Using the Simple Program Function Section 4-15
4-15 Using the Simple Program Function
4-15-1 Simple Program Function
The simple program function can be used for the following type of control.
The program will start when the “program start” parameter is changed
from RSET to STRT. END will be displayed on the No. 2 display and the
output assigned as the program end output will turn ON after the time set
in the “soak time” parameter has expired in the wait band. The “program
pattern” parameter can be used to select moving to STOP mode or con-
tinuing operation in RUN mode after the program ends.
Parameters Related to the Simple Program Function
Note (1) Set for Controllers with Thermocouple/Resistance Thermometer Multi-in-
puts. Set “none” as the unit for Controllers with Analog Inputs.
(2) The setting unit of the “wait band” parameter is %FS for Controllers with
Analog Inputs and the setting range is OFF or 0.01 to 99.99.
RSET STRT
PV
SP
Set point
Wait band
Wait band
Soak time END display
END output
Select either
STOP or RUN.
Parameter name Symbol Set (monitor) values Unit Display level
Program pattern ptrn OFF, STOP, CONT --- Initial setting level
Program start prst RSET, STRT --- Operation level
Soak time soak 1 to 9999 min or h Adjustment level
Soak time unit t-u m (minutes)/h (hours) --- Advanced function set-
ting level
Wait band wt-b OFF or 0.1 to 999.9 (See note 2.) °C or °F (See notes 1
and 2.)
Adjustment level
Soak time remain
monitor
sktr 0 to 9999 min or h Operation level