User Manual

156
Initial Setting Level Section 5-6
This parameter selects the output type for linear current outputs.
Select either 4 to 20 mA or 0 to 20 mA.
Related Parameter
Transfer output type (initial setting level): Page 155
Set the “move to advanced setting level” parameter set value to
169.
Move to the advanced setting level either by pressing the M key or O key
or by waiting for two seconds to elapse.
Related Parameter
Initial setting/communications protect (protect level): Page 116
o1-t Linear Current Output
A current output must be assigned.
Transfer type Default
4-20: 4 to 20 mA
0-20: 0 to 20 mA
4-20
Function
Setting
See
See
amov Move to Advanced Function Setting Level
The “initial setting/communications
protect” parameter must be set to 0.
Function
See
See