User Manual

79
Using Event Inputs Section 4-5
4-5-3 Settings
Switching between Set Points 0, 1, 2, and 3
Operating Procedure The following example sets the “number of multi-SP uses” parameter to 2.
Set points 0, 1, 2 and 3 will be set according to the ON/OFF states of event
inputs 1 and 2.
4-5-4 Executing Run/Stop Control
When the “event input assignment 1” or “event input assignment 2” parameter
is set to STO (RUN/STOP), control is started when event input 1 or 2 turns
OFF. Control is stopped when the input turns ON. Alarm outputs, however, will
be according to the process value.
The STOP indicator will light while control is stopped.
Operation Level
1. Press the O key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
2. Select the “move to advanced function setting level” parameter by press-
ing the M key.
3. Use the D key to enter “
169” (the password).
Advanced Function Setting Level
Move to the advanced function setting level by pressing the M key or
leaving the setting for at least two seconds.
Number of Multi-SP Uses Setting
4. Select the “number of multi-SP uses” parameter by pressing the M key.
5. Use the U key to set the parameter to 2.
6. To return to the initial setting level, press the O key for at least one sec-
ond.
7. To return to the operation level, press the O key for at least one second.
C
25
100
PV/SP
in-t
5
Input type
amov
-169
init
off
Parameter
initialization
ev-m
1
Number of
multi-SP uses
ev-m
2
E5CN
EV2
EV2
EV1
EV1
+
+
E5AN/EN
EV2
EV1
EV2
EV1
+
+
Setting Input contact Status
Event input 1 or 2 ON STOP
Event input 1 or 2 OFF RUN