User Manual
210
Appendix A
Adjustment Level
Parameters Characters Setting (monitor) value Display Default Unit Set value
Adjustment level dis-
play
l.adj
AT execute/cancel at OFF, ON off, on OFF None
Communications
writing
cmwt OFF, ON off, on OFF None
Heater current 1
value monitor
ct1 0.0 to 55.0 A
Heater current 2
value monitor
ct2 0.0 to 55.0 A
Leakage current 1
monitor
lcr1 0.0 to 55.0 A
Leakage current 2
monitor
lcr2 0.0 to 55.0 A
Heater burnout
detection 1
hb1 0.0 to 50.0 0.0 A
Heater burnout
detection 2
hb2 0.0 to 50.0 0.0 A
HS alarm 1 hs1 0.0 to 50.0 50.0 A
HS alarm 2 hs2 0.0 to 50.0 50.0 A
SP 0 sp-0 SP lower limit to SP upper
limit
0EU
SP 1 sp-1 SP lower limit to SP upper
limit
0EU
SP 2 sp-2 SP lower limit to SP upper
limit
0EU
SP 3 sp-3 SP lower limit to SP upper
limit
0EU
Temperature input
shift
ins −199.9 to 999.9 0.0 °C or °F
Upper-limit tempera-
ture input shift value
insh −199.9 to 999.9 0.0 °C or °F
Lower-limit tempera-
ture input shift value
insl −199.9 to 999.9 0.0 °C or °F
Proportional band p Multi-input: 0.1 to 999.9 8.0 °C or °F
(See note
6.)
Analog input: 0.1 to 999.9 10.0 %FS
Integral time i 0 to 3,999 233 Second
Derivative time d RT OFF: 0 to 3,999 40 Second
RT ON: 0.0 to 999.9 40.0 Second
Cooling coefficient c-sc 0.01 to 99.99 1.00 None
Dead band c-db Multi-input: −199.9 to 999.9 0.0 °C or °F
(See note
6.)
Analog input: −19.99 to 99.99 0.00 %FS
Manual reset value of-r 0.0 to 100.0 50.0 %
Hysteresis (heating) hys Multi-input: 0.1 to 999.9 1.0 °C or °F
(See note
6.)
Analog input: 0.01 to 99.99 0.10 %FS