User Manual

134
Adjustment Level Section 5-4
This parameter sets the current for the heater burnout alarm to be output.
The heater burnout alarm is output when the heater current value falls
below the setting of this parameter.
When the set value is 0.0, the heater burnout alarm is turned OFF. When
the set value is 50.0, the heater burnout alarm will turn ON.
Related Parameters
Heater current 1 monitor (adjustment level): Page 132
Heater burnout detection, Heater burnout latch, Heater burnout hysteresis
(advanced function setting level): Page 163
This parameter sets the current for the heater burnout alarm to be output.
The heater burnout alarm is output when the heater current value falls
below the setting of this parameter.
When the set value is 0.0, the heater burnout alarm is turned OFF. When
the set value is 50.0, the heater burnout alarm will turn ON.
Related Parameters
Heater current 2 monitor (adjustment level): Page 132
Heater burnout detection, Heater burnout latch, Heater burnout hysteresis
(advanced function setting level): Page 163
hb1 Heater Burnout Detection 1
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “heater burnout detection”
parameter must be set to ON.
Setting range Unit Default
0.0 to 50.0 A 0.0
Function
Setting
See
See
hb2 Heater Burnout Detection 2
Heater burnout and HS alarms must
be supported (two CTs).
Alarm 1 must be assigned.
The “heater burnout failure” parame-
ter must be set to ON.
Setting range Unit Default
0.0 to 50.0 A 0.0
Function
Setting
See
See