User Manual

176
Advanced Function Setting Level Section 5-7
This parameter enables or disables the LBA function and sets the detection
time interval.
Set the time interval for detecting loop burnouts.
To disable the LBA function, set 0.
Related Parameters
Alarm 1 type (initial setting level): Page 152
LBA level: Page 176, LBA band: Page 177 (advanced function setting level)
This parameter sets the LBA level.
If the deviation between the SP and PV exceeds the LBA level, a loop
burnout is detected.
Note Set “none” as the unit for Controllers with Analog Inputs.
Related Parameters
Process value/set point (operation level): Page 120
Alarm 1 type (initial setting level): Page 152
LBA detection time: Page 176, LBA band: Page 177 (advanced function set-
ting level)
lba LBA Detection Time
Alarm 1 must be assigned.
The alarm type must be set to 12
(LBA).
Setting range Unit Default
0 to 9999 Second 0
Function
Setting
See
See
lbal LBA Level
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
Models Setting range Unit Default
Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
0.1 to 999.9 °C or °F
(See note.)
8.0
Controllers with Analog Inputs 0.01 to 99.99 %FS 10.00
Function
Setting
See
See