Advanced Function Setting Level Section 5-7
Note Set “none” as the unit for Controllers with Analog Inputs.
■ Related Parameter
PV change color (advanced function setting level): Page 169
Alarm 1, 2, or 3 outputs are prevented from turning ON until after the delay
times set in these parameters have elapsed.
• Set the time for which the ON delay is to be enabled.
• To disable the ON delay, set 0.
■ Related Parameters
Alarm 1 to 3 type (initial setting level): Page 152 to 154
Models Setting range Unit Default
Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
0.1 to 999.9 °C or °F
(See note.)
5.0
Controllers with Analog Inputs 0.01 to 99.99 %FS 5.00
Setting
See
See
a1on Alarm 1 ON Delay
Alarm 1 must be assigned, and the
alarm 1 type must not be 0 or 12.
a2on Alarm 2 ON Delay
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
a3on Alarm 3 ON Delay
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Setting range Unit Default
0 to 999 Second 0
Function
Setting
See
See