Advanced Function Setting Level Section 5-7
This parameter sets the function to be assigned to control output 2.
Note (1) If c-o is assigned for standard control, a value equivalent to 0% will be
output.
(2) Can be selected only when the program pattern is not set to OFF.
(3) If the “standard or heating/cooling” parameter is set to heating/cooling
control, control automatically switches to c-o.
Related Parameters
Standard or heating/cooling: Page 150, Program pattern: Page 151, (initial
setting level)
This parameter sets the function to be assigned to alarm output 1.
Note (1) If c-o is assigned for standard control, a value equivalent to 0% will be
output.
(2) Can be selected only when the program pattern is not set to OFF.
(3) If a setting is changed when the “program pattern” parameter is not set to
OFF, control automatically switches to p.end.
Related Parameter
Program pattern (initial setting level): Page 151
out2 Control Output 2 Assignment
Control output 2 must be assigned.
Setting range Default
none: No function is assigned to control output 2. none
(See note
3.)
o: Heating control output is output.
c-o: Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output.
alm2: Alarm 2 is output.
alm3: Alarm 3 is output.
p.end: Program end is output. (See note 2.)
Function
Setting
See
See
alm1 Alarm 1 Assignment
Alarm output 1 must be assigned.
Setting range Default
none: No function is assigned to alarm output 1. alm1
(See note
3.)
o: Heating control output is output.
c-o: Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output.
alm2: Alarm 2 is output.
alm3: Alarm 3 is output.
p.end: Program end is output. (See note 2.)
Function
Setting
See
See