Operation Level Section 5-3
This parameter measures the heater current from the CT input used for
detecting heater burnout.
This parameter measures and displays the heater current value.
Heater burnouts are not detected if the control output (heating) ON time is
190 ms or less.
ffff is displayed when 55.0 A is exceeded.
If a heater burnout is detected, the HA indicator will light, and the relative
setting level will flash on the No. 1 display.
Related Parameters
Heater burnout detection 1, Heater burnout detection 2 (adjustment level):
Page 134
Heater burnout (advanced function setting level): Page 163
Error Displays ct2: Page 206
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
The heater current is measured and the leakage current 1 monitor is dis-
played.
HS are not detected if the control output (heating) OFF time is 190 ms or
less.
ffff is displayed when 55.0 A is exceeded.
If an SSR short-circuit is detected, the HA indicator will light, and the rela-
tive setting level will flash on the No. 1 display.
Related Parameters
HS alarm 1, HS alarm 2 (adjustment level): Page 135
Failure detection (advanced function setting level): Page 174
Error Displays lcr1: Page 206
ct2 Heater Current 2 Value Monitor
Heater burnout and HS alarms must
be supported (two CTs).
Alarm 1 must be assigned.
The “heater burnout detection”
parameter must be set to ON.
Monitor range Unit
0.0 to 55.0 A
Function
Monitor
See
See
lcr1 Leakage Current 1 Monitor
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The “HS alarm use” parameter must
be set to ON.
Monitor range Unit
0.0 to 55.0 A
Function
Monitor
See
See