User Manual
126
Operation Level Section 5-3
■ Related Parameters
Input type: Page 146, Scaling upper limit, Scaling lower limit, Decimal point
(initial setting level): Page 148 (initial setting level)
Alarm 3 type (initial setting level): Page 154
Standby sequence reset: Page 161, Alarm 3 open in alarm: Page 162, Alarm
3 hysteresis: Page 163, Alarm 3 latch: Page 167 (advanced function setting
level)
These parameters independently set the alarm value upper and lower limits
when the mode for setting the upper and lower limits is selected for the “alarm
1 type” parameter (initial setting level).
• This parameter sets the upper and lower limit values of alarm 1.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the “decimal
point” parameter setting.
■ Related Parameters
Input type: Page 146, Scaling upper limit, Scaling lower limit, Decimal point:
Page 148, Alarm 1 type: Page 152 (initial setting level), Standby sequence
reset: Page 161, Alarm 1 open in alarm: Page 162, Alarm 1 hysteresis: Page
163, Alarm 1 latch: Page 167 (advanced function setting level
These parameters independently set the alarm value upper and lower limits
when the mode for setting the upper and lower limits is selected for the “alarm
2 type” parameter (initial setting level).
• This parameter sets the upper and lower limit values of alarm 2.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the “decimal
point” parameter setting.
See
See
al1h Alarm Value Upper Limit 1
Alarm 1 must be assigned.
Alarm 1 type must be set to upper
and lower limits, upper and lower
limit range, or upper- and lower-limit
with standby sequence.
al1l Alarm Value Lower Limit 1
Setting range Unit Default
−1999 to 9999 EU 0
Function
Setting
See
See
al2h Alarm Value Upper Limit 2
Alarm 2 must be assigned.
Alarm 2 type must be set to upper
and lower limits, upper and lower
limit range, or upper- and lower-limit
alarm with standby sequence.
al2l Alarm Value Lower Limit 2
Setting range Unit Default
−1999 to 9999 EU 0
Function
Setting