Advanced Function Setting Level Section 5-7
• When this parameter is set to ON, the HS alarm is held until either of the
following conditions is satisfied.
a The HS alarm current is set to 50.0 A.
b The power is turned OFF then back ON again (i.e., power is reset).
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
■ Related Parameter
HS alarm use (advanced function setting level): Page 174
• This parameter sets the hysteresis for HS alarms.
■ Related Parameter
HS alarm use (advanced function setting level): Page 174
hsl HS Alarm Latch
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Setting range Default
on: Enabled, off: Disabled off
Function
Setting
See
See
hsh HS Alarm Hysteresis
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
The “HS alarm latch” must be set to
OFF.
Setting range Unit Default
0.1 to 50.0 A 0.1
Function
Setting
See
See