User Manual
xvi
Control
output 1
Relay E5CN-R@@
SPST-NO, 250 VAC, 3 A (resistive load)
Electrical life: 100,000 operations min.
E5CN-R@@
SPST-NO, 250 VAC, 3 A (resistive load)
Electrical life: 100,000 operations min.
E5CN-R@@U
SPDT, 250 VAC, 3 A (resistive load)
Electrical life: 100,000 operations min.
E5CN-R@@U
SPDT, 250 VAC, 3 A (resistive load)
Electrical life: 100,000 operations min.
E5AN-R@@
SPST-NO, 250 VAC, 5 A (resistive load)
Electrical life: 100,000 operations min.
E5AN-R@@
SPST-NO, 250 VAC, 5 A (resistive load)
Electrical life: 100,000 operations min.
E5EN-R@@
SPST-NO, 250 VAC, 5 A (resistive load)
Electrical life: 100,000 operations min.
E5EN-R@@
SPST-NO, 250 VAC, 5 A (resistive load)
Electrical life: 100,000 operations min.
Long-life
relay
(No model with long-life relays) E5CN-Y@@ (Added models with long-life relay out-
puts.)
SPST-NO, 250 VAC, 3 A (resistive load)
Electrical life: 1,000,000 operations min.
DC loads cannot be connected.
Voltage E5CN-Q@@
12 VDC ±15% (PNP)
Max. load current: 21 mA
With short-circuit protection
E5CN-Q@@
12 VDC ±15% (PNP)
Max. load current: 21 mA
With short-circuit protection
E5AN-Q@@
12 VDC +15%/−20% (PNP)
Max. load current: 40 mA
With short-circuit protection
E5AN-Q@@
12 VDC +15%/−20% (PNP)
Max. load current: 40 mA
With short-circuit protection
E5EN-Q@@
12 VDC +15%/−20% (PNP)
Max. load current: 40 mA
With short-circuit protection
E5EN-Q@@
12 VDC +15%/−20% (PNP)
Max. load current: 40 mA
With short-circuit protection
Current E5CN-C@@
4 to 20 mA DC
Load: 600 Ω max.
Resolution: Approx. 2,600
E5CN-C@@
4 to 20 mA DC or 0 to 20 mA DC
Load: 600 Ω max.
Resolution: Approx. 2,700
E5AN-C@@
4 to 20 mA DC
Load: 600 Ω max.
Resolution: Approx. 2,600
E5AN-C@@
4 to 20 mA DC or 0 to 20 mA DC
Load: 600 Ω max.
Resolution: Approx. 2,700
E5EN-C@@
4 to 20 mA DC
Load: 600 Ω max.
Resolution: Approx. 2,600
E5EN-C@@
4 to 20 mA DC or 0 to 20 mA DC
Load: 600 Ω max.
Resolution: Approx. 2,700
Control
output 2
Long-life
relay
--- E5AN/EN-@Y@ (Added models with long-life relay
outputs.)
SPST-NO, 250 VAC, 3 A (resistive load)
Electrical life: 1,000,000 operations min.
DC loads cannot be connected.
Voltage (No models with two control outputs) E5CN-@Q@
12 VDC ±15% (PNP)
Max. load current: 21 mA
With short-circuit protection
(No models with two control outputs) E5AN/EN-@Q@
12 VDC +15%/−20% (PNP)
Max. load current: 21 mA
With short-circuit protection
Item Previous models Improved models