User Manual
xv
■ Ratings
Item Previous models Improved models
Power con-
sumption
E5CN 7 VA (100 to 240 VAC, 50/60 Hz)
4 VA/3 W (24 VAC, 50/60 Hz or 24 VDC)
7.5 VA (100 to 240 VAC, 50/60 Hz)
5 VA/3 W (24 VAC, 50/60 Hz or 24 VDC)
E5CN-U 6 VA (100 to 240 VAC, 50/60 Hz)
3 VA/2 W (24 VAC, 50/60 Hz or 24 VDC)
6 VA (100 to 240 VAC, 50/60 Hz)
3 VA/2 W (24 VAC, 50/60 Hz or 24 VDC)
E5AN 9 VA (100 to 240 VAC, 50/60 Hz)
5 VA/4 W (24 VAC, 50/60 Hz or 24 VDC)
11 VA
5.5 VA/4 W
E5EN 9 VA (100 to 240 VAC, 50/60 Hz)
5 VA/4 W (24 VAC, 50/60 Hz or 24 VDC)
10 VA
5.5 VA/4 W
Sensor input E5@N-@@TC
Thermocouple: K, J, T, E, L, U, N, R, S, or B
Infrared temperature sensor: 10 to 70°C,
60 to 120°C or 115 to 165°C (160 to
260°C)
Voltage input: 0 to 50 mV
E5@N-@@T (Multi-input models)
Thermocouple: K, J, T, E, L, U, N, R, S, or B
Infrared temperature sensor: 10 to 70°C,
60 to 120°C or 115 to 165°C (140 to 260°C)
Voltage input: 0 to 50 mV
Platinum resistance thermometer:
Pt100 or JPt100
E5@N-@@P
Platinum resistance thermometer: Pt100 or
JPt100
(No models with analog inputs) E5@N-@@L (Models with analog inputs added.)
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V