User Manual
78
Using Event Inputs Section 4-5
4-5-2 How to Use the Multi-SP Function
The multi-SP function allows you to set up to four set points (SP 0 to 3) in the
adjustment level. The set point can be switched by operating the keys on the
front panel or by using external input signals (event inputs).
Using Event Inputs Event inputs can be used if the Controller supports the event input function
and if the “number of multi-SP uses” parameter is set to 1 or 2.
■ Number of Multi-SP Uses = 1
■ Number of Multi-SP Uses = 2
Note Event inputs can be used on E5@N-@@@B@ Controllers. Turn the event
inputs ON or OFF while the E5AN is turned ON. Event input ON/OFF changes
are detected for inputs of 50 ms or longer.
Using Key Operations You can select any of the set points 0 to 3 by changing the set value of the
“multi-SP uses” parameter. The “multi-SP uses” display conditions are as fol-
lows:
• If the Controller does not support event inputs, the “multi-SP uses” param-
eter must be set to ON.
• If the Controller supports event inputs, the “number of multi-SP uses”
parameter must be set to 0 and the “multi-SP uses” parameter must be
set to ON.
The following table shows the relationship between the “multi-SP uses”
parameter set value and the selected set point.
Note The set point can also be switched using communications.
Event input 1 Selected set point
OFF Set point 0
ON Set point 1
Event input 1 Event input 2 Selected set point
OFF OFF Set point 0
ON OFF Set point 1
OFF ON Set point 2
ON ON Set point 3
Multi-SP Selected set point
0Set point 0
1Set point 1
2Set point 2
3Set point 3