Adjustment Level Section 5-4
This parameter sets the current for the HS alarm to be output.
• The HS alarm is output when the heater current value goes above the set-
ting of this parameter.
• When the set value is 50.0, the HS alarm is turned OFF. When the set
value is 0.0, the HS alarm will turn ON.
■ Related Parameters
Leakage current 1 monitor (adjustment level): Page 133
HS alarm, HS alarm latch, HS alarm hysteresis (advanced function setting
level): Page 174
This parameter sets the current for the HS alarm to be output.
• The HS alarm is output when the heater current value goes above the set-
ting of this parameter.
• When the set value is 50.0, the HS alarm is turned OFF. When the set
value is 0.0, the HS alarm will turn ON.
■ Related Parameters
Leakage current 2 monitor (adjustment level): Page 133
HS alarm use, HS alarm latch, HS alarm hysteresis (advanced function set-
ting level): Page 174
hs1 HS Alarm 1
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Setting range Unit Default
0.0 to 50.0 A 50.0
Function
Setting
See
See
hs2 HS Alarm 2
Heater burnout and HS alarms must
be supported (two CTs).
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Setting range Unit Default
0.0 to 50.0 A 50.0
Function
Setting
See
See