User Manual
212
Appendix A
Scaling lower limit in-l −1,999 to scaling upper limit
−1
0None
Decimal point dp Multi-input: 0 to 1 0 None
Analog input: 0 to 3 0 None
Temperature unit d-u °C, °F c, f °CNone
SP upper limit sl-h SP lower limit + 1 / input
range lower limit (tempera-
ture)
1300 EU
SP lower limit + 1 / scaling
upper limit (analog)
100
SP lower limit sl-l Input range lower limit to SP
upper limit − 1 (temperature)
−200 EU
Scaling lower limit to SP
upper limit − 1 (analog)
0
PID ON/OFF intl ON/OFF 2-PID onof, pid ON/OFF None
Standard or heating/
cooling
s-hc Standard or heating/cooling send, h-c Standard None
ST st OFF, ON off, on ON None
Program pattern ptrn OFF, STOP, CONT off, stop,
cont
OFF None
Control period (heat) cp 0.5 or 1 to 99 0.5, 1 to 99 20 Second
Control period (cool) c-cp 0.5 or 1 to 99 0.5, 1 to 99 20 Second
Direct/reverse opera-
tion
orev Reverse operation, direct
operation
or-r, or-d Reverse
operation
None
Alarm 1 type alt1 0: Alarm function OFF
1: Upper and lower-limit
alarm
2: Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit
range alarm
5: Upper and lower-limit
alarm with standby
sequence
6: Upper-limit alarm with
standby sequence
7: Lower-limit alarm with
standby sequence
8: Absolute-value upper-limit
alarm
9: Absolute-value lower-limit
alarm
10: Absolute-value upper-limit
alarm with standby
sequence
11: Absolute-value lower-limit
alarm with standby
sequence
12: LBA (Loop Break Alarm)
2None
Parameters Characters Setting (monitor) value Display Default Unit Set value