User Manual

171
Advanced Function Setting Level Section 5-7
Note Set “none” as the unit for Controllers with Analog Inputs.
Related Parameter
PV change color (advanced function setting level): Page 169
Alarm 1, 2, or 3 outputs are prevented from turning ON until after the delay
times set in these parameters have elapsed.
Set the time for which the ON delay is to be enabled.
To disable the ON delay, set 0.
Related Parameters
Alarm 1 to 3 type (initial setting level): Page 152 to 154
Models Setting range Unit Default
Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
0.1 to 999.9 °C or °F
(See note.)
5.0
Controllers with Analog Inputs 0.01 to 99.99 %FS 5.00
Setting
See
See
a1on Alarm 1 ON Delay
Alarm 1 must be assigned, and the
alarm 1 type must not be 0 or 12.
a2on Alarm 2 ON Delay
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
a3on Alarm 3 ON Delay
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Setting range Unit Default
0 to 999 Second 0
Function
Setting
See
See