User Manual

135
Adjustment Level Section 5-4
This parameter sets the current for the HS alarm to be output.
The HS alarm is output when the heater current value goes above the set-
ting of this parameter.
When the set value is 50.0, the HS alarm is turned OFF. When the set
value is 0.0, the HS alarm will turn ON.
Related Parameters
Leakage current 1 monitor (adjustment level): Page 133
HS alarm, HS alarm latch, HS alarm hysteresis (advanced function setting
level): Page 174
This parameter sets the current for the HS alarm to be output.
The HS alarm is output when the heater current value goes above the set-
ting of this parameter.
When the set value is 50.0, the HS alarm is turned OFF. When the set
value is 0.0, the HS alarm will turn ON.
Related Parameters
Leakage current 2 monitor (adjustment level): Page 133
HS alarm use, HS alarm latch, HS alarm hysteresis (advanced function set-
ting level): Page 174
hs1 HS Alarm 1
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Setting range Unit Default
0.0 to 50.0 A 50.0
Function
Setting
See
See
hs2 HS Alarm 2
Heater burnout and HS alarms must
be supported (two CTs).
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Setting range Unit Default
0.0 to 50.0 A 50.0
Function
Setting
See
See