Adjustment Level Section 5-4
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
This parameter measures and displays the heater current when the heater is
OFF.
HS are not detected if the control output (heating) OFF time is 190 ms or
less.
ffff is displayed when 55.0 A is exceeded.
If an SSR short-circuit is detected, the HA indicator will light, and the rela-
tive setting level will flash on the No. 1 display.
Related Parameters
HS alarm 1, HS alarm 2 (adjustment level): Page 135
HS alarm use (advanced function setting level): Page 174
Error Displays lcr1: Page 206
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
This parameter measures and displays the heater current value.
HS are not detected if the control output (heating) OFF time is 190 ms or
less.
ffff is displayed when 55.0 A is exceeded.
If an SSR short-circuit is detected, the HA indicator will light, and the rela-
tive setting level will flash on the No. 1 display.
Related Parameters
HS alarm 1, HS alarm 2 (adjustment level): Page 135
HS alarm use (advanced function setting level): Page 174
Error Displays lcr2: Page 206
lcr1 Leakage Current 1 Monitor
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Monitor range Unit
0.0 to 55.0 A
Function
Monitor
See
See
lcr2 Leakage Current 2 Monitor
Heater burnout and HS alarms must
be supported (two CTs).
Alarm 1 must be assigned.
The “HS alarm” parameter must be
set to ON.
Monitor range Unit
0.0 to 55.0 A
Function
Monitor
See
See