Advanced Function Setting Level Section 5-7
• In the operation level or adjustment level, the display automatically returns
to the PV/SP if there are no key operations for the time set for this param-
eter.
• The automatic display return time is disabled when the parameter is set to
OFF. (In that case, the display will not be automatically switched.)
• When a parameter is set to ON, once the alarm function has turned ON it
is held until the power is turned OFF. The latch can be canceled, however,
by switching to the initial setting level, communications setting level,
advanced function setting level, or calibration level.
• If alarm outputs are set to “close in alarm,” the outputs are kept closed. If
they are set to “open in alarm,” they are kept open.
■ Related Parameters
Alarm value 1 to 3: Page 124 to 125, Alarm value upper limit 1 to 3: Page 126
to 127, Alarm value lower limit 1 to 3: Page 126 to 127 (operation level)
Alarm 1 to 3 type (initial setting level): Page 152 to 154
Standby sequence reset: Page 161, Alarm 1 to 3 open in alarm: Page 162,
Alarm 1 to 3 hysteresis: Page 163 (advanced function setting level)
ret Automatic Display Return Time
Setting range Unit Default
OFF, 1 to 99 Second off
Function
Setting
a1lt Alarm 1 Latch
Alarm 1 must be assigned, and the
alarm 1 type must not be 0.
a2lt Alarm 2 Latch
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
a3lt Alarm 3 Latch
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Setting range Default
on: Enabled, off: Disabled off
Function
Setting
See