User Manual

80
Using Event Inputs Section 4-5
4-5-5 Switching between Auto and Manual Control
When the “event input assignment 1” or “event input assignment 2” parameter
is set to MANU (auto/manual), manual control will start when event input 1 or
2 turns ON. Auto control will start when the input turns OFF.
The MANU indicator will light during manual control.
4-5-6 Controlling the Start of the Simple Program Function
When the “event input assignment 1” or “event input assignment 2” parameter
is set to PRST (program start), the program will start when event input 1 or 2
turns ON. The program will be reset when the input turns OFF and the RUN/
STOP status will automatically switch to STOP mode. If the program END out-
put is ON, the program END output will turn OFF.
Note The specified event input function can be used when the “number of multi-SP
uses” parameter is set to 0 or 1 (i.e., when it is not set for the set point set-
ting).
Event input assignments 1 and 2 are as follows according to the setting of the
“number of multi-SP uses” parameter:
Note One of the settings.
Parameters
Setting Input contact Status
Event input 1 or 2 OFF Automatic
Event input 1 or 2 ON Manual
Setting Input contact Status
Event input 1 or 2 OFF Reset
Event input 1 or 2 ON Start
Parameter Setting Event inputs
Event input
assignment 1
Event input
assignment 2
Function of event
input 1
Function of event
input 2
Number of
multi-SP
uses
0
Event input assignment
(See note.)
Event input assignment
(See note.)
Specified event input
function
Specified event input
function
NONE
Event input assignment None Specified event input
function
Event input assignment NONE Specified event input
function
None
NONE NONE None None
1 --- (Setting data not dis-
played.)
Event input assignment Multi-SP, 2 points
(switching set points 0
and 1)
Specified event input
function
--- (Setting data not dis-
played.)
NONE Multi-SP, 2 points
(switching set points 0
and 1)
None
2 --- (Setting data not dis-
played.)
--- (Setting data not dis-
played.)
Multi-SP, 4 points (switching set points 0, 1, 2, 3)
Symbol Parameter: Level Description
ev-1 Event input assignment 1: Advanced function setting
level
Function of
event input func-
tion
ev-2 Event input assignment 2: Advanced function setting
level
ev-m Number of multi-SP uses: Advanced function setting
level