Cat. No.
E5CN/E5CN-U/E5AN/E5EN Digital Temperature Controller User’s Manual Revised November 2005
Preface OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The E5CN, E5CN-U, E5AN, and E5EN are Digital Temperature Controllers. The E5CN and E5CN-U are both compact temperature controllers, with the E5CN featuring screw terminal connections, and the E5CN-U featuring socket pin connections.
Read and Understand this Manual Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request.
Safety Precautions ■ Definition of Precautionary Information The following notation is used in this manual to provide precautions required to ensure safe usage of the product. The safety precautions that are provided are extremely important to safety. Always read and heed the information provided in all safety precautions. The following notation is used. CAUTION Indicates a potentially hazardous situation which, if not avoided, is likely to result in minor or moderate injury or in property damage.
■ Safety Precautions CAUTION Do not touch the terminals while power is being supplied. Doing so may occasionally result in minor injury due to electric shock. Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to enter the product. Doing so may occasionally result in electric shock, fire, or malfunction. Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from explosion may occasionally occur.
CAUTION Tighten the terminal screws to between 1.13 and 1.36 N·m. Loose screws may occasionally result in fire. (See note.) Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may occasionally result in property damage or accidents. A malfunction in the Temperature Controller may occasionally make control operations impossible or prevent alarm outputs, resulting in property damage.
Precautions for Safe Use Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the performance and functions of the product. Not doing so may occasionally result in unexpected events. 1) The product is designed for indoor use only. Do not use the product outdoors or in any of the following locations. • Places directly subject to heat radiated from heating equipment. • Places subject to splashing liquid or oil atmosphere.
14) Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol. 15) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after power ON. 16) The output may turn OFF when shifting to certain levels. Take this into consideration when performing control. 17) The number of EEPROM write operations is limited. Therefore, use RAM write mode when frequently overwriting data during communications or other operations.
Precautions for Operation 1) 2) 3) 4) It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON. Due consideration must be given to this time when incorporating Temperature Controllers into a control panel or similar device. Make sure that the Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display.
Improved Functions Functional upgrades have been implemented for E5CN/CN-U Digital Temperature Controllers of lot number 01440 (manufactured 1 April 2004) or later, and for E5AN/EN Digital Temperature Controllers of lot number 01150 (manufactured 1 January 2005) or later. The previous and improved models can be distinguished by the front panel, as shown below.
■ Ratings Item Power con- E5CN sumption E5CN-U E5AN E5EN Sensor input Previous models 7 VA (100 to 240 VAC, 50/60 Hz) 4 VA/3 W (24 VAC, 50/60 Hz or 24 VDC) 6 VA (100 to 240 VAC, 50/60 Hz) 3 VA/2 W (24 VAC, 50/60 Hz or 24 VDC) 9 VA (100 to 240 VAC, 50/60 Hz) 5 VA/4 W (24 VAC, 50/60 Hz or 24 VDC) 9 VA (100 to 240 VAC, 50/60 Hz) 5 VA/4 W (24 VAC, 50/60 Hz or 24 VDC) E5@N-@@TC Thermocouple: K, J, T, E, L, U, N, R, S, or B Infrared temperature sensor: 10 to 70°C, 60 to 120°C or 115 to 165°C (160 to 260°C) Volta
Control output 1 Item Relay Long-life relay Voltage Current Control output 2 Long-life relay Voltage Previous models E5CN-R@@ SPST-NO, 250 VAC, 3 A (resistive load) Electrical life: 100,000 operations min. E5CN-R@@U SPDT, 250 VAC, 3 A (resistive load) Electrical life: 100,000 operations min. E5AN-R@@ SPST-NO, 250 VAC, 5 A (resistive load) Electrical life: 100,000 operations min. E5EN-R@@ SPST-NO, 250 VAC, 5 A (resistive load) Electrical life: 100,000 operations min.
Display method Item E5CN E5AN/EN Transfer output Previous models 7-segment digital display and single-LED indicators Character height: PV: 9.9 mm, SV: 6.4 mm 7-segment digital display and single-LED indicators (No models with transfer outputs) Improved models 11-segment digital display and single-LED indicator (Improved visibility) (A 7-segment digital display also possible.) Character height: PV: 11.0 mm, SV: 6.
Conventions Used in This Manual Model Notations “E5CN, E5CN-U, E5AN, and E5EN” is used when the information being provided applies to all E5CN@@@, E5CN-@@@U, E5AN-@@@, or E5EN-@@@ Digital Temperature Controllers. The notation used in the manual (e.g., for model designations in SECTION 5 Parameters) for information that is restricted by the model is given in the following table.
How to Read Display Symbols The following tables show the correspondence between the symbols displayed on the displays and alphabet characters. The default is for 11-segment displays. a b c d e f g h i j k l m A B C D E F G H I J K L M n o p q r s t u v w x y z N O P Q R S T U V W X Y Z The “character select” parameter in the advanced function setting level can be turned OFF to display the following 7-segment characters.
xx
TABLE OF CONTENTS SECTION 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1-1 Names of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1-2 I/O Configuration and Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1-3 Setting Level Configuration and Key Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TABLE OF CONTENTS SECTION 5 Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 5-1 Conventions Used in this Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 5-2 Protect Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 5-3 Operation Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About this Manual: This manual describes the E5CN/CN-U/AN/EN Digital Temperature Controllers and includes the sections described below. Please read this manual carefully and be sure you understand the information provided before attempting to set up or operate an E5CN/CN-U/AN/EN Digital Temperature Controller. • Overview Section 1 introduces the features, components, and main specifications of the E5CN/CN-U/AN/EN Digital Temperature Controllers.
xxiv
SECTION 1 Introduction This section introduces the features, components, and main specifications of the E5CN and E5CN-U Digital Temperature Controllers. 1-1 1-2 1-3 1-4 Names of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1-1-1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1-1-2 Meanings of Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 1-1 Names of Parts 1-1 Names of Parts 1-1-1 Front Panel E5CN/CN-U The front panel is the same for the E5CN and E5CN-U. Temperature unit PV ALM1 ALM2 ALM3 Operation indicators No. 1 display HA SV OUT1 STOP No. 2 display OUT2 CMW MANU Up Key Level Key E5CN Mode Key Down Key E5AN Temperature unit No. 1 display Operation indicators No.
Section 1-1 Names of Parts E5EN Operation indicators No. 1 display Temperature unit No. 2 display Operation indicators Mode Key Level Key 1-1-2 Down Key Up Key Meanings of Indicators No. 1 Display Displays the process value or parameter type. Lights for approximately one second during startup. No. 2 Display Displays the set point, parameter operation read value, or the variable input value. Lights for approximately one second during startup. Operation Indicators 1,2,3... 1.
Section 1-1 Names of Parts 7. Temperature Unit (Key) Lights when settings change protect is ON (i.e., when the U and D keys are disabled by protected status. The temperature unit is displayed when parameters are set to display a temperature. The display is determined by the currently selected “temperature unit” parameter set value. c indicates °C and f indicates °F. Flashes during ST operation. 1-1-3 Using the Keys This section describes the basic functions of the front panel keys.
Section 1-2 I/O Configuration and Main Functions 1-2 I/O Configuration and Main Functions 1-2-1 I/O Configuration E5CN Control section Temperature input or analog input Control output 1 Control output 1 Control output 2 Control output 2 Heating/cooling CT1 input External power supply for ES1B Alarm output 3 CT2 input Alarm output 2 Event inputs 2 channels Alarm output 2 Alarm output 1 Set point input functions from external digital switches: RUN/STOP Program Start Auto/Manual HBA Alarm ou
Section 1-2 I/O Configuration and Main Functions E5CN-U Control section Temperature input or analog input Control output 1 Control output 2 Control output 1 Heating/ cooling Alarm output 3 Alarm output 2 Standard Alarm output 2 Alarm output 1 Alarm output 1 Input error Simple program END output Q2T-U Note Basic model number Functions can be assigned individually for each output by changing the set values for the control output 1 assignment, the alarm 1 assignment, and the alarm 2 assignment in t
Section 1-2 I/O Configuration and Main Functions E5AN/EN Control section Temperature input or analog input Control output 1 Control output 1 Control output 2 Control output 2 Heating/cooling External power supply for ES1B CT1 input CT2 input Alarm output 3 Alarm output 3 Alarm output 2 Alarm output 2 Alarm output 1 HBA Event inputs 2 channels Alarm output 1 HS alarm Set point input functions from external digital switches: RUN/STOP Program Start Auto/Manual Input error Simple program END o
Section 1-2 I/O Configuration and Main Functions 1-2-2 Main Functions This section introduces the main E5CN/CN-U/AN/EN functions. For details on particular functions and how to use them, refer to SECTION 3 Basic Operation and following sections.
I/O Configuration and Main Functions Section 1-2 • When the “input error output” parameter is set to ON, alarm output 1 turns ON when an input error occurs. Control Adjustment • Optimum PID constants can be set easily by performing AT (auto-tuning) or ST (self-tuning). Event Inputs • With the E5@N-@@@B, the following functions can be executed using event inputs: switching set points (multi-SP, 4 pts. max.
Section 1-3 Setting Level Configuration and Key Operations 1-3 Setting Level Configuration and Key Operations Parameters are divided into groups, each called a “level.” Each of the set values (setting items) in these levels is called a “parameter.” The parameters on the E5CN/CN-U/AN/EN are divided into the following eight levels. When the power is turned ON, all of the display lights for approximately one second. Power ON Started in manual mode. Started in automatic mode.
Setting Level Configuration and Key Operations Section 1-3 Of these levels, the initial setting level, communications setting level, advanced function setting level, and calibration level can be used only when control is stopped. Control outputs are stopped when any of these four levels is selected. Protect Level • To switch to the protect level from either the operation level or the adjustment level, simultaneously hold down the O and M keys for at least 3 seconds. (See note.
Section 1-3 Setting Level Configuration and Key Operations • This level is for setting the display auto-return time, event input assignments, standby sequence, and alarm hysteresis, and it is the level for moving to the user calibration. Communications Setting Level • To move to the communications setting level from the initial setting level, press the O key once (for less than 1 s). When using the communications function, set the communications conditions in this level.
Section 1-4 Communications Function • When you turn the power OFF, you must first fix the settings (by pressing the M key). The settings are sometimes not changed by merely pressing the U or D keys. 1-4 Communications Function The E5CN/AN/EN is provided with a communications function that enables parameters to be checked and set from a host computer. If the communications function is required, use a model that has that function (E5@N-@@@03 and E5AN/EN-@@@01).
Section 1-4 Communications Function Setting Communications Data Match the communications specifications of the E5CN/AN/EN and the host computer. If a 1:N connection is being used, ensure that the communications specifications for all devices in the system (except the communications Unit No.) are the same. Parameter Protocol setting Symbol psel Setting (monitor) value CompoWay/F (SYSWAY), Modbus Communications Unit No. u-no 0 to 99 Communications baud rate bps 1.2, 2.4, 4.8, 9.6, 19.2, 38.4 1.
SECTION 2 Preparations This section describes the work required to prepare the E5CN and E5CN-U Digital Temperature Controllers for operation, including installation and wiring. 2-1 2-2 2-3 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2-1-1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2-1-2 Panel Cutout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 2-1 Installation 2-1 Installation 2-1-1 Dimensions Unit: mm E5CN 44.8 × 44.8 48 × 48 E5CN-U 48 × 48 44.8 × 44.
Section 2-1 Installation E5EN 2-1-2 Panel Cutout Unit: mm E5CN/CN-U Individual Mounting Group Mounting (48 × number of Units − 2.5) +1.0 60 min. 0 E5AN Individual Mounting Group Mounting (96 × number of Units − 3.5) +1.0 120 min.
Section 2-1 Installation E5EN Individual Mounting Group Mounting (48 × number of Units − 2.5) +1.0 120 min. 0 • Waterproofing is not possible when group mounting several Controllers. • The recommended panel thickness is 1 to 5 mm for E5CN/E5CN-U, and 1 to 8 mm for E5AN/E5EN. • Units must not be closely mounted vertically. (Observe the recommended mounting space limits.
Section 2-1 Installation Mounting to the Panel 1,2,3... 1. For waterproof mounting, waterproof packing must be installed on the Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. There is no waterproof packing included with the E5CN-U. 2. Insert the E5CN/E5CN-U into the mounting hole in the panel. 3.
Section 2-1 Installation 2-1-4 Removing the Temperature Controller from the Case The Temperature Controller can be removed from the case to perform maintenance without removing the terminal leads. This is possible for only the E5CN, E5AN, and E5EN, and not for the E5CN-U. Check the specifications of the case and Temperature Controller before removing the Temperature Controller from the case. E5CN Tool insertion hole Flat-blade screwdriver (Unit: mm) (1) 20 min.
Section 2-2 Wiring Terminals 3. When inserting the E5AN/E5EN Temperature Controller, check to make sure that the sealing rubber is in place. Then, while pushing the front panel into place, turn the Phillips screwdriver to the right in the opposite direction used when removing the panel to tighten the screws on the top and bottom surfaces (tightening torque: 0.3 to 0.5 N·m). Make sure that electronic components do not come into contact with the case.
Section 2-2 Wiring Terminals E5CN-U Relay output SPDT 250 VAC, 3 A (Resistive load) Control output 1 + Voltage output A 12 VDC, 21 mA B Alarm output (Relay output), 250 VAC, 1 A (Resistive load) 6 5 7 4 Alarm output 1/ input error 8 Alarm output 2 Control output 2 9 3 2 B 10 1 + 11 Input power supply TC/Pt Multi-input Note 100 to 240 VAC 24 VAC/DC (no polarity) For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.
Section 2-2 Wiring Terminals 2-2-3 Wiring In the connection diagrams, the left side of the terminal numbers represents the inside of the Controller and the right side represents the outside. Power supply • With the E5CN, connect to terminals 9 and 10; with the E5CN-U, connect to pins 10 and 11; with the E5AN and E5EN, connect pins 1 and 2. The following table shows the specifications. Input power supply 100 to 240 VAC, 50/60 Hz E5CN 7.
Section 2-2 Wiring Terminals +V +V +V 1 1 + L 2 GND 2 Relay 4 5 GND 5 6 6 1 + L 2 − − Current E5CN +v + L + − Voltage Relay − Voltage E5CN-U +v + + L GND Relay 4 L − − Voltage Current E5AN/EN • The following table shows the specifications for each output type.
Section 2-2 Wiring Terminals measures to prevent excessive temperature rise and spreading of fire. Take countermeasures such as installing a surge absorber. As an additional safety measure, provide error detection in the control loop. (Use the Loop Break Alarm (LBA) and HS alarm that are provided for the E5@N.) Varistor Long-life relay output Inductive load 1 Varistor 2 Select a surge absorber that satisfies the following conditions.
Section 2-2 Wiring Terminals • Long-life relay outputs use semiconductors for switching when closing and opening the circuit, thereby reducing chattering and arcing and improving durability. However, if high levels of noise or surge are imposed between the output terminals, short-circuit faults may occasionally occur. If the output becomes permanently shorted, there is the danger of fire due to overheating of the heater.
Section 2-2 Wiring Terminals ALM2 ALM1, input error ALM1, HBA/HS alarm, input error ALM2 E5CN E5CN-U ALM3 ALM2 ALM1, HBA/HS alarm, input error E5AN/EN • The relay specifications are as follows: CT Inputs E5CN/CN-U SPST-NO 250 VAC 1 A E5AN/EN SPST-NO 250 VAC 3 A • When the HBA or the HS alarm is to be used with the E5CN-@@H@ or the E5CN-@@HH@, connect a current transformer (CT) across terminals 14 and 15 or terminals 13 and 15 (no polarity).
Section 2-2 Wiring Terminals − + EV1 + + EV2 EV2 − E5CN-@@@B Communications EV1 + E5AN/EN-@@@B RS-485 • When communications are to be used with the E5@N-@@@03, connect communications cable across terminals 11 and 12. 11 B (+) 12 A (−) RS-485 E5@N-@@@03 Specify both ends of the transmission path including the host computer as end nodes (that is, connect terminators to both ends). The minimum terminal resistance is 54 Ω.
Section 2-2 Wiring Terminals RS-232C (E5AN/EN Only) • When communications are to be used with the E5AN/EN-@@@01@, connect communications cable across terminals 11 to 13. SD RD RS-232C SG E5AN/EN-@@@01@ Host computer RS-232C: 25-pin E5AN/EN Host computer (DOS/V) RS-232C: 9-pin E5AN/EN RS-232C RS-232C SD (TXD) RD (RXD) RS (RTS) CS (CTS) DR (DSR) SG No. 11 SD 12 RD 13 SG 2 3 4 5 6 7 DR (DSR) RS (RTS) CS (CTS) ER (DTR) 20 FG RD (RXD) SD (TXD) ER (DTR) SG No.
Section 2-3 Using the Support Software Port Note 2-3 Contact your OMRON representative for information on using the external power supply for ES1B for other applications. The external power supply for ES1B cannot be used on E5CN-C (Current Output Model). Using the Support Software Port Use the communications port for Support Software to connect the personal computer to the Temperature Controller when using EST2-2C-MV1 CXThermo or other Support Software.
Using the Support Software Port Section 2-3 3. Install the driver. Install the driver to enable the Cable to be used with the personal computer. • Installation When the Cable is connected with the personal computer, the OS detects the product as a new device. At this time, install the driver using the installation wizard. For details on installation methods, refer to the user’s manual for the E58-CIFQ1 USB-Serial Conversion Cable.
Using the Support Software Port 32 Section 2-3
SECTION 3 Basic Operation This section describes the basic operation of the E5CN and E5CN-U Digital Temperature Controllers, including key operations to set parameters and descriptions of display elements based on specific control examples. 3-1 3-2 Initial Setting Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Setting the Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 3-2-1 Input Type . . . . . . . . .
Section 3-1 Initial Setting Examples 3-1 Initial Setting Examples Initial hardware setup, including the sensor input type, alarm types, control periods, and other settings is done using parameter displays. The O and M keys are used to switch between parameters, and the amount of time that you press the keys determines which parameter you move to. This section describes two typical examples. Explanation of Examples Changing Parameters in-t 0 in-h 100 M M A image means that there are parameters.
Section 3-1 Initial Setting Examples Example 2 Input type: 9 (T thermocouple, −200°C to 400°C) Control method: PID control PID constants found using autotuning (AT). Alarm type: 2 upper limit Alarm value 1: 30°C Set point: 150°C Setup Procedure Power ON Power ON Operation Level C 25 PV/SP 0 Press the O key for at least 3 s. Initial Setting Level Control stops. Initial Setting Level Use the U and D keys to select the input type.
Section 3-2 Setting the Input Type 3-2 Setting the Input Type The Controller supports four input types: platinum resistance thermometer, thermocouple, infrared temperature sensor, and analog inputs. Set the input type that matches the sensor that is used. In the product specifications, there are models with thermocouple/resistance thermometer inputs (multi-input) and models with analog input. The settings differ depending on the model. Check to make sure which model you are using.
Section 3-2 Setting the Input Type List of Input Types Input type Controllers Platinum resistance with Therthermometer mocouple/ Resistance Thermometer Multiinput Thermocouple Specifications Set value Pt100 0 1 2 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F) 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) JPt100 3 4 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F) 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) K 5 6 −200 to 1,300 (°C)/−300 to 2,300 (°F) −20.0 to 500.0 (°C)/0.0 to 900.
Section 3-3 Selecting the Temperature Unit 3-3 3-3-1 Selecting the Temperature Unit Temperature Unit • Either °C or °F can be selected as the temperature unit. • Set the temperature unit in the “temperature unit” parameter of the initial setting level. The default is c (°C). Operating Procedure 1. Press the O key for at least three seconds to move from the operation level to the initial setting level. Operation Level C The following example shows how to select °C as the temperature unit.
Section 3-5 Setting Output Specifications 3-5-2 Direct and Reverse Operation • “Direct operation” increases the manipulated variable whenever the process value increases. “Reverse operation” decreases the manipulated variable whenever the process value increases.
Section 3-5 Setting Output Specifications orev Direct/reverse operation or-r 6. To return to the operation level, press the O key for at least one second. Operation Level C 30 5. Select the “direct/reverse operation” parameter by pressing the M key. The default is or-r (reverse operation). To select or-d (direct operation), press the U key. PV/SP 0 3-5-3 Assigned Output Functions • Function assignments can be changed by changing the settings for control and alarm assignments.
Section 3-5 Setting Output Specifications Operating Procedure Operation Level C 25 PV/SP The following example sets the following control and alarm assignments. Control output 1: Control output (heating); Control output 2: Control output (cooling); Alarm output 1: Alarm 1; Alarm output 2: Alarm 2 1. Press the O key for at least three seconds to move from the operation level to the initial setting level. 100 Initial Setting Level in-t Input type 2.
Section 3-6 Setting the Set Point (SP) Advanced Function Setting Level 10. Select the “alarm 1 assignment” parameter by pressing the M key. Control output 1 alm1 assignment alm1 11. Press the U or D key to set alm1. (The default is alm1.) alm1 alm1 Advanced Function Setting Level alm2 12. Select the “alarm 2 assignment” parameter by pressing the M key. Control output 2 assignment alm2 13. Press the U or D key to set alm2. (The default is alm2.) alm2 alm2 Input type 14.
Section 3-7 Using ON/OFF Control C 30 2. Use the U and D keys to set the set point to 200°C. 200 3-7 Using ON/OFF Control In ON/OFF control, the control output turns OFF when the temperature being controlled reaches the preset set point. When the manipulated variable turns OFF, the temperature begins to fall and the control turns ON again. This operation is repeated over a certain temperature range.
Section 3-7 Using ON/OFF Control Parameters Symbol s-hc cntl orev c-db c-sc hys chys 3-7-2 Parameter: Level Standard or heating/cooling: Initial setting level PID ON/OFF: Initial setting level Direct/reverse operation: Initial setting level Dead band: Adjustment level Cooling coefficient: Adjustment level Hysteresis (heating): Adjustment level Hysteresis (cooling): Adjustment level Application Specifying control method Specifying control method Specifying control method Heating/cooling control Heating/c
Determining PID Constants (AT, ST, Manual Setup) Section 3-8 Setting the Hysteresis Operating Procedure 1. Press the O key to move from the operation level to the adjustment level. Operation Level C Set the hysteresis to 2.0°C. 25 PV at AT execute/ cancel 200 2. The “AT execute/cancel” parameter will be displayed in the adjustment level. off C hys Hysteresis (heating) 3. Select the “Hysteresis (heating)” parameter by pressing the M key. 1.0 C hys 2.0 4.
Section 3-8 Determining PID Constants (AT, ST, Manual Setup) AT execute/cancel at at off No. 1 display on AT execution in progress If you move to the operation level during AT execution, the No. 2 display flashes to indicate that AT is being executed. PV/SP C C 25 100 25 100 No. 2 display AT execution in progress Only the “communications writing,” “RUN/STOP,” “AT execution/cancel,” and “program start” parameters can be changed during AT execution. Other parameters cannot be changed.
Section 3-8 Determining PID Constants (AT, ST, Manual Setup) Note Operating Procedure PID Constants When control characteristics are already known, PID constants can be set directly to adjust control. PID constants are set in the “proportional band” (P), “integral time” (I), and “derivative time” (D) parameters in the adjustment level. This procedure executes self-tuning (ST). Input type 1. Press the O key for at least three seconds to move from the operation level to the initial setting level.
Section 3-8 Determining PID Constants (AT, ST, Manual Setup) This procedure sets the ST stable range to 20°C. Advanced Function Setting Level C ST stable st-b range 1. Select the “ST stable range” parameter by pressing the M key in the advanced function setting level. 1%0 C 2. Use the U key to set the parameter to 20°C.
Section 3-8 Determining PID Constants (AT, ST, Manual Setup) • When the temperature (PV) falls short of the set point for the PID constants when using AT or ST in normal mode, executing AT or ST in RT mode tends to improve performance. Temperature Temperature Set value Set value Start of control Time Start of control Time • When the manipulated variable (MV) is saturated, the amount of overshooting may be somewhat higher in comparison to PID control based on AT or ST in normal mode.
Section 3-8 Determining PID Constants (AT, ST, Manual Setup) 3-8-4 Manual Setup Individual PID constants can be manually set in the “proportional band,” “integral time,” and “derivative time” parameters in the adjustment level. Operating Procedure In this example, the “proportional band” parameter is set to 10.0, the “integral time” parameter to 250, and the “derivative time” parameter to 45. 1. Press the O key to move from the operation level to the adjustment level.
Section 3-9 Alarm Outputs When I (Integral Time) Is Adjusted Increased Decreased It takes a long time to reach the set point. It takes time to achieve a stable state, but overshooting, undershooting, and hunting are reduced. Set value Overshooting and undershooting occur. Hunting occurs. The Controller starts up faster.
Section 3-9 Alarm Outputs Set value Alarm type 7 8 9 Lower-limit with standby sequence ON OFF Absolute-value upperlimit ON OFF Absolute-value lower-limit 10 12 X X ON OFF 0 X ON OFF 0 X ON OFF ON OFF 0 X ON OFF LBA (alarm 1 type only) ON OFF SP ON OFF Absolute-value upperlimit with standby sequence Absolute-value lower-limit with standby sequence 11 Note Alarm output operation When alarm value X When alarm value X is positive is negative ON OFF 0 X SP X 0 X 0 X 0 X 0 --- (
Section 3-9 Alarm Outputs 3-9-2 Alarm Values al1l Alarm lower limit value al2l • To set the alarm value upper and lower limits for deviation, set the upper and lower limits in each of the “alarm 1 to 3 upper limit,” and “alarm 1 to 3 lower limit” parameters in the operation level. al3l al1h • Alarm values are indicated by “X” in the table on the previous page. When the upper and lower limits are set independently, “H” is displayed for upper limit values, and “L” is displayed for lower limit values.
Section 3-10 Using HBA and HS Alarms 3-10 Using HBA and HS Alarms 3-10-1 HBA and HS Alarm Operations • Heater burnout detection is executed by measuring heater current while the control output for heating is ON, and HS detection is executed by measuring heater current while it is OFF. For details, refer to the following table. (Heater burnout detection and HS detection cannot be used with the control output for cooling.
Section 3-10 Using HBA and HS Alarms • If there is little difference between the current in normal and abnormal states, detection may become unstable. To stabilize detection, set a current value difference of at least 1.0 A for heaters of less than 10.0 A, and at least 2.5 A for heaters of 10.0 A or more. If the heater current is too low, loop the load line several times through a CT, as shown in the diagram below. Looping it through twice will double the detection current.
Section 3-10 Load Using HBA and HS Alarms Load (such as a heater) Lo ad ad Lo AC line Product To CT input CT CT Product To CT input 3. V connecting lines: Refer to the following diagram for CT installation positions. Heater voltage fluctuations are not considered here, so be take that into account when setting the detection current.
Section 3-10 Using HBA and HS Alarms • Set the total current value for normal heater operation to 50 A or less. When a current value of 55.0 A is exceeded, ffff is displayed in the “heater current 1 (and 2) value monitor” and “leakage current 1 (and 2) monitor” parameters.
Section 3-10 Using HBA and HS Alarms Three-phase Heaters Delta Connecting Lines Example: Using Three 200-VAC, 2-kW Heaters Normal 17.3 A→ 17.3 A→ Load 200 V 200 V ad Lo ad Lo 200 V Product 17.3 A→ To CT input CT Product To CT input The current when each phase is normal is 17.3 A (≈ √3 × 10 A). Burnout Burnout Burnout 10 A→ 15 A→ Product To CT input ad 17.
Section 3-10 Using HBA and HS Alarms Star Connecting Lines Example: Using Three 200-VAC, 2-kW Heaters Normal Load 5.8 A→ 200 V Load (such as a heater) 200 V Lo d ad a Lo 5.8 A→ CT 200 V Product To CT input 5.8 A→ CT Product To CT input The current when each phase is normal is 5.8 A (≈ 10 A × (1 /√3)).
Section 3-10 Using HBA and HS Alarms V Connecting Lines Example: Using Two 200-VAC, 2-kW Heaters Normal 10 A→ CT ad Product To CT input Lo 200 V 17.
Section 3-10 Using HBA and HS Alarms 3-10-5 Settings (HBA) To activate the heater burnout alarm, set the “heater burnout detection” parameter to ON in the advanced function setting level and set the “heater burnout detection 1” and “heater burnout detection 2” parameters in the adjustment level. Operating Procedure This procedure sets the “heater burnout detection 1” parameter to 2.5.
Section 3-10 Using HBA and HS Alarms hb1 8. Select the “heater burnout detection 1” parameter by pressing the M key. Refer to 3-10-3 Calculating Detection Current Values on page 56 when making the settings. Heater burnout detection 1 0.0 9. For this example, set 2.5. To return to the operation level, press the O key for less than one second. hb1 2.
Section 3-10 Using HBA and HS Alarms ■ Operation Level C 25 PV/SP HS Alarm Settings 5. Press the O key for at least one second to move from the advanced function setting level to the initial setting level and then to the operation level. 100 Adjustment Level 6. Press the O key for less than one second to move from the operation level to the adjustment level. Adjustment level l.adj display Leakage current 7. lcr1 1 monitor Select the “leakage current 1 monitor” parameter by pressing the M key.
SECTION 4 Applications Operations This section describes scaling, the SP ramp function, and other special functions that can be used to make the most of the functionality of the E5CN and E5CN-U Digital Temperature Controllers. 4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 Shifting Input Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 4-1-1 Shifting Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66 4-14 Using the Transfer Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 4-14-1 Transfer Output Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 4-15 Using the Simple Program Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 4-15-1 Simple Program Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 4-15-2 Operation at the Program End . . . . . . . . . . . . . . . . . . . .
Section 4-1 Shifting Input Values 4-1 4-1-1 Shifting Input Values Shifting Inputs The input shift matched to the sensor currently selected in the “input type” parameter is displayed. • A 2-point shift is applied for infrared temperature sensors. A 2-point shift can also be used if the “input shift type” parameter (advanced function setting level) is set to INS2 for a thermocouple or platinum resistance thermometer.
Section 4-1 Shifting Input Values Two-point shift insh Upper-limit temperature input shift value insl Lower-limit temperature input shift value • Separate shift values can be set for the upper limit and lower limit of the sensor input range for an infrared sensor as well as for a thermocouple or platinum resistance thermometer with the “input shift type” set to INS2.
Section 4-1 Shifting Input Values (C) Control target Infrared Temperature Sensor Power supply (B) Thermometer Output (A) E5CN/AN/EN Temperature Controller Figure 1 Offset Configuration for an Infrared Temperature Sensor Method for a 1-point Shift 1,2,3... C insh Upper-limit temperature input shift value 2. Check the control target temperature (B) and the Controller readout (A).
Section 4-1 Shifting Input Values Method for a 2-point Shift Use a 2-point input shift if you want to increase the accuracy of the readout values across the range of the sensor. 1,2,3... 1. Shift the Controller readout at two points, near room temperature and near the value at which the temperature of the control target is to be controlled.
Section 4-2 Alarm Hysteresis Upper-limit Temperature Input Shift Value C Upper-limit insh temperature input shift 52.7 4-2 insh = 260 − 40 × {(110 − 105) − (25 − 40)} + (25 − 40) = 52.
Section 4-2 Alarm Hysteresis 4-2-3 Close in Alarm/Open in Alarm • When “close in alarm” is set, the status of the alarm output function will be output as is. When “open in alarm” is set, the status of the alarm output function will be reversed before being output. • Close in alarm/open in alarm can be set separately for each alarm. • Close in alarm/open in alarm is set in the “alarm 1 open in alarm” to “alarm 3 open in alarm” parameters (advanced function setting level).
Section 4-3 Setting Scaling Upper and Lower Limits for Analog Inputs 4-3 Setting Scaling Upper and Lower Limits for Analog Inputs 4-3-1 Analog Input in-h Scaling upper limit in-l Scaling lower limit dp Decimal point • When an analog input is selected, scaling can be performed as needed by the control application. • Scaling is set in the “scaling upper limit,” “scaling lower limit,” and “decimal point” parameters (initial setting level).
Section 4-4 Executing Heating/Cooling Control 7. Press the U and D keys to set 1. dp 1 8. To return to the operation level, press the O key for one second. 4-4 4-4-1 Executing Heating/Cooling Control Heating/Cooling Control Heating/cooling control can be used on the E5@N-@2@@@, E5@N-@3@@@, or E5@N-@Q@@@. Heating/cooling control operates when h-c (heating/cooling) is selected for the “standard or heating/cooling” parameter. The following functions are assigned to outputs in the initial status.
Section 4-4 Executing Heating/Cooling Control Dead Band • For heating/cooling control, the dead band is set with the set point as its center. The dead band width is the set value of the “dead band” parameter (adjustment level). Setting a negative value produces an overlapping band. • If an overlapping band is set, the bumpless function may not operate when switching between manual operation and automatic operation. • The default is 0.
Executing Heating/Cooling Control 4-4-2 Section 4-4 Settings To set heating/cooling control, set the “standard or heating/cooling,” “dead band,” and “cooling coefficient” parameters. Setting Heating/Cooling Control Operating Procedure Initial Setting Level Standard or s-hc heating/cooling Standard or heating/cooling = Heating/cooling 1. Press the O key for at least three seconds to move from the operation level to the initial setting level. stnd 2.
Section 4-5 Using Event Inputs 4-5 Using Event Inputs 4-5-1 Event Input Settings • Event inputs can be used for the multi-SP function, starting/stopping operation (RUN/STOP), switching between auto/manual, and program starts. • Of these, the multi-SP function, event inputs are used only for the number (0 to 2) set in the “number of multi-SP uses” parameter (advanced function level).
Section 4-5 Using Event Inputs 4-5-2 How to Use the Multi-SP Function The multi-SP function allows you to set up to four set points (SP 0 to 3) in the adjustment level. The set point can be switched by operating the keys on the front panel or by using external input signals (event inputs). Using Event Inputs Event inputs can be used if the Controller supports the event input function and if the “number of multi-SP uses” parameter is set to 1 or 2.
Section 4-5 Using Event Inputs 4-5-3 Settings Switching between Set Points 0, 1, 2, and 3 Operating Procedure Operation Level C 25 PV/SP The following example sets the “number of multi-SP uses” parameter to 2. 1. Press the O key for at least three seconds to move from the operation level to the initial setting level. 100 Initial Setting Level in-t Input type 2. Select the “move to advanced function setting level” parameter by pressing the M key. 5 3.
Section 4-5 Using Event Inputs 4-5-5 Switching between Auto and Manual Control When the “event input assignment 1” or “event input assignment 2” parameter is set to MANU (auto/manual), manual control will start when event input 1 or 2 turns ON. Auto control will start when the input turns OFF. The MANU indicator will light during manual control.
Section 4-6 Setting the SP Upper and Lower Limit Values 4-6 4-6-1 Setting the SP Upper and Lower Limit Values Set Point Limiter The setting range of the set point is limited by the set point limiter. The set point limiter is used to prevent the control target from reaching abnormal temperatures. The upper- and lower-limit values of the set point limiter are set using the “set point upper limit” and “set point lower limit” parameters in the initial setting level.
Section 4-7 Using the SP Ramp Function to Limit the SP Change Rate C sl-h Set point upperlimit 2. Select the “set point upper limit” parameter. 1300 C 3. Use the U and D keys to set the parameter to 1000. sl-h 1000 Setting the Set Point Lower-limit Value Operating Procedure C sl-l Set point lower limit Set Point Lower Limit = −100 1. Select the “set point lower limit” parameter in the initial setting level. -200 C sl-l 2. Use the U and D keys to set the parameter to −100.
Section 4-7 Using the SP Ramp Function to Limit the SP Change Rate Parameters Symbol ol-h ol-l sl-h sl-l sprt spru alsp Operation at Startup Parameter: Level MV upper limit: Adjustment level MV lower limit: Adjustment level Set point upper limit: Initial setting level Set point lower limit: Initial setting level SP ramp set value: Adjustment level SP ramp time unit: Advanced function setting level Alarm SP selection: Advanced function setting level Description To limit the manipulated variable To limit
Section 4-8 Moving to the Advanced Function Setting Level Alarms during SP Ramp Operation The operation of alarms during SP ramp operation depends on whether alarms are set to be based on the ramp set point or the target set point (refer to the following diagrams). The set point to be used is set in the “alarm SP selection” parameter.
Section 4-9 Using the Key Protect Level Operation Level C 25 PV/SP 5. Press the O and M keys simultaneously for at least one second to return to the operation level. 100 Initial Setting Level in-t Input type 6. Move to the advanced function setting level. Press the O key for at least three seconds to move from the operation level to the initial setting level.
Section 4-9 Using the Key Protect Level Operation/Adjustment Protect The following table shows the relationship between set values and the range of protection.
Section 4-9 Using the Key Protect Level 4-9-2 Entering the Password to Move to the Protect Level • Protect level can be moved to only by display the password display and entering the correct password. (The user can set any password in the “protect level password” parameter. If no password is set (i.e., if the password is set to 0 in the “protect level password” parameter), the password input display to move to protect level will not be displayed and the protect level can be moved to directly.
Section 4-9 Using the Key Protect Level Setting the Password Operating Procedure Use the following procedure to set the password to move to the protect level. ■ Example To set the Password to 1234 Operation Level C 25 PV/SP 100 Protect Level oapt 1. Press the O and M keys simultaneously for at least the time set in the “move to protect level time” parameter to move from the operation level to Operation/adjustthe protect level.
Section 4-10 PV Change Color 4-10 PV Change Color 4-10-1 PV Color Change Function Use the PV color change function to change the color of the PV display (No. 1 display). There are three display colors, orange, red, and green, and you can select from the following three modes and eight functions. colr • Constant: This mode displays orange, red, or green all the time.
PV Change Color Section 4-10 PV Stable Band When the mode to link to the PV stable band is selected, the PV display color will change according to whether the present value (PV) is lower than, within, or higher than the PV stable band shown in the following figure. The PV stable band is set with the SP as the center, as shown below. pv-b PV stable band PV stable PV stable band band Low Within High PV SP The default is 5.
Section 4-10 PV Change Color 5. Press the U key to set the parameter to r-gr. colr r-g.r Advanced Function Setting Level C pv-b 6. Select the “PV stable band” parameter by pressing the M key. PV stable band 5.0 C 7. Use the U key to set the parameter to 15.0. pv-b 15.0 8. To return to the initial setting level, press the O key for at least one second. 9. To return to the operation level, press the O key for at least one second.
Section 4-11 Alarm Delays 4-11 Alarm Delays 4-11-1 Alarm Delays • Delays can be set for the alarm outputs. ON and OFF delays can be set separately for alarms 1, 2, and 3. The ON and OFF delays for alarm 1 function only for the alarm function. If the alarm output 1 is set to be output as an OR with other alarm functions (i.e., the heater burnout alarm, HS alarm, or input error output alarm), the delays will not function for the other alarms.
Section 4-11 Alarm Delays Note (1) The defaults are 0, i.e., the ON and OFF delays are disabled. (2) The parameters are displayed when alarm outputs are assigned and when the alarm type is set to any type but 0 (none). Operating Procedure Use the following procedure to set ON and OFF delays for the alarm 1 output. An ON delay of 5 seconds and an OFF delay of 10 s will be set. Operation Level C 25 PV/SP 100 Initial Setting Level in-t Input type 1.
Section 4-12 Loop Break Alarm 4-12 Loop Break Alarm 4-12-1 Loop Break Alarm (LBA) • With a loop break alarm, there is assumed to be an error in the control loop if the control deviation (SP − PV) is greater than the threshold set in the “LBA level” parameter and if the control deviation is not reduced by at least the value set in the “LBA detection band” parameter within the LBA detection time. • Loop break alarms are detected at the following times.
Section 4-12 Loop Break Alarm • Detection in not possible if a fault occurs that causes an increase in temperature while control is being applied to increase the temperature (e.g., an SSR short-circuit fault). • Detection in not possible if a fault occurs that causes a decrease in temperature while control is being applied to decrease the temperature (e.g., a heater burnout fault).
Section 4-12 Loop Break Alarm 3. Set the “LBA detection time” parameter to two times the measured time. LBA Level • Set the control deviation when the control loop is working properly. • The default is 8.0 (°C/°F) for Controllers with Thermocouple/Resistance Thermometer Multi-Inputs and 10.00% FS for Controllers with Analog Inputs.
Section 4-13 Performing Manual Control C 7. Press the U key to set the parameter to 10. lba 10 Advanced Function Setting Level C lbal 8. Select the “LBA level” parameter by pressing the M key. LBA level 8.0 C 9. Press the U key to set the parameter to 8.0. (The default is 8.0.) lbal 8.0 Advanced Function Setting Level C lbab 10. Select the “LBA band” parameter by pressing the M key. LBA band 3.0 C 11. Press the U or D key to set the parameter to 3.0. (The default is 3.0.) lbab 3.
Section 4-13 Performing Manual Control Note In balanceless-bumpless operation, the MV before switching is used initially after the switch and then gradually changed to achieve the proper value after switch to prevent radical changes in the MV after switching operation. The overall manual operation is illustrated in the following figure.
Section 4-13 Performing Manual Control Operation Level C Press O key for at least 1 s. 25 PV M C 25 PV/SP 100 Manual Control Level M C 25 20 PV/MV a-m Press O key for at least 3 s. a-m display flashes for at least 1 s. a-m Auto/manual switch M m-sp Multi-SP 0 M • If an event input is set to “MANU” (auto/manual), the “auto/manual switch” parameter will not be displayed. Use the event input to switch between automatic and manual modes.
Section 4-13 Performing Manual Control Operating Procedure Use the following procedure to set the manipulated variable in manual mode. Operation Level C 25 PV/SP 100 Initial Setting Level in-t Input type 1. Press the O key for at least three seconds to move from the operation level to the initial setting level. 5 2. Select the “PID ON/OFF” parameter by pressing the M key. cntl pid Initial Setting Level Move to ad- function amov vanced setting level 3.
Section 4-14 Using the Transfer Output C 11. Press the U or D key to set the manual MV. (In this example, the MV is set to 500%.) 25 50.0 Note The manual MV setting must be fixed (see page 12), but values changed with key operations are reflected in the control output immediately. 12. Press the O key for at least one second to move from the manual control level to the operation level.
Section 4-14 Using the Transfer Output Output current (mA) 20.3 20 Transfer output value Control output 4 3.7 0 MV (%) 100 (The above graph is for when the linear current output type is set to 4 to 20 mA.) Transfer Scaling • Reverse scaling is possible by setting the “transfer output lower limit” parameter larger than the “transfer output upper limit” parameter.
Section 4-14 Using the Transfer Output Operating Procedure The following procedure sets the transfer output for an SP range of −50 to 200. Operation Level C 25 PV/SP 100 Initial Setting Level in-t Input type 1. Press the O key for at least three seconds to move from the operation level to the initial setting level. 5 Initial Setting Level 2. Select the “transfer output type” parameter by pressing the M key. Transfer output tr-t type off 3. Press the U key to select sp (set point).
Section 4-15 Using the Simple Program Function 4-15 Using the Simple Program Function 4-15-1 Simple Program Function • The simple program function can be used for the following type of control. SP Wait band Wait band Set point PV Soak time RSET → STRT END display END output Select either STOP or RUN. • The program will start when the “program start” parameter is changed from RSET to STRT. END will be displayed on the No.
Section 4-15 Using the Simple Program Function Program Pattern Either of two program patterns can be selected. The simple program operation will not be performed if the “program pattern” parameter is set to OFF. ■ Pattern 1 (STOP) Control will stop and the STOP mode will be entered when the program has ended. Wait band Wait band Set point PV RSET → STRT Soak time END display END output Automatically switches from RUN to STOP mode.
Section 4-15 Using the Simple Program Function Starting Method Any of the following three methods can be used to start the simple program. • Setting the “program start” parameter to STRT. • Turning ON an event input. (The program start must be assigned to an event input. See note.) • Starting with an Operation Command using communications. (When the program start is not assigned to an event input.) Note When an event input is used to start and reset the simple program, writing is performed to EEPROM.
Section 4-15 Using the Simple Program Function 4-15-2 Operation at the Program End Display at the Program End When the program ends, the process value will be displayed on the No. 1 display (see note) and the set point and “end” will be alternately displayed on the No. 2 display at 0.5 s intervals. Note One of the following displays: PV/SP, PV only, or PV/MV. 120.1 Displayed alternately. end 120.
Using the Simple Program Function Section 4-15 Operation Level C 25 PV/SP 100 Initial Setting Level in-t Input type 1. Press the O key for at least three seconds to move from the operation level to the initial setting level. 5 Initial Setting Level ptrn 2. Select the “program pattern” parameter by pressing the M key. Program Pattern off 3. Use the U key to set the parameter to STOP. ptrn stop Operation Level C 25 PV/SP 4.
Section 4-15 Using the Simple Program Function 4-15-3 Application Example Using a Simple Program The program will be started by changing the setting of the “program start” parameter. The following example shows using a simple program with the program pattern set to STOP.
Section 4-16 Output Adjustment Functions 4-16 Output Adjustment Functions 4-16-1 Output Limits • Output limits can be set to control the output using the upper and lower limits to the calculated MV. • The following MV takes priority over the MV limits. Manual MV MV at stop MV at PV error Output 100% MV upper limit MV lower limit 0% • For heating/cooling control, upper and lower limits are set of overall heating/cooling control. (They cannot be set separately for heating/cooling.
Section 4-16 Output Adjustment Functions 4-16-3 MV at PV Error • The MV to be output for input errors or heater burnout errors can be set. The MV at stop takes priority when stopped and the manual MV takes priority in manual mode. Parameter MV at PV error Note Setting range Unit −5.0 to 105.0 for standard % control −105.0 to 105.0 (heating/cooling control) Default 0.0 The order of priority is as follows: Manual MV > MV at stop > MV at PV error.
SECTION 5 Parameters This section describes the individual parameters used to setup, control, and monitor operation. 5-1 Conventions Used in this Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114 5-1-1 Meanings of Icons Used in this Section . . . . . . . . . . . . . . . . . . . . . . 114 5-1-2 About Related Parameter Displays . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 5-1 Conventions Used in this Section 5-1 Conventions Used in this Section 5-1-1 Meanings of Icons Used in this Section Describes the functions of the parameter. Function Describes the setting range and default of the parameter. Setting Used to indicate parameters used only for monitoring. Monitor Describes the parameter settings, such as those for Operation Commands, and procedures.
Section 5-2 Protect Level 5-2 Protect Level Three levels of protection are provided on the E5CN, operation/adjustment protect, initial setting/communications protect, and setting change protect. These protect levels prevent unwanted operation of the keys on the front panel in varying degrees. Power ON Operation Level Adjustment Level Press the O + M keys; display will flash. Press the O Key less than 1 s. C 25 100 Press the O + M Keys for at least 1 s. Press the O + M Keys for at least 3 s.
Section 5-2 Protect Level pmov The “password to move to protect level” password must not be set to 0. Move to Protect Level The password to move to the protect level is entered for this parameter. • The password to move to the protect level (i.e., the password set for the “password to move to protect level” parameter) is entered for this parameter. Function • The “operation/adjustment protect” parameter will be displayed if the correct password is entered.
Section 5-2 Protect Level ■ Setting Change Protect Changes to settings using key operations are restricted. Set value OFF Description Settings can be changed using key operations. ON Settings cannot be changed using key operations. (The protect level settings, however, can be changed.) • The all protect indication ( pmsk ) will light when setting is ON. This parameter is displayed only when a parameter mask has been set from the Setup Tool.
Section 5-3 Operation Level 5-3 Operation Level Display this level to perform control operations on the E5CN. You can set alarm values, monitor the manipulated variable, and perform other operations in this level. In the advanced function setting level, you can set a parameter to hide or show the set points. Power ON Operation Level Adjustment Level Press the O Key less than 1 s. Press the O Key for at least 1 s; display will flash. Press the O Key for at least 1 s.
Section 5-3 Operation Level Operation Level Page 25 Process value C 119 Page C 25 Process value/set point 120 C a-m Auto/manual switch 120 C 120 sp-m Set point during SP 121 ct1 Heater current 1 121 ct2 Heater current 2 122 lcr1 Leakage current 1 122 lcr2 Leakage current 2 123 0 M 0 ramp M 0.0 value monitor M 0.0 value monitor M 0.0 monitor M 0.
Section 5-3 Operation Level Process Value/Set Point The process value is displayed on the No. 1 display, and the set point is displayed on the No. 2 display. Monitor range Function Unit Process value Input indication range (See page 219.) EU Set point Setting range SP lower limit to SP upper limit EU Unit During temperature input, the decimal point position depends on the currently selected sensor, and during analog input it depends on the “decimal point” parameter setting.
Section 5-3 Operation Level sp-m The “SP ramp set value” parameter must not be set to OFF. The “ST” parameter must be set to OFF. Set Point During SP Ramp This parameter monitors the set point during SP ramp operation. A ramp is used to restrict the change width of the set point as a rate of change. Function This parameter is displayed when a set value is input for the “SP ramp set value” (adjustment level).
Section 5-3 Operation Level ct2 Heater Current 2 Value Monitor Heater burnout and HS alarms must be supported (two CTs). Alarm 1 must be assigned. The “heater burnout detection” parameter must be set to ON. This parameter measures the heater current from the CT input used for detecting heater burnout. This parameter measures and displays the heater current value. Function • Heater burnouts are not detected if the control output (heating) ON time is 190 ms or less. Monitor range 0.0 to 55.
Section 5-3 Operation Level lcr2 Heater burnout and HS alarms must be supported (two CTs). Alarm 1 must be assigned. The “HS alarm use” parameter must be set to ON. Leakage Current 2 Monitor This parameter measures the heater current from the CT input used for detecting SSR short-circuits. This parameter measures and displays the heater current value. Function • HS are not detected if the control output (heating) OFF time is 190 ms or less. Monitor range 0.0 to 55.
Section 5-3 Operation Level sktr The “program pattern” parameter must not be set to OFF. Soak Time Remain • This parameter measures and displays the remaining time of the soak time for the simple program function.
Section 5-3 Operation Level ■ Related Parameters See Input type: Page 146, Scaling upper limit, Scaling lower limit, Decimal point (initial setting level): Page 148 (initial setting level) Alarm 1 type (initial setting level): Page 152 Standby sequence reset: Page 161, Alarm 1 open in alarm: Page 162, Alarm 1 hysteresis: Page 163, Alarm 1 latch: Page 167 (advanced function setting level) al-2 Alarm 2 must be assigned. The alarm 2 type must be set to other than an upper and lower limit alarm.
Section 5-3 Operation Level ■ Related Parameters See Input type: Page 146, Scaling upper limit, Scaling lower limit, Decimal point (initial setting level): Page 148 (initial setting level) Alarm 3 type (initial setting level): Page 154 Standby sequence reset: Page 161, Alarm 3 open in alarm: Page 162, Alarm 3 hysteresis: Page 163, Alarm 3 latch: Page 167 (advanced function setting level) al1h Alarm Value Upper Limit 1 al1l Alarm Value Lower Limit 1 Alarm 1 must be assigned.
Section 5-3 Operation Level ■ Related Parameters See Input type: Page 146, Scaling upper limit, Scaling lower limit, Decimal point: Page 148, Alarm 2 type: Page 154 (initial setting level), Standby sequence reset: Page 161, Alarm 2 open in alarm: Page 162, Alarm 2 hysteresis: Page 163, Alarm 2 latch: Page 167 (advanced function setting level) al3h Alarm Value Upper Limit 3 al3l Alarm Value Lower Limit 3 Alarm 3 must be assigned.
Section 5-3 Operation Level c-o The control system must be set to heating/cooling control. The “MV display” parameter must be set to ON. MV Monitor (Cooling) This parameter is used to check the manipulated variable for the cooling control output during operation. • This parameter cannot be set. Function • During heating/cooling control, the manipulated variable on the cooling control output is monitored. • The default is OFF and the manipulated variable is not displayed.
Section 5-4 Adjustment Level 5-4 Adjustment Level This level is for executing AT (auto-tuning) and other operations, and for set control parameters. This level provides the basic Controller parameters for PID control (proportional band, integral time, derivative time) and heating/cooling control. Power ON Operation Level Adjustment Level Press the O Key less than 1 s. Control in progress To move to the adjustment level from the operation level, press the O key once.
Section 5-4 Adjustment Level Adjustment Level Page Page l.adj Adjustment level display C M 131 C off M cmwt Communications off writing M 131 ct2 Heater current 2 value 132 0.0 monitor M 136 133 lcr2 Leakage current 2 133 hb1 Heater burnout 134 hb2 Heater burnout 134 hs1 HS alarm 1 135 hs2 HS alarm 2 135 0.0 monitor M 0.0 monitor M 0.0 detection 1 M C sp-2 SP 2 136 C sp-3 SP 3 136 C ins Temperature input 0.0 shift M C 140 50.
Section 5-4 Adjustment Level at AT Execute/Cancel The E5CN must be in operation, and control must be 2-PID control. This parameter executes auto-tuning (AT). Function • The MV is forcibly increased and decreased around the set point to find the characteristics of the control object. From the results, the PID constants are automatically set in the “proportional band” (P), “integral time” (I), and “derivative time” (D) parameters. • This parameter is normally off.
Section 5-4 Adjustment Level ct1 Heater Current 1 Value Monitor Heater burnout and HS alarms must be supported. Alarm 1 must be assigned. The “heater burnout detection” parameter must be set to ON. This parameter measures the heater current from the CT input used for detecting heater burnout. This parameter measures and displays the heater current value. Function • Heater burnouts are not detected if the control output (heating) ON time is 190 ms or less. Monitor range 0.0 to 55.
Section 5-4 Adjustment Level lcr1 Heater burnout and HS alarms must be supported. Alarm 1 must be assigned. The “HS alarm” parameter must be set to ON. Leakage Current 1 Monitor This parameter measures the heater current from the CT input used for detecting SSR short-circuits. This parameter measures and displays the heater current when the heater is OFF. Function • HS are not detected if the control output (heating) OFF time is 190 ms or less. Monitor range 0.0 to 55.
Section 5-4 Adjustment Level hb1 Heater burnout and HS alarms must be supported. Alarm 1 must be assigned. The “heater burnout detection” parameter must be set to ON. Heater Burnout Detection 1 This parameter sets the current for the heater burnout alarm to be output. • The heater burnout alarm is output when the heater current value falls below the setting of this parameter. Function • When the set value is 0.0, the heater burnout alarm is turned OFF. When the set value is 50.
Section 5-4 Adjustment Level hs1 Heater burnout and HS alarms must be supported. Alarm 1 must be assigned. The “HS alarm” parameter must be set to ON. HS Alarm 1 This parameter sets the current for the HS alarm to be output. • The HS alarm is output when the heater current value goes above the setting of this parameter. Function • When the set value is 50.0, the HS alarm is turned OFF. When the set value is 0.0, the HS alarm will turn ON. Setting range 0.0 to 50.0 Unit A Default 50.
Section 5-4 Adjustment Level sp-0 sp-1 sp-2 sp-3 SP 0 SP 1 SP 2 SP 3 The “number of multi-SP uses” parameter must be set to 1 or 2. The “multi-SP uses” parameter must be set to ON. These parameters set the set points when the multi-SP function is used. The values set in these parameters can be selected by operating the keys on the front panel or by using event inputs.
Section 5-4 Adjustment Level insh Upper-limit Temperature Input Shift Value insl Lower-limit Temperature Input Shift Value The “input type” parameter must be set for a thermocouple or resistance thermometer and the “input shift type” parameter must be set to a 2point shift, or the “input type” parameter must be set for an infrared sensor.
Section 5-4 Adjustment Level p i d Proportional Band Integral Time Derivative Time The control must be set to 2-PID control. These parameters set PID control constants. PID constants are automatically set when AT or ST is executed. P action: Refers to control in which the MV is proportional to the deviation (control error). I action: Refers to a control action that is proportional to the time integral of the deviation. With proportional control, there is normally an offset (control error).
Section 5-4 Adjustment Level c-sc The control must be heating/cooling control and 2-PID control. Cooling Coefficient If the heating characteristics and cooling characteristics of the control object are very different and good control characteristics cannot be achieved with the same PID constants, the cooling coefficient can be used to adjust the proportional band (P) for the control output assigned to the cooling side.
Section 5-4 Adjustment Level of-r The control must be standard control and 2-PID control. The “integral time” parameter must be set to 0. Manual Reset Value • This parameter sets the required manipulated variable to remove offset during stabilization of P or PD control. Function Setting range 0.0 to 100.0 Unit % Default 50.
Section 5-4 Adjustment Level soak The “program pattern” parameter must not be set to OFF. Soak Time • This parameter sets the time for the control operation when using the simple program function.
Section 5-4 Adjustment Level mv-s The control must be set to 2-PID control. The “MV at stop and error addition” parameter must be ON. MV at Stop • This parameter sets the MV to use when the RUN/STOP status changes from RUN to STOP. Function Setting range Setting −5.0 to 105.0 for standard control −105.0 to 105.0 (heating/cooling control) Unit % Default 0.
Section 5-4 Adjustment Level sprt The “ST” parameter must be set to OFF. SP Ramp Set Value • This parameter sets the rate of change during SP ramp operation. Set the maximum permissible change width per unit of time as the SP ramp set value. The SP ramp function is disabled if this parameter is set to OFF. Function • During temperature input, the decimal point position of the SP ramp set value is dependent on the currently selected sensor, and during analog input it is dependent on scaling.
Section 5-5 Manual Control Level 5-5 Manual Control Level The manipulated variable can be set in manual mode if the “PV/MV” parameter is displayed. The final MV used in automatic mode will be used as the initial manual MV when moving from automatic mode to manual mode. In manual mode, the change value will be fixed immediately and reflected in the actual MV. Power ON Operation Level a-m Press the O Key for at least 1 s. Press the O Key for at least 1 s; display will flash.
Section 5-6 Initial Setting Level 5-6 Initial Setting Level This level is used to set up the basic Temperature Controller specifications. In this level, you can set the “input type” parameter to set the sensor input to be connected, limit the setting range of set points, set the alarm modes, and perform other operations. Power ON Operation Level Press the O Key for at least 1 s. Press the O Key for at least 1 s; display will flash. Initial Setting Level C 25 100 Press the O Key for at least 3 s.
Section 5-6 Initial Setting Level Initial Setting Level Page in-t Input type 146 in-h Scaling upper limit 148 in-l Scaling lower limit 148 dp Decimal point 148 5 M c-cp Control period (cool) 151 oreV Direct/reverse operation 152 alt1 Alarm 1 type 152 alt2 Alarm 2 type 154 alt3 Alarm 3 type 154 tr-t Transfer output type 155 or-r M 0 M 2 M 148 c M 2 M sl-h SP upper limit 149 sl-l SP lower limit 149 cntl PID·ON/OFF 149 tr-h Transfer output upper 155 or s-hc Standard heatin
Section 5-6 Initial Setting Level Input type Controllers Platinum resistance with Therthermometer mocouple/ Resistance Thermometer Multiinputs Thermocouple Controllers with Analog Inputs Specifications Set value Pt100 0 Input temperature range −200 to 850 (°C)/−300 to 1,500 (°F) 1 2 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F) 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) JPt100 3 4 −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F) 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) K 5 6 −200 to 1,300 (°C)/−300 to 2,300 (°F) −20.
Section 5-6 Initial Setting Level in-h in-l dp Scaling Upper Limit Scaling Lower limit Decimal Point The input type must be set for an analog input. • These parameters can be used when the input type is set for an analog input. • When an analog input is used, scaling is performed. Set the upper limit in the “scaling upper limit” parameter and the lower limit in the “scaling lower limit” parameter.
Section 5-6 Initial Setting Level sl-h sl-l Function SP Upper Limit SP Lower Limit • These parameters set the upper and lower limits of the set points. A set point can be set within the range defined by the upper and lower limit set values in the “SP upper limit” and “SP lower limit” parameters. If these parameters are reset, any set point that is outside of the new range will be forcibly changed to either the upper limit or the lower limit.
Section 5-6 Initial Setting Level ■ Related Parameters See AT execute/cancel: Page 131, Manual reset, Hysteresis (heating), and Hysteresis (cooling): Page 140 (adjustment level) ST stable range (advanced function setting level): Page 165 s-hc Standard or Heating/Cooling • This parameter selects standard control or heating/cooling control.
Section 5-6 Initial Setting Level ■ Related Parameters See ptrn Input type: Page 146, PID ON/OFF: Page 149 (initial setting level), ST stable range (advance function setting level): Page 165 Program Pattern This parameter sets the type of control when using the simple program function. • If the program pattern is set to OFF, the simple program will not operate. Function Setting • If the program pattern is set to STOP, the RUN/STOP status will change to STOP after the soak time has expired.
Section 5-6 Initial Setting Level orev Direct/Reverse Operation • “Direct operation” refers to control where the manipulated variable is increased when the process value increases. Alternatively, “reverse operation” refers to control where the manipulated variable is increased when the process value decreases. Function Setting range Default or-r: Reverse operation, or-d: Direct operation or-r Setting alt1 Alarm 1 Type Alarm 1 must be assigned.
Section 5-6 Initial Setting Level Set values Alarm type 10 11 12 Note Alarm output operation When alarm value X When alarm value X is positive is negative Absolute-value upperlimit with standby sequence Absolute-value lower-limit with standby sequence ON OFF LBA (alarm 1 type only) --- X ON OFF X ON OFF 0 X ON OFF 0 0 X 0 (1) With set values 1, 4 and 5, the upper- and lower- limit values can be set independently for each alarm type, and are expressed as “L” and “H.
Section 5-6 Initial Setting Level alt2 Alarm 2 Type Alarm 2 must be assigned. • Select one of the following three alarm 2 types: Deviation, Deviation range, or Absolute value Function Refer to the alarm 1 type list.
Section 5-6 Initial Setting Level tr-t Transfer Output Type A current output must be assigned. • When current output is to be used as transfer output, this parameter sets the transfer output type. • If current output is not to be used as transfer output, set this parameter to OFF.
Section 5-6 Initial Setting Level o1-t Linear Current Output A current output must be assigned. This parameter selects the output type for linear current outputs. • Select either 4 to 20 mA or 0 to 20 mA. Function Transfer type 4-20: 4 to 20 mA 0-20: 0 to 20 mA Default 4-20 Setting ■ Related Parameter See amov Transfer output type (initial setting level): Page 155 Move to Advanced Function Setting Level The “initial setting/communications protect” parameter must be set to 0.
Section 5-7 Advanced Function Setting Level 5-7 Advanced Function Setting Level The advanced function setting level is used for optimizing Controller performance. To move to this level, input the password (“−169”) from the initial setting level. To be able to enter the password, the “initial setting/communications protect” parameter in the protect level must be set to 0. • The parameters in this level can be used when the “initial setting/communications protect” parameter is set to 0.
Section 5-7 Advanced Function Setting Level Advanced Function Setting Level Page hbl Heater burnout 164 rlrv MB command 169 hsl HS alarm 175 ev-m Number of 159 hbh Heater burnout 164 colr PV display 169 hsh HS alarm 175 ev-1 Event input 160 pv-b PV stable band 170 lba LBA detection 176 ev-2 Event input 160 a1on Alarm 1 ON 171 none assignment 1 M stop assignment 2 off latch M 0.1 hysteresis M C st-b ST stable 165 alfa α 165 15.
Section 5-7 Advanced Function Setting Level ev-m Number of Multi-SP Uses Event inputs must be supported. Multi-SP is a function for setting set points 0 to 3 in advance, and switching between these set points using the ON/OFF combinations of event inputs 1 and 2. Function The “number of multi-SP uses” parameter is used when the number of preset set points is either two or four. This parameter determines whether the “event input assignment 1” and “event input assignment 2” parameters are displayed.
Section 5-7 Advanced Function Setting Level Note Event input 1 OFF ON Event input 2 Selected set point Set point 2 ON ON Set point 3 Event inputs can be used on E5@N-@@@B@ Controllers. Turn the event inputs ON or OFF while the power is turned ON. Event input ON/OFF changes are detected for inputs of 50 ms or longer.
Section 5-7 Advanced Function Setting Level ■ Related Parameters See Multi-SP set point setting (operation level): Page 120 Number of multi-SP uses (advanced function setting level): Page 159 spru The “ST” parameter must be set to OFF. SP Ramp Time Unit • This parameter sets the time unit for the rate of change during SP ramp operation.
Section 5-7 Advanced Function Setting Level ■ Related Parameters See Alarm 1 to 3 type (initial setting level): Page 152 to 154 Alarm 1 to 3 latch (advanced function setting level): Page 167 al1n Alarm 1 Open in Alarm Alarm 1 must be assigned. • This parameter sets the output status for alarm 1. Function • When “close in alarm” is set, the status of the alarm output function will be output as is.
Section 5-7 Advanced Function Setting Level ■ Related Parameters Alarm value 2 and 3: Page 125, Alarm value upper limit 2 and 3, Alarm value lower limit 2 and 3: Page 126 to 127 (operation level) See Alarm 2 to 3 type (initial setting level): Page 154 Alarm 2 and 3 hysteresis: Page 163, Standby sequence reset: Page 161, Alarm 2 and 3 latch: Page 167 (advanced function setting level) alh1 Alarm 1 Hysteresis Alarm 1 must be assigned, and the alarm 1 type must not be 0 or 12.
Section 5-7 Advanced Function Setting Level hbl Heater burnout and HS alarms must be supported. Alarm 1 must be assigned. The “heater burnout detection” parameter must be set to ON. Heater Burnout Latch • When this parameter is set to ON, the heater burnout alarm is held until either of the following conditions is satisfied. Function a Heater burnout detection is set to 0.0 A. b The power is turned OFF then back ON again (i.e., power is reset).
Section 5-7 Advanced Function Setting Level st-b ST must be ON and temperature input, standard control, 2-PID control must be set. ST Stable Range • The setting of this parameter determines when ST operates. This parameter cannot be used when ST is set to OFF. Function Setting range 0.1 to 999.9 Unit °C or °F Default 15.0 Setting ■ Related Parameters See alfa Input type: Page 146, PID ON/OFF: Page 149, ST: Page 150 (initial setting level) ST must be OFF and 2-PID control must be set.
Section 5-7 Advanced Function Setting Level inf Input Digital Filter • This parameter sets the time constant for the input digital filter. The following diagram shows the effect on data after passing through the digital filter: Function PV before passing through filter A PV after passing through filter 0.63 A (Time constant) Time Input digital filter Setting range 0.0 to 999.9 Unit Second Default 0.
Section 5-7 Advanced Function Setting Level ret Automatic Display Return Time • In the operation level or adjustment level, the display automatically returns to the PV/SP if there are no key operations for the time set for this parameter. Function • The automatic display return time is disabled when the parameter is set to OFF. (In that case, the display will not be automatically switched.
Section 5-7 Advanced Function Setting Level prlt Move to Protect Level Time • This parameter sets the key pressing time required to move to the protect level from the operation level or the adjustment level. Function Setting range 1 to 30 Unit Second Default 3 Setting ■ Related Parameters See sero Operation/adjustment protect, initial setting/communications protect, setting change protect (protect level): Page 116 Input Error Output Alarm 1 must be assigned.
Section 5-7 Advanced Function Setting Level rlrv Communications must be supported. CompoWay/F must be selected as the protocol. MB Command Logic Switching • .This parameter switches the logic of the MB command (communications writing switch) for the SYSWAY communications protocol • The MB command (communications writing switch) is the equivalent of the MB command (remote/local switch) of the E5@J. Function • The setting indicated by the shaded area is the default (same logic as E5@J).
Section 5-7 Advanced Function Setting Level Mode Linked to alarm 1 Setting Function PV change color Application example Alarm value ON ALM1 lit PV OFF SP ALM1 not lit ALM1 lit Application example r-g Red to Green Red Green To display the PV reached signal g-r Green to Red Green Red To display error signals Linked to PV stable band Within Within PV stable PV stable band band Low Within High PV SP r-g.r g-o.r o-g.
Section 5-7 Advanced Function Setting Level Setting Note Models Controllers with Thermocouple/Resistance Thermometer Multi-inputs Setting range 0.1 to 999.9 Unit °C or °F (See note.) Default 5.0 Controllers with Analog Inputs 0.01 to 99.99 %FS 5.00 Set “none” as the unit for Controllers with Analog Inputs. ■ Related Parameter See PV change color (advanced function setting level): Page 169 a1on Alarm 1 ON Delay Alarm 1 must be assigned, and the alarm 1 type must not be 0 or 12.
Section 5-7 Advanced Function Setting Level a1of Alarm 1 OFF Delay Alarm 1 must be assigned, and the alarm 1 type must not be 0 or 12. a2of Alarm 2 OFF Delay a3of Alarm 3 OFF Delay Alarm 2 must be assigned, and the alarm 2 type must not be 0. Alarm 3 must be assigned, and the alarm 3 type must not be 0. Alarm 1, 2, or 3 outputs are prevented from turning OFF until after the delay times set in these parameters have elapsed. • Set the time for which the OFF delay is to be enabled.
Section 5-7 Advanced Function Setting Level mvse MV at Stop and Error Addition The control must be set to 2-PID control. This parameter sets whether or not the “MV at stop” and “MV at PV error” parameters are to be displayed. • Set whether or not the “MV at stop” and “MV at PV error” parameters are to be displayed.
Section 5-7 Advanced Function Setting Level rt The control must be set to 2-PID control. The input type must be set to temperature input. RT This parameter executes robust tuning (RT). • When AT or ST is executed with RT selected, PID constants are automatically set which make it hard for control performance to degenerate even when control object characteristics are changed.
Section 5-7 Advanced Function Setting Level hsl Heater burnout and HS alarms must be supported. Alarm 1 must be assigned. The “HS alarm” parameter must be set to ON. HS Alarm Latch • When this parameter is set to ON, the HS alarm is held until either of the following conditions is satisfied. Function a The HS alarm current is set to 50.0 A. b The power is turned OFF then back ON again (i.e., power is reset).
Section 5-7 Advanced Function Setting Level lba Alarm 1 must be assigned. The alarm type must be set to 12 (LBA). LBA Detection Time This parameter enables or disables the LBA function and sets the detection time interval. • Set the time interval for detecting loop burnouts. • To disable the LBA function, set 0.
Section 5-7 Advanced Function Setting Level lbab Alarm 1 must be assigned. The alarm type must be set to 12 (LBA). The LBA detection time must not be 0. LBA Band • This parameter sets the LBA band. • If a control deviation greater than the LBA band is not reduced when the LBA level is exceeded, an loop burnout is detected. Function Setting Note Models Controllers with Thermocouple/Resistance Thermometer Multi-inputs Setting range 0.0 to 999.9 Unit °C or °F (See note.) Default 3.
Section 5-7 Advanced Function Setting Level out2 Control Output 2 Assignment Control output 2 must be assigned. • This parameter sets the function to be assigned to control output 2. Function Setting range Default none: No function is assigned to control output 2. o: Heating control output is output. Setting c-o: Cooling control output is output. (See note 1.) alm1: Alarm 1 is output. none (See note 3.) alm2: Alarm 2 is output. alm3: Alarm 3 is output. p.end: Program end is output. (See note 2.
Section 5-7 Advanced Function Setting Level alm2 Alarm 2 Assignment Alarm output 2 must be assigned. • This parameter sets the function to be assigned to alarm output 2. Function Setting range none: No function is assigned to alarm output 2. o: Heating control output is output. Setting c-o: Cooling control output is output. (See note 1.) alm1: Alarm 1 is output. Default alm2 (See note 3.) alm2: Alarm 2 is output. alm3: Alarm 3 is output. p.end: Program end is output. (See note 2.
Section 5-7 Advanced Function Setting Level alm3 Alarm output 3 must be assigned (E5AN and E5EN only). Alarm 3 Assignment • This parameter sets the function to be assigned to alarm output 3. Function Setting range Default none: No function is assigned to alarm output 3. o: c-o: Setting alm3 (See note 3.) Heating control output is output. Cooling control output is output. (See note 1.) alm1: Alarm 1 is output. alm2: Alarm 2 is output. alm3: Alarm 3 is output. p.end: Program end is output.
Section 5-7 Advanced Function Setting Level t-u The “program pattern” parameter must not be set to OFF. Soak Time Unit • Set the soak time unit for the simple program function. Function Setting range Default m: Minutes, h: Hours m Setting ■ Related Parameters See Program start, Soak time remain (operation level): Page 123 Soak time, Wait band (adjustment level): Page 141 Program pattern (initial setting level): Page 151 alsp Alarm SP Selection Alarm 1, 2, and 3 functions must be assigned.
Section 5-8 Communications Setting Level 5-8 psel u-no bps len sbit prty sdwt Communications Setting Level Protocol Setting Communications Unit No. Communications Baud Rate Communications Data Length Communications Stop Bits Communications Parity Send Data Wait Time Communications must be supported. CompoWay/F must be selected as the protocol. CompoWay/F must be selected as the protocol. • Each parameter is enabled when the power is reset.
SECTION 6 CALIBRATION This section describes how the user can calibrate the E5CN and E5CN-U Digital Temperature Controllers. 6-1 6-2 6-3 6-4 Parameter Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184 User Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186 6-2-1 Calibrating Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 6-1 Parameter Structure 6-1 Parameter Structure • To execute user calibration, enter the password “1201” at the “move to calibration level” parameter in the advanced function setting level. The mode will be changed to the calibration mode, and adj will be displayed. • The “move to calibration level” parameter may not be displayed when the user is doing the calibration for the first time.
Section 6-1 Parameter Structure Controllers with Analog Inputs Advanced Function Setting Level adj 30 Moves automatically according to input type. Current input Voltage input 0: 4 to 20 mA 1: 0 to 20 mA 2: 1 to 5 V 3: 0 to 5 V 4: 0 to 10 V a 20 1v 5 2v10 a 1v 1 2v 1 c8e7 c7c3 1 4677 sac0 b104 4ad9 str no When calibration has been performed after purchase, the user calibration information shown in the following illustration will be displayed when moving to the calibration level. .
Section 6-2 User Calibration 6-2 User Calibration The E5CN/CN-U/AN/EN is correctly calibrated before it is shipped from the factory, and normally need not be calibrated by the user. If, however, it must be calibrated by the user, use the parameters for calibrating temperature input and analog input. OMRON, however, cannot ensure the results of calibration by the user. Also, calibration data is overwritten with the latest calibration results.
Section 6-3 Thermocouple Calibration (Thermocouple/Resistance Thermometer Input) 6-3-1 Preparations E5CN 9 Input power supply 10 STV − 4 Cold junction compensator + 5 0°C/32°F Compensating conductor E5CN-U 10 Input power supply 11 STV − 2 Cold junction compensator + 1 0°C/32°F Compensating conductor 1 E5AN/EN STV Input power supply 2 − 17 Cold junction compensator + 18 0°C/32°F Compensating conductor • Set the cold junction compensator designed for compensation of internal thermo
Section 6-3 Thermocouple Calibration (Thermocouple/Resistance Thermometer Input) In this example, calibration is shown for a Controller with a Thermocouple/ Resistance Thermometer Multi-input, with thermocouple/infrared temperature sensor set as the input type. 1,2,3... 1. Connect the power supply. 2. Connect a standard DC current/voltage source (STV), precision digital multimeter (DMM), and contact junction compensator (e.g.
Section 6-3 Thermocouple Calibration (Thermocouple/Resistance Thermometer Input) Press the M key. The display changes as shown on the left for input types 6, 8, 9, 10, 13, 14, 16, 17, 18, 19, 20, 21, and 22. Set the STV to −6 mV. Allow the count value on the No. 2 display to fully stabilize, then press the D key to temporarily register the calibration settings. If this count value is outside of the specified range, the No. 2 display will flash and the count value will not be temporarily registered. 9.
Platinum Resistance Thermometer Calibration (Thermocouple/Resistance Thermometer Input) 6-4 Section 6-4 Platinum Resistance Thermometer Calibration (Thermocouple/Resistance Thermometer Input) In this example, calibration is shown for Controller with a Thermocouple/ Resistance Thermometer Multi-input, with a resistance thermometer set as the input type. Use connecting wires of the same thickness. 1,2,3... 1. Connect the power supply. 2.
Platinum Resistance Thermometer Calibration (Thermocouple/Resistance Thermometer Input) Section 6-4 7. Next calibrate the B-B' input. Change the connections as follows: 9 E5CN Input power supply 10 A 3 B' 4 6-dial B 5 10 E5CN-U Input power supply 11 A 3 B' 2 6-dial B 1 1 E5AN/EN Input power supply 2 A 16 B' 17 6-dial B 18 pb10 4544 pb-0 4083 str no 8. When the M key is pressed, the status changes as shown to the left. Set the 6-dial to 10 Ω. Allow the count value on the No.
Section 6-5 Analog Input Calibration (Thermocouple/Resistance Thermometer Input) 6-5 Analog Input Calibration (Thermocouple/Resistance Thermometer Input) In this example, calibration is shown for a Controller with a Thermocouple/ Resistance Thermometer Multi-input, with an analog input (0 to 50 mV) set as the input type. E5CN E5CN-U E5AN/EN 9 10 Input power supply 1 Input power supply 10 Input power supply 11 2 STV 4 − STV 2 − STV 17 − DMM 5 + DMM 1 + DMM 18 + 1,2,3... 1.
Section 6-6 Calibrating Analog Input (Analog Input) 6-6 Calibrating Analog Input (Analog Input) 6-6-1 Calibrating a Current Input In this example, calibration is shown for a Controller with an Analog Input, with a current input set as the input type. 1,2,3... 1. Connect the power supply. 2. Connect an STV and DMM to the current input terminals, as shown in the following diagram.
Section 6-6 Calibrating Analog Input (Analog Input) 6-6-2 Calibrating a Voltage Input In this example, calibration is shown for a Controller with an Analog Input, with a voltage input set as the input type. 1,2,3... 1. Connect the power supply. 2. Connect an STV and DMM to the voltage input terminals, as shown in the following diagram. E5CN E5AN/EN 9 1 Input power supply Input power supply 10 adj 30 Input type 2 or 3: 1v-5 c7c3 STV 4 − STV 17 − DMM 5 + DMM 18 + 3. Turn the power ON. 4.
Section 6-7 Checking Indication Accuracy 6-7 Checking Indication Accuracy • After calibrating the input, be sure to check the indication accuracy to make sure that the calibration has been executed correctly. • Operate the E5CN/CN-U/AN/EN in the process value/set point monitor mode. • Check the indication accuracy at the following three values: upper limit, lower limit, and mid-point.
Section 6-7 Checking Indication Accuracy 6-7-2 Platinum Resistance Thermometer • Preparations The diagram below shows the required device connections. 9 E5CN Input power supply 10 A 3 B' 4 6-dial B 5 10 E5CN-U Input power supply 11 A 3 B' 2 6-dial B 1 1 E5AN/EN Input power supply 2 A 16 B' 17 6-dial B 18 • Operation Set the 6-dial to the resistance equivalent to the check value. 6-7-3 Analog Input • Preparations The diagram below shows the required device connections.
Section 6-7 Checking Indication Accuracy Current Input for a Controller with an Analog Input 9 E5CN Input power supply 10 + 3 − 4 1 STV E5AN/EN Input power supply 2 + 16 − 17 STV Voltage Input for a Controller with an Analog Input 9 E5CN Input power supply 10 − 4 + 5 1 STV E5AN/EN Input power supply 2 − 17 + 18 STV • Operation Set the STV output to the voltage or current equivalent to the check value.
Appendix A Specifications Ratings Supply voltage Operating voltage range 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC 85 to 110% of rated supply voltage Power consumption E5CN E5CN-U 7.5 VA 6 VA 5 VA/3 W 3 VA/2 W E5AN E5EN 11 VA 10 VA 5.5 VA/4 W 5.5 VA/4 W Sensor input (See note 1.
Appendix A Indication method Other functions 11-segment/7-segment digital display and single-lighting indicator Depend on the model Ambient temperature Ambient humidity −10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C 25% to 85% Storage temperature Altitude −25 to 65°C (with no condensation or icing) 2,000 m or less Recommended fuse Installation environment T2A, 250 VAC, time lag, low shut-off capacity Installation Category II, Pollution Class 2 (IEC 61010-1 compliant)
Appendix A Controllers with Thermocou- 0.1 to 999.9°C or °F) ple/Resistance Thermome- (in units of 0.1°C or °F) (See note 3.) ter Multi-inputs Hysteresis Controllers with Analog Inputs 0.01% to 99.99% FS (in units of 0.01% FS) Controllers with Thermocou- 0.1 to 999.9°C or °F) ple/Resistance Thermome- (in units of 0.1 EU) (See note 3.) ter Multi-inputs Proportional band (P) Controllers with Analog Inputs 0.1% to 999.9% FS (in units of 0.
Appendix A External Dimensions E54-CT1 2.8 10.5 di a. 3 25 5. 8 di a. 7.5 21 15 10 Tw o, 3. 5 40 30 E54-CT3 2.36 dia. 40 × 40 12 di a.
Appendix A E58-CIFQ1 USB-Serial Conversion Cable Specifications Item Applicable OS Specifications Windows 2000/XP Applicable software Applicable models Thermo Mini, CX-Thermo OMRON E5CN/CN-U Digital Temperature Controllers USB interface rating DTE speed Conforms to USB Specification 1.
Appendix A Error Displays When an error occurs, the error contents are shown on the No. 1 display. This section describes how to check error codes on the display, and the actions to be taken to remedy the problems. s.err Input Error Meaning The input value has exceeded the control range. (See note.
Appendix A Action Control continues, allowing normal operation. The message is displayed when the PV, PV/SP, or PV/MV is displayed. Resistance thermometer input (Except for models with a setting range of −199.9 to 500.0°C) Thermocouple input (Except for models with a setting range of −199.9 to 400.0°C) ES1B Control range s.err display Numeric display Resistance thermometer input (Except for models with a setting range of −1999. to 500.
Appendix A ffff Current Value Exceeds Meaning This error is displayed when the heater current value exceeds 55.0 A. Action Control continues, allowing normal operation. An error message is displayed when the following items are displayed. Heater current 1 value monitor Heater current 2 value monitor Leakage current 1 monitor Leakage current 2 monitor ct1 ct2 lcr1 lcr2 Heater Burnout HS Alarm Meaning When heater burnout or an HS alarm occurs, the No. 1 display in the applicable setting level flashes.
Appendix A Timing During operation Status Overshooting Undershooting Hunting Temperature is not rising Meaning ON/OFF control is enabled (default: ON/OFF control selected). Countermeasures Select PID control and execute either ST (self-tuning) or AT (auto-tuning). When using self-tuning, turn ON the power supply to the Temperature Controller and load (heater, etc.) at the same time, or turn ON the load power supply first.
Appendix A Timing During operation (continued) Status Temperature error is large Input error (S.err display) Meaning Thermometer has burnt out or short-circuited. Thermometer lead wires and power lines are in the same conduit, causing noise from the power lines (generally, display values will be unstable). Connection between the Temperature Controller and thermocouple is using copper wires. Installation location of thermometer is unsuitable.
Appendix A Parameter Operation Lists Multi-input: Controllers with Thermocouple/Resistance Thermometer Multi-inputs Analog input:Controllers with Analog Inputs Operation Level Parameters Process value Characters Set point Setting (monitor) value Sensor input indication range Display Default Unit SP lower limit to SP upper limit 0 EU 0 to 3 0 None Auto/manual switch Multi-SP set point setting Set point during SP ramp a-m m-sp sp-m SP lower limit to SP upper limit EU Heater current 1 value
Appendix A Adjustment Level Parameters Characters Adjustment level dis- l.adj play Setting (monitor) value Display Unit AT execute/cancel Communications writing Heater current 1 value monitor Heater current 2 value monitor at cmwt OFF, ON OFF, ON ct1 0.0 to 55.0 A ct2 0.0 to 55.0 A Leakage current 1 monitor lcr1 0.0 to 55.0 A Leakage current 2 monitor lcr2 0.0 to 55.0 A Heater burnout detection 1 Heater burnout detection 2 HS alarm 1 hb1 0.0 to 50.0 0.0 A hb2 0.0 to 50.0 0.
Appendix A Parameters Hysteresis (cooling) Characters Setting (monitor) value chys Multi-input: 0.1 to 999.9 Soak time Wait band soak wt-b Display Analog input: 0.01 to 99.99 1 to 9,999 Multi-input: OFF, 0.1 to 999.9 Default 1.0 0.10 off, 0.1 to 999.9 1 OFF off, 0.01 to OFF Analog input: OFF, 0.01 to 99.99 99.99 −5.0 to 105.0 (standard) 0.0 −105.0 to 105.0 (heating/cooling) −5.0 to 105.0 (standard) 0.0 −105.0 to 105.
Appendix A Parameters Scaling lower limit Characters Setting (monitor) value in-l −1,999 to scaling upper limit −1 Decimal point dp Multi-input: 0 to 1 Analog input: 0 to 3 Temperature unit SP upper limit d-u sl-h °C, °F SP lower limit + 1 / input range lower limit (temperature) Display c, f 0 Default Unit None 0 0 None None °C 1300 None EU SP lower limit + 1 / scaling upper limit (analog) Input range lower limit to SP upper limit − 1 (temperature) Scaling lower limit to SP upper limit − 1
Appendix A Parameters Alarm 2 type Alarm 3 type Transfer output type Transfer output upper limit Characters Setting (monitor) value alt2 0: Alarm function OFF 1: Upper and lower-limit alarm 2: Upper-limit alarm 3: Lower-limit alarm 4: Upper and lower-limit range alarm 5: Upper and lower-limit alarm with standby sequence 6: Upper-limit alarm with standby sequence 7: Lower-limit alarm with standby sequence 8: Absolute-value upper-limit alarm 9: Absolute-value lower-limit alarm 10: Absolute-value upper-limi
Appendix A Parameters Event input assignment 2 Characters Setting (monitor) value ev-2 NONE: None STOP: RUN/STOP MANU: Auto/manual switch PRST: Program start (See note 5.
Appendix A Parameters PV change color Characters Setting (monitor) value colr Orange, Red, Green Display org, red, grn Red to Green: When ALM1 is r-g lit, Green to Red: When ALM1 is g-r lit Red to Green to Red r-g.r Within PV stable band: Green Outside stable band: Red Green to Orange to Red g-o.r Within PV stable band: Green Outside stable band: Green, Red Orange to Green to Red o-g.
Appendix A Parameters Control output 1 assignment Control output 2 assignment Alarm 1 assignment Alarm 2 assignment Alarm 3 assignment (E5AN/E5EN only) Character select Soak time unit 216 Characters Setting (monitor) value out1 When control output 1 is a pulse output (See note 2.): NONE: No assignment O: Control output (heating) C-O: Control output (cooling) ALM1: Alarm 1 ALM2: Alarm 2 ALM3: Alarm 3 P.END: Program end output (See note 4.) When control output 1 is a linear output (See note 2.
Appendix A Parameters Alarm SP selection Characters Setting (monitor) value alsp SP-M: Ramp set point SP: Set point Move to calibration level cmov Display sp-m, sp −1999 to 9,999 Default SP-M Unit None 0 None Set value Protect Level Parameters Characters Move to protect level pmov Operation/adjustoapt ment protect Setting (monitor) value Display Default Unit −1999 to 9,999 0 to 3 0 0 None None 1 None Initial setting/communications protect icpt 0 to 2 Setting change protect wtpt O
Appendix A Note (1) Transfer output type Setting (monitor) range Set point SP lower limit to SP upper limit Default (transfer output upper/lower limits) (See note 1.1.) SP upper limit/lower limit Set point during SP ramp PV SP lower limit to SP upper limit SP upper limit/lower limit EU Temperature: Sensor setting range lower limit to sensor setting range upper limit Sensor setting range upper/ lower limit EU Scaling upper/lower limit EU 100.0/0.0 % 100.0/0.
Appendix A Sensor Input Setting Range, Indication Range, Control Range Controllers with Thermocouple/ Resistance Thermometer Multiinputs Input type Specifications Set value Resistance ther- Pt100 0 mometer 1 Input temperature range −200 to 850 (°C)/−300 to 1,500 (°F) −199.9 to 500.0 (°C)/−199.9 to 900.0 (°F) 0.0 to 100.0 (°C)/0.0 to 210.0 (°F) Input indication range −220 to 870 (°C)/−340 to 1,540 (°F) −199.9 to 520.0 (°C)/−199.9 to 940.0 (°F) −20.0 to 120.0 (°C)/−40.0 to 250.0 (°F) 3 −199.9 to 500.
Appendix A Controllers with Analog Inputs Input type Current input Specifications Set value 0 4 to 20 mA Voltage input 0 to 20 mA 1 to 5 V 1 2 0 to 5 V 0 to 10 V 3 4 Input temperature range Any of the following ranges, by scaling: −1,999 to 9,999 −199.9 to 999.9 −19.99 to 99.99 −1.999 to 9.999 Input indication range −5% to 105% of setting range. The display shows −1999 to 9999 (numeric range with decimal point omitted).
Appendix A Setting Levels Diagram This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level. Power ON Started in manual mode. Started in automatic mode. Press the O Key for at least 1 s. Operation Level C Manual mode (See note 3.
Appendix A Press the O Key for at least 3 s. Displays other than that for switching between automatic and manual. Power ON Parameter Flow Starting in manual mode. This section describes the parameters set in each level. Pressing the M key at the last parameter in each level returns to the top parameter in that level. Manual control level C 25 PID control only Press the O Key for at least 1 s Starting in automatic mode. PV/MV Press the O Key less than 1 s.
Appendix A Press the O Key for at least 1 s. Initial Setting Level Advanced Function Setting Level Press the O Key less than 1 s.
Index Numerics 2-PID control, 38, 149 A adjustment level, 11, 129 parameter operation list, 210 advanced function setting level, 11, 157 moving to, 84, 156 parameter operation list, 213 alarm delays, 92 alarms, 8 alarm 1 assignment, 178 alarm 2 assignment, 179 alarm 3 assignment, 180 alarm delays, 92 alarm hysteresis, 71 alarm latch, 71 alarm outputs, 40, 51 alarm outputs 1 and 2 wiring, 26 alarm types, 51 alarm values, 53 operation, 72 analog input, 8, 73, 196 calibration, 192, 193 AT (auto-tuning), 45 AT
Index E5CN, 16 E5CN-U, 16 E5EN, 17 direct operation, 39, 152 Display Range Exceeded (error display), 204 down key, 4 E error displays, 202 Current Value Exceeds, 206 Display Range Exceeded, 204 HB Error, 205 Heater Burnout, 206 HS Alarm, 206 Input Error, 204 Memory Error, 205 event inputs, 9, 27, 77, 78 wiring, 27 external dimensions Current Transformer (CT), 202 external power supply for ES1B, 9, 29, 68, 200 I I/O configuration, 5 basic model E5AN, 7 E5CN, 5 E5CN-U, 6 E5EN, 7 main functions, 8 indication
Index integral time, 50 K keys down key, 4 key operations, 10 level key, 4 mode key, 4 operations, 4 up key, 4 O ON/OFF control, 38, 149 setting, 44 one-point shift, 69 open in alarm, 72 operation level, 11, 118 parameter operation list, 209 operation/adjustment protect, 86 output functions assignments, 40 output limits, 110 L LBA (loop break alarm), 94 band, 95 detection time, 95 level, 95, 96 level key, 4 loop break alarm (LBA), 94 M main functions, 8 manual control, 80, 97 manual control level, 11 mo
Index alarm 2 type, 154 alarm 3 assignment, 180 alarm 3 hysteresis, 163 alarm 3 latch, 167 alarm 3 OFF delay, 172 alarm 3 ON delay, 171 alarm 3 open in alarm, 162 alarm 3 type, 154 alarm SP selection, 181 alarm value 1, 124 alarm value 2, 125 alarm value 3, 125 alarm value lower limit 1, 126 alarm value lower limit 2, 126 alarm value lower limit 3, 127 alarm value upper limit 1, 126 alarm value upper limit 2, 126 alarm value upper limit 3, 127 alpha, 165 AT execute/cancel, 131 auto/manual select addition, 1
Index send data wait time, 182 set point during SP ramp, 121 setting change protect, 116 soak time, 141 soak time remain, 124 soak time unit, 181 SP 0, 136 SP 1, 136 SP 2, 136 SP 3, 136 SP lower limit, 149 SP ramp set value, 143 SP ramp time unit, 161 SP upper limit, 149 ST (self-tuning), 150 ST stable range, 165 standard or heating/cooling, 150 standby sequence reset, 161 temperature input shift, 136 temperature unit, 148 transfer output lower limit, 155 transfer output type, 155 transfer output upper limi
Index HS alarm, 63 moving to advanced function setting level, 62 hysteresis, 45 LBA detection time, 95 password, 88 PID ON/OFF, 44 SP lower limit, 82 SP upper limit, 81 switching between SPs, 79 shifting input values, 67 simple program function, 104, 109 controlling start, 80 starting, 106 soak time, 106 SP ramp, 82 alarm operations, 84 operation at startup, 83 restrictions, 83 specifications, 199 Current Transformer (CT), 201 external power supply for ES1B, 29 output, 38 USB-Serial Conversion Cable, 203 ST
Revision History A manual revision code appears as a suffix to the catalog number on the front cover of the manual. Cat. No. H134-E1-01A Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version. Revision code 01 01A Date February 2005 Revised content Original production November 2005 Page 21: Middle illustration changed. Page 138: Hysteresis (cooling) setting range corrected. Page 151: Set value of 12 added to table.