User Manual

NO. MODE DISPLAY FUNCTION RANGE UNIT DEFAULT USER REMARKS
79 init PARAMETER INITIALIZE off / fact / user - off off keep settings, fact return to factory defaults, user reset cust defaults
80
ev-m NUMBER OF MULTI SP USED 0 to 2 - 1 0= No SP via event 1= 1 event I/P for (2)SP 2= 2 event I/P for (4)SP
81
eV-1 EVENT INPUT ASSIGNMENT 1 none / stop / manu / prst - none if Event I/P closed, control=stopped, Manual MV=selected or program=started
82
eV-2 EVENT INPUT ASSIGNMENT 2 none / stop / manu / prst - stop if selected and Event I/P closed, control is stopped or program is strated
83
mspu MULTI SP USES off / on - off OFF means only one setvalue (SP) available ON means 4 SP available
84
spru SETPOINT RAMP TIME UNIT Seconds / Minutes - m Amount of E.U. per second or per minute of SP ramp
85
rest STANDBY SEQUENCE RESET METHOD a / b - a In mode b the alarm stand-by condition is only reset on power up
86
al1n ALARM 1 OPEN IN ALARM n-o / n-c - n-o n-o Close relay in Alarm n-c Open relay in Alarm
87
alh1 ALARM 1 HYSTERESIS 0.1 - 999.9 E.U, 0.2 Difference between switch ON and Switch OFF alarm. (E5CN-xxL type 0.02)
88
al2n ALARM 2 OPEN IN ALARM n-o / n-c - n-o n-o Close relay in Alarm n-c Open relay in Alarm
89
alh2 ALARM 2 HYSTERESIS 0.1 - 999.9 E.U, 0.2 Difference between switch ON and Switch OFF alarm. (E5CN-xxL type 0.02)
90
al3n ALARM 3 OPEN IN ALARM n-o / n-c - n-o n-o Close relay in Alarm n-c Open relay in Alarm
91
alh3 ALARM 3 HYSTERESIS 0.1 - 999.9 E.U, 0.2 Difference between switch ON and Switch OFF alarm. (E5CN-xxL type 0.02)
92
hbu HBA (HEATER BURNOUT ALARM) USED off / on - on HBA alarm enabled
93
hbl HBA LATCH off / on - off HBA alarm latched (alarm is hold until operator resets the alarm)
94
hbh HBA HYSTERESIS 0.1 to 50.0 A 0.1 Difference between switch ON and Switch OFF alarm.
95
st-b ST (SELF TUNE) STABLE RANGE 0,1 to 999,9 °C / °F 15.0 When PV goes out of stable range, tune is started if st is on (line 66)
96
alfa ALFA: SETVALUE CHANGE FEED FORWARD 0,00 to 1,00 - 0.65 OMRON's unique 2PID control feature, 0,65 is good for most applications
97
inf INPUT FILTER 0.0 - 999.9 SEC 0.0 Digital first order input filter with time constant to be set
98
pVad ADDITIONAL PV DISPLAY off / on - off When set to on it is possible to show PV without SV
99
o-dp MANIPULATED VARIABLE (MV) DISPLAY off / on - off when set to on it is possible to show mv in scroll list
100
ret AUTOMATIC RETURN OF DISPLAY MODE off , 1 to 99 SEC off Automatic fall back to operator level (time set)
101
a1lt ALARM 1 LATCH off / on - off To reset latch: power on/off or move in/out of setting level
102
a2lt ALARM 2 LATCH off / on - off To reset latch: power on/off or move in/out of setting level
103
a3lt ALARM 3 LATCH off / on - off To reset latch: power on/off or move in/out of setting level
104
prlt PROTECT LEVEL MOVE TIME 1 to 30 SEC 3 Key pressing time required to move to protect level
105 ADVANCED
sero INPUT SENSOR ERROR ALARM off / on - off When set to on alarm 1 becomes "or" with this alarm
106 FUNCTION
cjc COLD JUNCTION COMPENSATION METHOD off / on - on on =Internal CJC off External CJC
107 SETTING
rlrv MB COMMAND LOGIC SWITCHING off / on - off When set to on communication is according to E5_J
108 LEVEL
colr PV COLOR CHANGE FUNCTION --> - red *2 org red grn r-g g-r r-g.r g-or o-gr
109 pv-b PV COLOR CHANGE STABLE BAND 0.1 to 999.9 E.U, 5.0 PV display is green when PV is within the stable band
110
a1on ALARM 1 ON DELAY 0 - 999 SEC 0 Set the time for the alarm condition to be present before the alarm is active
111
a2on ALARM 2 ON DELAY 0 - 999 SEC 0 Set the time for the alarm condition to be present before the alarm is active
112
a3on ALARM 3 ON DELAY 0 - 999 SEC 0 Set the time for the alarm condition to be present before the alarm is active
113
a1of ALARM 1 OFF DELAY 0 - 999 SEC 0 Set the time for the alarm condition to be present before the alarm is deactive
114
a2of ALARM 2 OFF DELAY 0 - 999 SEC 0 Set the time for the alarm condition to be present before the alarm is deactive
115
a3of ALARM 3 OFF DELAY 0 - 999 SEC 0 Set the time for the alarm condition to be present before the alarm is deactive
116
istp INPUT SHIFT TYPE ins1 / ins2 -
ins1
One point (linear offset) or Two point input shift (offset & gain alternative)
117
mvse MV AT SENSOR ERROR & STOP SELECT off / on - off When off MV at error is 0%. when on MV value is set at line 52/53
118
amad AUTO/MANUAL SELECT ADDITIONAL off / on -
on
Shows or Hide the Auto/Manual selection display in the operator list
119
rt RT (robust tuning) off / on - off New style auto tuning, use when PV hunting is becomes a problem
120
hsu HSA (HEATER SSR SHORT ALARM) USED off / on - off Heater/SSR Short alarm enabled
121
hsl HSA LATCH off / on - off HSA alarm latched (alarm is hold until operator resets the alarm)
122
hsh HSA HYSTERESIS 0.1 to 50.0 A 0.1 Difference between switch ON and Switch OFF alarm.
123
lba LBA (LOOP BREAK ALARM) DETECTION TIME 0 - 9999 SEC 0 0 means LBA is off. For E5CN-xxL types range = 0.00 to 99.99
124
lbal LBA LEVEL 0.1 to 999.9 (0.01 to 99.99 *4) E.U, 8 set this value the same as the P value, For E5CN-xxL type default is 10% f.s.
125
lbab LBA BAND 0.0 to 999.9 E.U. 3 For E5CN-xxL type default is 0.20
126 out1 CONTROL OUTPUT 1 ASSIGNMENT *4 + *5 - o Select function for output 1 : none, output, alarm, or Program end
127
out2 CONTROL OUTPUT 2 ASSIGNMENT *4 - none Select function for output 2 : none, output, alarm, or Program end
128
alm1 SUB / AUX / ALM OUTPUT 1 ASSIGNMENT *4 - alm1 Select function for sub output 1 : none, output, alarm, or Program end
129
alm2 SUB / AUX / ALM OUTPUT 2 ASSIGNMENT *4 - alm2 Select function for sub output 2 : none, output, alarm, or Program end
130
csel CHARACTER SELECT off / on -
on
use 11 of 7 segments display, set of off if you need old style 7 segment
131
t-u SOAK TIME UNIT Minute / Hour -
m
132 alsp ALARM SETPOINT SELECTION sp-m / sp -
sp-m
alarm react on target SP or on SP during ramp
133 cmov CALIBRATION MOVE PARAMETER -1.999 to 9.999 0 Move to calibration mode
134
psel PROTOCOL SELECT cwf / mod - cwf select communications protocol, CompowayF or Modbus RTU
135 COMMUNICA-
u-no COMMUNICATIONS UNIT NO. 0 - 99 - 1 Controller's address
136 TIONS
bps BAUD RATE 1.2 2.4 4.8 9.6 19.2 38.4 kbps 9.6 Communication speed
137 SETTING
len COMMUNICATIONS DATA LENGTH 7 / 8 BITS 7 To set the length of data
138 LEVEL
sbit COMMUNICATIONS STOP BIT 1 / 2 BITS 2 Number of stop bits
139
prty COMMUNICATIONS PARITY none / even / odd - even To set the parity check bit
140 sdwt SEND DATA WAIT TIME 0 - 99 ms 20 time wait before reply is given
NOT ALL PARAMETERS ARE SHOWN AT ALL TIMES ! !, ( DEPEND ON FUNCTION AVAILABLE OR SELECTED) BLUE: Input and PV
* 1 AFTER THE TEMPERATURE INPUT TYPE IS SET, THE UPPER AND LOWER SCALING VALUES CAN BE SET GREEN: Control / PID
* 2 PV is FIXED ORANGE or FIXED RED or FIXED GREEN or RED>GREEN on ALM1 or GREEN>RED on ALM1 PURPLE: Alarms
or GREEN within stable band and RED outside or GREEN below, ORANGE within and RED obove or ORANGE below GREEN within and RED above GREY: MV / Output
* 3 MORE DETAILS AT THE BOTOM OF THIS OR THE OTHER SIDE PAGE YELLOW: SetValue SV/SP
* 4
none o c-o alm1 alm2 alm3 p.end *5 E5CN-xxxL type none o c-o only
ORANGE: HA Heater Alarm (Burnout and SSR short)
CN
new E5CN- Parameter List
NEW