User Manual
146
Initial Setting Level Section 5-6
• This parameter sets the type of sensor.
• When this parameter is changed, the set point limiter is changed to the
defaults. If the input type must be changed, set the “SP upper limit” and
“SP lower limit” parameters (initial setting level).
• Set one of the set values from the following table.
The defaults are as follows:
Controllers with Thermocouple/Resistance Thermometer Multi-inputs:
5 (K thermocouple)
Controllers with Analog Inputs: 0 (current input, 4 to 20 mA)
• If a platinum resistance thermometer is mistakenly connected while a set-
ting for other than a platinum resistance thermometer is in effect, S.ERR
will be displayed. To clear the S.ERR display, check the wiring and then
cycle the power.
Initial Setting Level
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
in-l
0
dp
0
in-t
5
in-h
100
d-u
c
sl-h
1300
C
sl-l
-200
C
cntl
onof
s-hc
stnd
st
on
ptrn
off
cp
20
c-cp
20
oreV
or-r
alt1
2
alt2
2
alt3
2
tr-t
off
tr-h
100.0
tr-l
0.0
o1-t
4-20
amov
0
Page Page
Input type
Scaling upper limit
Scaling lower limit
Decimal point
Temperature unit
SP upper limit
SP lower limit
PID·ON/OFF
ST
Program pattern
Control period (heat)
Control period (cool)
Direct/reverse operation
Alarm 1 type
Alarm 2 type
Alarm 3 type
Transfer output type
Transfer output upper
limit
Transfer output lower
limit
Linear current output
Move to advanced
function setting level
Standard or
heating/cooling
146
148
148
148
148
149
149
149
150
150
151
151
151
152
152
154
154
155
155
155
156
156
in-t Input Type
Function
Setting