Datasheet

E5GC
9
Characteristics
*1. The indication accuracy of K thermocouples in the 200 to 1,300C range, T and N thermocouples at a temperature of 100C max., and U
and L thermocouples at any temperature is 2C 1 digit max. The indication accuracy of B thermocouples at a temperature of 400C max. is
not specified. The indication accur
acy of B thermocouples at a temperature of 400 to 800C is 3C max.
The indication accuracy of R and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W
thermocouples is (0.3% of PV or 3C, whichever is greater) 1 digit max.
The indication accur
acy of PLII thermocouples is (0.3% of PV or 2C, whichever is greater) 1 digit max.
*2. However, the precision between 0 and 4 mA for a 0 to 20 mA output is 1% FS max.
*3. Ambient temperature: 10C to 23C to 55C, Voltage range: 15% to 10% of rated voltage
*4. K thermocouple at 100C max.: 10C max.
*5. The unit is determined by the setting of the Integral/Deriva
tive Time Unit parameter.
*6. External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.
*7. Refer to your OMRON website for the most recent information on applicable models.
*8. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Indication accuracy
(at the temperature of 23C)
Thermocouple: (0.3 % of indication value or 1C, whichever is greater) 1 digit max.*1
Platinum resistance thermometer: (0.2 % of indication value or 0.8C, whichever is greater) 1 digit max.
Analog input:
0.2% FS
1 digit max.
CT input: 5% FS 1 digit max.
Simple transfer output accuracy 0.3% FS max.*2
Influence of temperature *3
Thermocouple input (R, S, B, W, PL II): (
1% of indication value or
10
C, whichever is greater)
1 digit max.
Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *4
Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Analog input: 1% FS 1 digit max.
CT input: 5% FS 1 digit max.
Influence of voltage *3
Influence of EMS.
(at EN 61326-1)
Input sampling period 50 ms
Hysteresis
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Proportional band (P) for cooling
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 (decimal point position depends on input type)
Influence of signal source
resistance
Thermocouple: 0.1C/ max. (100 max.), Platinum resistance thermometer: 0.1C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength
100 to 240 VAC: 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
24 VAC/DC: 2,300 VAC, 50/60 Hz for 1 min between terminals of different charge
Vibration
Malfunction 10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y and Z directions
Resistance 10 to 55 Hz, 20 m/s
2
for 2 hr each in X, Y, and Z directions
Shock
Malfunction 100 m/s
2
, 3 times each in X, Y, and Z directions
Resistance 300 m/s
2
, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 80 g, Adapter: Approx. 4 g 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.62 or higher
Setup Tool port
E5GC side panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer. *6
E5GC bottom panel: An E58 -CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable
are used together to connect a USB port on the computer. *6
Standards
Approved standards
cULus: UL 61010-1/CSA C22.2 No.61010-1, Korean wireless regulations (Radio law: KC Mark) (Some
models only.) *7
Conformed standards EN 61010-1 (IEC 61010-1)
EMC
EMI: EN61326-1 *8
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage: EN55011 Group 1, class A
EMS: EN61326-1 *8
ESD Immunity: EN61000-4-2
Electromagnetic Field Immunity: EN61000-4-3
Burst Noise Immunity: EN61000-4-4
Conducted Disturbance Immunity: EN61000-4-6
Surge Immunity: EN61000-4-5
Voltage Dip/Interrupting Immunity: EN61000-4-11