User Manual

151
Initial Setting Level Section 5-6
Related Parameters
Input type: Page 146, PID ON/OFF: Page 149 (initial setting level), ST stable
range (advance function setting level): Page 165
This parameter sets the type of control when using the simple program func-
tion.
If the program pattern is set to OFF, the simple program will not operate.
If the program pattern is set to STOP, the RUN/STOP status will change to
STOP after the soak time has expired. If the program pattern is set to
CONT, control will continue in RUN status after the soak time has expired.
Related Parameters
Program start, Soak time remain: Page 123, RUN/STOP: Page 124 (operation
level)
Soak time, Wait band (adjustment level): Page 141
Soak time unit (advanced function setting level): Page 181
These parameters set the output periods. Set the control periods taking
the control characteristics and the electrical durability of the relay into
consideration.
For standard control, use the “control period (heat)” parameter. The “con-
trol period (cool)” parameter cannot be used.
Whenever the heating control output is a current output, the “control
period (heat)” parameter cannot be used.
For heating/cooling control, the control period can be set independently
for heating and cooling. The “control period (heat)” parameter is used for
the heating control output, and the “control period (cool)” parameter is
used for the cooling control output.
Related Parameters
PID ON/OFF (initial setting level): Page 149
See
See
ptrn Program Pattern
Setting range Default
off Simple program function turned OFF off
stop Go to STOP mode at end of program.
cont Continue in RUN mode at end of program.
Function
Setting
See
See
cp Control Period (Heat)
The cooling control output and heat-
ing control output must be assigned
to relay/voltage outputs.
The control must be set to 2-PID
control.
For the “control period (cool)” param-
eter, the control must be set to heat-
ing/cooling control.
c-cp Control Period (Cool)
Parameters Setting range Unit Default
Control period (heat) 0.5 or 1 to 99 Second 20
Control period (cool) 0.5 or 1 to 99 Second 20
Function
Setting
See
See