Using the Simple Program Function Section 4-15
Operation Level
Initial Setting Level
1. Press the O key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
2. Select the “program pattern” parameter by pressing the M key.
3. Use the U key to set the parameter to STOP.
Operation Level
4. Press the O key for at least one second to move from the initial setting
level to the operation level.
Adjustment Level
5. Press the O key to move from the operation level to the adjustment level.
Adjustment Level
6. Select the “soak time” parameter by pressing the M key.
7. Use the U key to set the parameter to 10. (The soak time unit is set in
“soak time unit” parameter in the advance function setting level. The de-
fault is m (minutes).
Adjustment Level
8. Select the “wait band” parameter by pressing the M key.
9. Use the U key to set the parameter to 3.0.
Operation Level
10. Press the O key to move from the adjustment level to the operation level.
C
25
100
PV/SP
in-t
5
Input type
ptrn
off
Program Pattern
ptrn
stop
C
25
100
PV/SP
l.adj
Adjustment level
display
soak
1
Soak time
soak
10
wt-b
off
Wait band
wt-b
3.0
C
25
100
PV/S
P