User Manual
163
Advanced Function Setting Level Section 5-7
■ Related Parameters
Alarm value 2 and 3: Page 125, Alarm value upper limit 2 and 3, Alarm value
lower limit 2 and 3: Page 126 to 127 (operation level)
Alarm 2 to 3 type (initial setting level): Page 154
Alarm 2 and 3 hysteresis: Page 163, Standby sequence reset: Page 161,
Alarm 2 and 3 latch: Page 167 (advanced function setting level)
• These parameters set alarm 1, 2, and 3 hysteresis.
Note Set “none” as the unit for Controllers with Analog Inputs.
■ Related Parameters
Alarm value 1 to 3: Page 124 to 125, Alarm value upper limit 1 to 3: Page 126
to 127, Alarm value lower limit 1 to 3: Page 126 to 127 (operation level)
Alarm 1 to 3 type (initial setting level): Page 152 to 154
Standby sequence reset: Page 161, Alarm 1 to 3 open in alarm: Page 162,
Alarm 1 to 3 latch: Page 167 (advanced function setting level)
• Set to use the heater burnout alarm.
See
See
alh1 Alarm 1 Hysteresis
Alarm 1 must be assigned, and the
alarm 1 type must not be 0 or 12.
alh2 Alarm 2 Hysteresis
Alarm 2 must be assigned, and the
alarm 2 type must not be 0.
alh3 Alarm 3 Hysteresis
Alarm 3 must be assigned, and the
alarm 3 type must not be 0.
Models Setting range Unit Default
Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
0.1 to 999.9 °C or °F
(See note.)
0.2
Controllers with Analog Inputs 0.01 to 99.99 %FS 0.02
Function
Setting
See
See
hbu HB ON/OFF
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
Setting range Default
on: Enabled, off: Disabled on
Function
Setting