User Manual

161
Advanced Function Setting Level Section 5-7
Related Parameters
Multi-SP set point setting (operation level): Page 120
Number of multi-SP uses (advanced function setting level): Page 159
This parameter sets the time unit for the rate of change during SP ramp
operation.
Related Parameters
Ramp SP monitor (operation level): Page 121
SP ramp set value (adjustment level): Page 143
This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Condition A
Control started (including power ON), and set point, alarm value (alarm
value upper/lower limit), or input shift value (upper/lower-limit temperature
input shift value) changed.
Condition B
Power ON
The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
See
See
spru SP Ramp Time Unit
The “ST” parameter must be set to
OFF.
Setting range Default
s: EU/s, m: EU/min m
Function
Setting
See
See
rest Standby Sequence Reset
The alarm 1/2/3 type must be set to
a type with a standby sequence.
Setting range Default
a: Condition A, b: Condition B a
Function
Alarm
(after change)
Alarm
SP change
Condition A only
Condition A
only
Alarm hysteresis
: Standby sequence canceled
: Standby sequence reset
Alarm output:
Condition A
Alarm output:
Condition B
Setting