NO. MODE DISPLAY FUNCTION RANGE UNIT DEFAULT USER REMARKS
1 pmov MOVE TO PROTECT LEVEL -1999 to 9999 - 0 *3 Only available when password <> zero (0)
2
oapt OPERATION / ADJUSTMENT PROTECTION 0 to 3 - 0 *3 Protect level of parameter (0=Low 3=High)
3 PROTECT
icpt INITIAL SETTING / COMMUNICATION PROTECT 0 to 2 - 1 *3 Protect level of levels (0=Low 2=High)
4 LEVEL
wtpt SETTING CHANGE PROTECTION off / on - off *3
5
pmsk PARAMETER MASK off / on - on *3 Displayed only when setting parameter mask, off shows all parameter
6 prlp MOVE TO PROTECT LEVEL PASSWORD -1999 to 9999 - 0
*3 press "level" key with up/down key to change password
7
a-m AUTO/MANUAL SELECT - - --Pid control only, displayed when "Additional Auto/Manual select" is on
8
m-sp MULTI SETPOINT (SETPOINT 0-3) 0 to 3 - 0 Gives the number of the current active setvalue (0-3)
9
sp-m SETPOINT DURING SP RAMP READ ONLY E.U. --Current setvalue while sv is ramping up to target sv
10
ct1 ct2 HEATER CURRENT 1 AND 2 VALUE MONITOR READ ONLY A --Reads the heater current trough CT in conduction (MV <> 0%)
11
lcr1 lcr2 LEAKAGE CURRENT 1 AND 2 VALUE MONITOR READ ONLY A --Reads the heater current trough CT when MV = 0%
12 prst PROGRAM START
rset / strt
- rset
Programmer idle (rset) or running (strt )
13
sktr SOAK TIME REMAINING 0 - 9999 m/h --Reads the remaining soak time before program end
14 OPERATION r-s RUN / STOP MODE
run / stop
- run
stop
= No control, only PV measurement and alarms
15 LEVEL
al-1 ALARM VALUE 1 -1999 to 9999 E.U. 0 *3 Set Alarm value X for alt1 =2, 3, 6, 7, 8, 9, 10 and 11
16
al1h ALARM VALUE 1 UPPER LIMIT -1999 to 9999 E.U. 0 *3 Set Alarm value H for alt1 =1, 4 and 5
17
al1l ALARM VALUE 1 LOWER LIMIT -1999 to 9999 E.U. 0 *3 Set Alarm value L for alt1 =1, 4 and 5
18
al-2 ALARM VALUE 2 -1999 to 9999 E.U. 0 *3 Set Alarm value X for alt2 =2, 3, 6, 7, 8, 9, 10 and 11
19
al2h ALARM VALUE 2 UPPER LIMIT -1999 to 9999 E.U. 0 *3 Set Alarm value H for alt2 =1, 4 and 5
20
al2l ALARM VALUE 2 LOWER LIMIT -1999 to 9999 E.U. 0 *3 Set Alarm value L for alt2 =1, 4 and 5
21
al-3 ALARM VALUE 3 -1999 to 9999 E.U. 0 *3 Set Alarm value X for alt3 =2, 3, 6, 7, 8, 9, 10 and 11
22
al3h ALARM VALUE 3 UPPER LIMIT -1999 to 9999 E.U. 0 *3 Set Alarm value H for alt3 =1, 4 and 5
23
al3l ALARM VALUE 3 LOWER LIMIT -1999 to 9999 E.U. 0 *3 Set Alarm value L for alt3 =1, 4 and 5
24
o MV MONITOR (OUT1) READ ONLY % - - Read PID heat output value
25
c-o MV MONITOR (OUT2) READ ONLY % --Read PID cool output value
26
l.adj ADJUSTMENT LEVEL READ ONLY - --Displayed one time when moving to adjustment level
27
at AUTO TUNE EXECUTE/CANCEL off / on - off Performs a one shot autotune
28
cmwt COMMUNICATION WRITING ALLOWED off / on - off Parameter writing through serial comms allowed
29
ct1 ct2 HEATER CURRENT 1 AND 2 VALUE MONITOR READ ONLY A - - Reads the heater current trough CT in conduction (MV <> 0%)
30
lcr1 lcr2 LEAKAGE CURRENT 1 AND 2 VALUE MONITOR READ ONLY A - - Reads the heater current trough CT when MV = 0%
31
hb1 HEATER BURNOUT DETECTION 1 0,0 to 50,0 A 0.0 Set low current detection level (0 = OFF)
32
hb2 HEATER BURNOUT DETECTION 2 0,0 to 50,0 A 0.0 Set low current detection level (0 = OFF)
33
hs1 HEATER SHORT SSR DETECTION 1 0,0 to 50,0 A 50.0 Set high leakage current detection level (50 = OFF)
34
hs2 HEATER SHORT SSR DETECTION 2 0,0 to 50,0 A 50.0 Set high leakage current detection level (50 = OFF)
35
sp-0 SET POINT 0 SETPOINT UPPER to LOWER E.U. 0
36 sp-1 SET POINT 1 SETPOINT UPPER to LOWER E.U. 0
37 sp-2 SET POINT 2 SETPOINT UPPER to LOWER E.U. 0
38 sp-3 SET POINT 3 SETPOINT UPPER to LOWER E.U. 0
39 ins TEMPERATURE INPUT SHIFT -199,9 to 999,9 E.U. 0.0 Trim the PV to match an external reference source, linear 1 point methode
40
insh TEMPERATURE INPUT SHIFT UPPER LIMIT -199,9 to 999,9 E.U. 0.0 Trim the PV to match an external reference source, high point
41
insl TEMPERATURE INPUT SHIFT LOWER LIMIT -199,9 to 999,9 E.U. 0.0 Trim the PV to match an external reference source, low point
42
p PROPORTIONAL BAND 0,1 to 999,9 E.U. 8.0 *4 with E5CN-xxxL : P = 10% f.s.
43 ADJUSTMENT
i INTEGRAL TIME 0 TO 3999 SEC 233 If "I" = 0 then "of-r" (line 47) is 50% by default
44 LEVEL
d DIFFERENTIAL TIME 0 TO 3999 SEC 40 When RT is on (line 119) range is 0.0 to 999.9
45
c-sc COOLING COEFFICIENT 0,01 to 99,99 - 1.00 Only Heat/Cool operation. Balance control by adjusing cool output gain
46
c-db DEAD BAND -199,9 to 999,9 (-19.99 to 99.99 *4) E.U. 0.0 Only Heat/Cool operation. Area around 0% MV where MV is forced to 0%
47
of-r MANUAL RESET VALUE 0,0 to 100,0 % 50.0 Remove PV-SV offset in P or PD operation (available when I=0)
48
hys HYSTERESIS (OUT1) 0,1 to 999,9 (0.01 to 99.99 *4) E.U. 1.0 Only On/Off operation. Ouput OFF at SV, Output ON at SV - hys (0,1 for *4)
49
c-hys HYSTERESIS (OUT2) 0,1 to 999,9 (0.01 to 99.99 *4) E.U. 1.0 Only On/Off operation. Ouput OFF at SV, Output ON at SV + hys (0,1 for *4)
50
soak PROGRAM SOAK TIME 1 - 9999 m/h 0 Set time for Soak/Dwell here
51
wt-b PROGRAM WAIT BAND OFF, 0,1 to 999,9 E.U, off When the PV goes outside the band the Soak time is on WAIT
52
mv-s MANUAL VALUE AT STOP MV UPPER to LOWER LIMIT % 0.0 Forced output % when the controller is stopped (RUN/STOP)
53
mv-e MANUAL VALUE AT PV ERROR MV UPPER to LOWER LIMIT % 0.0 Forced output % when the sensor error break alarm is active
54
sprt SP RAMP SET VALUE OFF, 1 to 9999 E.U, off Maximum change of SV per minute or second (set with parameter #84)
55
ol-h MV UPPER LIMIT 0.0 to 105.0 % 105.0 0.0 is not valid when using standard control (-0.1 or 0.1 is used)
56 ol-l MV LOWER LIMIT
(-105.0) -5.0 to 0.0 (or
ol-h)
%
.-5.0 105.0 DEPENDING ON standard OR Heat & Cool Control
57
in-t INPUT TYPE 0 to 23 - 5 *3 *4 For Analogue Input Type (E5CN-xxxL) range = 0 - 4 default is 0
58
in-h SCALING UPPER LIMIT SCALE LOW+1 to 9999 E.U. 100 *1 Analogue input only
59
in-l SCALING LOWER LIMIT -1999 to SCALE HIGH -1 E.U. 0 *1 Analogue input only
60
dp DECIMAL POINT 0 to 1 - 0 Setting provides xxxx or xxx.x display (*4 = 0 to 4 decimal places)
61
d-u TEMPERATURE UNIT SELECTION C / F - °C Select degree Centigrade of Farenheit
62
sl-h SETVALUE UPPER LIMIT sl-l+1 to SENSOR High - 1300 *1 (Default Pt100 setting = 850 Default *4 setting 100)
63
sl-l SETVALUE LOWER LIMIT SENSOR Low to sl-h-1 - -200 *1 (Default *4 setting 0)
64
cntl CONTROL: PID - ON/OFF pid / onof - onof pid = 2PID - onof = ON/OFF
65 INITIAL
s-hc CONTROL: STANDARD - HEAT&COOL stnd / h-c - stnd stnd =Standard h-c=Heat&Cool (with H&C 2 alarms max, not 3)
66 SETTING
st ST SELF TUNING off / on - on on Starts AT on power-up and when <> st-b (line 95)
67 LEVEL
ptrn PROGRAM PATERN TYPE off / stop / cont - off type of programmer, OFF or Continue (run) / Stop (run) at end of soak/dwell
68
cp CONTROL PERIOD (OUT1) 0.5, 1 to 99 (steps of 1 sec) SEC 20 OUT1 duty cycle at 100% MV (heat)
69
c-cp CONTROL PERIOD (OUT2) 0.5, 1 to 99 (steps of 1 sec) SEC 20 OUT2 duty cycle at 100% MV (cool)
70
oreV DIRECT / REVERSE OPERATION or-r / or-d - or-r Usually REVERSE is for heat and DIRECT is for cool applications
71
alt1 ALARM 1 TYPE 0 to 12 - 2 *3 Alarm Type 1 is not shown when ptrn (line 67) is in use (Cont or Stop)
72
alt2 ALARM 2 TYPE 0 to 11 - 2 *3
73
alt3 ALARM 3 TYPE 0 to 11 - 2 *3
74
tr-t TRANSFER OUTPUT TYPE off sp sp-m pv mv c-mv - off Only for Linear Ouput models (E5CN-Cxxx-xxx)
75
tr-h TRANSFER OUTPUT UPPER LIMIT low to high of SP, MV or PV - 100.0 Only for Linear Ouput models (E5CN-Cxxx-xxx)
76
tr-l TRANSFER OUTPUT LOWER LIMIT low to high of SP, MV or PV - 0.0 Only for Linear Ouput models (E5CN-Cxxx-xxx)
77
o1-t LINEAR OUTPUT TYPE 0-20 / 4-20 mA 4-20 Only for Linear Ouput models (E5CN-Cxxx-xxx)
78 amoV MOVE TO ADVANCED FUNCTION SETTING LEVEL -1.999 to 9.999 - 0 Move to ADVANCED level with -169 (default factory setting)
NOT ALL PARAMETERS ARE SHOWN AT ALL TIMES ! !, ( DEPEND ON FUNCTION AVAILABLE OR SELECTED) BLUE: Input and PV
* 1 AFTER THE TEMPERATURE INPUT TYPE IS SET, THE UPPER AND LOWER SCALING VALUES CAN BE SET GREEN: Control / PID
* 2 PV IS FIXED RED OR FIXED GREEN OR GREEN>RED ON ALM1 OR RED>GREEN ON ALM1 PURPLE: Alarms
OR GREEN WITHIN STABLE BAND AND RED OUTSIDE OR AMBER BELOW, GREEN WITHIN AND RED ABOVE BAND GREY: MV / Output
* 3 MORE DETAILS AT THE BOTOM OF THIS OR THE OTHER SIDE PAGE YELLOW: SetValue SV/SP
* 4
V
alid for E5CN-xxxL-500 linear input models ORANGE: HA Heater Alarm (Burnout and SSR short)
new E5CN- Parameter List