User Manual
168
Advanced Function Setting Level Section 5-7
• This parameter sets the key pressing time required to move to the protect
level from the operation level or the adjustment level.
■ Related Parameters
Operation/adjustment protect, initial setting/communications protect, setting
change protect (protect level): Page 116
• When this parameter is set to ON, alarm 1 output turns ON for input
errors.
The alarm 1 operation indicator will not light.
• The alarm 1 output is an OR output of alarm 1, HBA burnout/HS alarm,
and input error.
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
• Specifies whether cold junction compensation is to be performed inter-
nally by the Controller or to be performed externally when the input type
setting is to between 5 and 22.
• The cold junction compensation external setting is enabled when the tem-
perature difference is measured using two thermocouples or two ES1B
Sensors.
■ Related Parameter
Input type (initial setting level): Page 146
prlt Move to Protect Level Time
Setting range Unit Default
1 to 30 Second 3
Function
Setting
See
See
sero Input Error Output
Alarm 1 must be assigned.
Setting range Default
on: Enabled, off: Disabled off
Function
Setting
cjc Cold Junction Compensation Method
Input type must be thermocouple or
infrared temperature sensor
Setting range Default
on: Internally, off: Externally on
Function
Setting
See
See