User Manual
184
Parameter Structure
Section 6-1
6-1 Parameter Structure
• To execute user calibration, enter the password “1201” at the “move to
calibration level” parameter in the advanced function setting level. The
mode will be changed to the calibration mode, and adj will be displayed.
• The “move to calibration level” parameter may not be displayed when the
user is doing the calibration for the first time. If this happens, set the “ini-
tial/communications protect” parameter in the protect level to 0 before
moving to the advanced function setting level.
• The calibration mode is ended by turning the power OFF.
• The parameter calibrations in the calibration mode are structured as
shown below.
Controllers with Thermocouple/Resistance Thermometer Multi-inputs
19: K140F/60C
20: K240F/120C
21: K280F/140C
22: K440F/220C
5: K
7: J
11: E
12: L
15: N
6: K
8: J
9, 10: T
13, 14: U
16: R
17: S
18: B
1: Pt100
2: Pt100
3: JPt100
4: JPt100
0: Pt100 23: 0 to 50 mV
adj
30
p390
e20c
str
no
p280
e26b
t54
b9a5
t24
e220
c54
b9as
p10
4543
p10
4543
t-6
2988
t-6
0200
t-6
2988
pb10
4544
pb10
4544
c54
ba13
pb 0
4083
pb 0
4083
c-6
29be
bias
35b8
bias
35b8
Advanced Function Setting
Level
Moves automatically according to input type.
Platinum resistance
thermometer
Thermocouple or infrared
temperature sensor
Analog input