1.
Transfer output lower
limit
tr-l See note 1. See note 1. See note 1.
Linear current output o1-t 4-20: 4 to 20 mA
0-20: 0 to 20 mA
4-20, 0-20 4-20 None
Move to advanced
function setting level
amov −1999 to 9,999 0 None
Parameters Characters Setting (monitor) value Display Default Unit Set value
Manual MV −5.0 to 105.0 (standard)
−105.0 to 105.0 (heating/cool-
ing)
0.0 %
Parameters Characters Setting (monitor) value Display Default Unit Set value
Parameter initializa-
tion
init OFF, FACT off, fact OFF None
Number of multi-SP
uses
ev-m 0 to 2 1 None
Event input assign-
ment 1
ev-1 NONE: None
STOP: RUN/STOP
MANU: Auto/manual switch
PRST: Program start (See
note 5.)
none,
stop,
manu, prst
NONE None