User Manual

181
Advanced Function Setting Level Section 5-7
Set the soak time unit for the simple program function.
Related Parameters
Program start, Soak time remain (operation level): Page 123
Soak time, Wait band (adjustment level): Page 141
Program pattern (initial setting level): Page 151
This parameter sets whether the set point that triggers a deviation alarm dur-
ing SP ramp operation is to be the ramp SP or target SP.
Set whether the set point that triggers a deviation alarm is the ramp SP or
target SP.
Related Parameters
SP ramp set value (adjustment level): Page 143
ST (initial setting level): Page 150
This parameter sets the password to move to the calibration level.
Set the password to move to the calibration level. The password is 1201.
Move to the calibration level either by pressing the M key or O key or by
waiting for two seconds to elapse.
Related Parameter
Initial setting/communications protect (protect level): Page 116
t-u Soak Time Unit
The “program pattern” parameter
must not be set to OFF.
Setting range Default
m: Minutes, h: Hours m
Function
Setting
See
See
alsp Alarm SP Selection
Alarm 1, 2, and 3 functions must be
assigned.
The “SP ramp set value” and “ST”
parameters must not be set to OFF.
The alarm type must set to a devia-
tion alarm.
Setting range Default
sp-m: Ramp SP, sp: SP sp-m
Function
Setting
See
See
cmov Move to Calibration Level
Initial setting/communications protect
must be 0.
Function
See
See