Initial Setting Level Section 5-6
These parameters can be used when the input type is set for an analog
input.
When an analog input is used, scaling is performed. Set the upper limit in
the “scaling upper limit” parameter and the lower limit in the “scaling lower
limit” parameter.
The “decimal point” parameter specifies the decimal point position of
parameters (set point, etc.) whose unit is EU.
Scaling Upper Limit, Scaling Lower Limit
Decimal Point
Related Parameters
Input type (initial setting level): Page 146
Set the temperature input unit to either
°C or °F.
Related Parameters
Input type (initial setting level): Page 146
in-h Scaling Upper Limit
The input type must be set for an
analog input.
in-l Scaling Lower limit
dp Decimal Point
Parameters Setting range Unit Default
Scaling upper limit Scaling lower limit + 1 to 9999 None 100
Scaling lower limit 1999 to scaling upper limit 1None 0
Parameters Model Setting
range
Default
Decimal Point Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
0 to 1 0
Controllers with Analog Inputs 0 to 3 0
Set value Settings Example
0 0 digits past decimal point 1234
1 1 digits past decimal point 123.4
2 2 digits past decimal point 12.34
3 3 digits past decimal point 1.234
Function
Setting
See
See
d-u Temperature Unit
The input type must be set for a tem-
perature input.
Setting range Default
c: °C, f: °F c
Function
Setting
See
See