User Manual

141
Adjustment Level Section 5-4
This parameter sets the time for the control operation when using the sim-
ple program function.
Related Parameters
Program start, Soak time remain (operation level): Page 123
Wait band (adjustment level): Page 141
Program pattern (initial setting level): Page 151
Soak time unit (advanced function setting level): Page 181
This parameter sets the stable band within which the soak time is mea-
sured for the simple program function.
Note Set “none” as the unit for Controllers with Analog Inputs.
Related Parameters
Program start, Soak time remain (operation level): Page 123
Soak time (adjustment level): Page 141
Program pattern (initial setting level): Page 151
Soak time unit (advanced function setting level): Page 181
soak Soak Time
The “program pattern” parameter
must not be set to OFF.
Setting range Unit Default
1 to 9999 min or h 1
Function
Setting
See
See
wt-b Wait Band
The “program pattern” parameter
must not be set to OFF.
Model Setting range Unit Default
Controllers with Thermocouple/Resis-
tance Thermometer Multi-inputs
OFF or 0.1 to
999.9
°C or °F
(See note.)
off
Controllers with Analog Inputs OFF or 0.01 to
99.99
%FS
Function
Setting
See
See