User Manual

200
Appendix A
Note (1) For the setting ranges for each sensor input, see page 219.
(2) When connecting the ES2-THB, connect it 1:1.
(3) Always connect an AC load to a long-life relay output. The output will not turn OFF if a DC load is
connected, because a triac is used for switching when closing and opening the circuit.
HBA and HS Alarm (for Controller with Heater Burnout and HS Alarm)
Note (1) When the control output 1 ON time is less than 190 ms, heater burnout detection and heater current
measurement are not performed.
(2) When the control output 1 OFF time is less than 190 ms, HS alarm and leakage current measure-
ment are not performed.
External Power Supply for ES1B
Note Contact your OMRON representative for information on using the external power supply for ES1B for
other applications.
Characteristics
Indication method 11-segment/7-segment digital display and single-lighting indicator
Other functions Depend on the model
Ambient temperature 10 to 55°C (with no condensation or icing); with 3-year guarantee: 10 to 50°C
Ambient humidity 25% to 85%
Storage temperature 25 to 65°C (with no condensation or icing)
Altitude 2,000 m or less
Recommended fuse T2A, 250 VAC, time lag, low shut-off capacity
Installation environment Installation Category II, Pollution Class 2 (IEC 61010-1 compliant)
Max. heater current 50 A AC
Input current readout accuracy ±5% FS ±1 digit max.
Heater burnout alarm setting
range
0.1 to 49.9 A (0.1 A units)
0.0 A: Heater burnout alarm output turns OFF.
50.0 A: Heater burnout alarm output turns ON.
Min. detection ON time: 190 ms (See note 1.)
HS alarm setting range 0.1 to 49.9 A (0.1 A units)
0.0 A: HS alarm output turns ON.
50.0 A: HS alarm output turns OFF.
Min. detection OFF time: 190 ms (See note 2.)
Output voltage 12 VDC ±10%
Output current 20 mA max.
Indication accuracy
(ambient temperature of
23°C)
Thermocouple (See note 1.):
E5CN/AN/EN: (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
E5CN-U: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
Analog input: ±0.5% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Temperature variation
influence (See note 2.)
Thermocouple (R, S, B)
(±1% of PV or ±10°C, whichever is greater) ±1 digit max. (E5CN)
(±2% of PV or ±10°C, whichever is greater) ±1 digit max. (E5CN-U)
Other thermocouples:
(±1% of PV or ±4°C, whichever is greater) ±1 digit max. (E5CN)
(±2% of PV or ±4°C, whichever is greater) ±1 digit max. (E5CN-U)
*K thermocouple at 100°C max: ±10°C max.
Platinum resistance thermometer:
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1% FS ±1 digit max. (See note 2.)
Voltage variation influence
(See note 2.)