155
Initial Setting Level Section 5-6
• When current output is to be used as transfer output, this parameter sets
the transfer output type.
• If current output is not to be used as transfer output, set this parameter to
OFF.
■ Related Parameter
Transfer output upper limit, Transfer output lower limit (initial setting level):
Page 155
• This parameter sets the upper and lower limit values of transfer outputs.
■ Related Parameter
Transfer output type (initial setting level): Page 155
tr-t Transfer Output Type
A current output must be assigned.
Transfer output type Default
OFF off off
Set point sp
Set point during SP ramp sp-m
PV pv
MV monitor (heating) mv
MV monitor (cooling) c-mv
Function
Setting
See
See
tr-h Transfer Output Upper Limit
A current output must be assigned.
The transfer output type must not be
set to OFF.
tr-l Transfer Output Lower Limit
Function
Setting
Transfer output
type
Setting range Default Unit
Transfer
output lower
limit
Transfer
output upper
limit
Set point SP lower limit to SP upper limit SP lower limit SP upper limit EU
Set point during
SP ramp
SP lower limit to SP upper limit
PV Temperature Senor setting range lower limit
to sensor setting range upper
limit
Sensor setting
range lower
limit
Sensor setting
range upper
limit
Analog Analog scaling lower limit to
analog scaling upper limit
Scaling lower
limit
Scaling upper
limit
MV monitor
(heating)
Standard −5.0 to 105.0 0.0 100.0 %
Heating/
cooling
0.0 to 105.0
MV monitor
(cooling)
0.0 to 105.0
See
See