New Product Digital Temperature Controller E5@C/E5@C-T E5@C Series That Pursues Greater Visibility with Large White PV Display. Added new models with Push-In Plus Terminal that Reduce Wiring Work.
Digital Temperature Controller E5GC (48 24 mm) Easy Operation and High Performance of the E5@C Series in a Compact 48 24mm Body • A compact body of 48 24 90 mm (W H D) that is ideal for small equipment, laboratory instruments, and others. • White PV display with a height of 10.5 mm for high visibility even with the compact body. • Removable terminal block to simplify maintenance. Select from screw terminal or screwless clamp terminal for the wiring method. • High-speed sampling at 50 ms.
E5GC Model Number Legend and Standard Models Model Number Legend E5GC-@@ @ @ @ M-@@@ (Example: E5GC-RX1A6M-015) A B C D E F Model A B Control No. of outputs 1 auxiliary and 2 outputs C Power supply voltage D E F Terminal type Input type Options Meaning 48 24 mm E5GC Control output 1 Relay output Voltage output (for driving SSR) Linear current output RX QX *1 CX *2 0 1 2 A D 6 C M *3 *3, *4 *5 *1. *2. *3. *4. *5. *6.
E5GC Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2 Communications Conversion Cable Model E58-CIFQ2-E Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the bottom-panel Setup Tool port. Current Transformers (CTs) Hole diameter 5.8 mm 12.0 mm Model E54-CT1 E54-CT3 Mounting Adapter Model Y92F-53 (2pcs) Note: This Mounting Adapter is provided with the Digital Temperature Controller.
E5GC Specifications Ratings Power supply voltage Operating voltage range Power consumption Sensor input Input impedance Control method Relay output Control output Auxiliary output Voltage output (for driving SSR) Linear current output Number of outputs Output specifications Number of inputs Event input External contact input specifications Setting method Indication method Multi SP Bank switching Other functions Ambient operating temperature Ambient operating humidity Storage temperature Altitude R
E5GC Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type Platinum resistance thermometer Sensor specification Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 120 165 140 to 260°C 2300 2300 1800 1800 1700 1700 1700 1600 1500 Temperature range (°C) 1400 1300 1300 1300 1300 1200 1100 1000 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.
E5GC Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.) Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1.
E5GC *1. With set values 1, 4, and 5, the upper- and lower-limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm Case 3 (Always OFF) Case 2 Case 1 H<0, L<0 L H SP H<0, L>0 |H| < |L| H SP L H H>0, L<0 |H| > |L| H SP L H<0, L>0 |H| ≥ |L| L SP SP H L H>0, L<0 |H| ≤ |L| *3.
E5GC Characteristics Indication accuracy (at the temperature of 23C) Simple transfer output accuracy Influence of temperature *3 Influence of voltage *3 Influence of EMS. (at EN 61326-1) Input sampling period Hysteresis Proportional band (P) Integral time (I) Derivative time (D) Proportional band (P) for cooling Integral time (I) for cooling Derivative time (D) for cooling Control period Manual reset value Alarm setting range Influence of signal source resistance Insulation resistance Thermocouple: (0.
E5GC Windows XP/Vista/7/8/10 *1 CX-Thermo version 4.62 or higher E5@C-T Series, E5@C Series, and E5CB Series Conforms to USB Specification 2.0 38,400 bps Computer: USB (Type A plug) Connector Digital Temperature Controller: Special serial specifications connector Power supply Bus power (Supplied from the USB host controller) *2 Power supply voltage 5 VDC Current 450 mA max. consumption 4.70.2 VDC (Supplied from USB-Serial Conversion Output voltage Cable to the Digital Temperature Controller.) 250 mA max.
E5GC External Connections E5GC Control Outputs E5GC-@ @ @ @ @ M - @ @ @ Relay output 250 VAC, 2 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max. (1) (2)(3)(4)(5) (6) ↑ Terminal type Auxiliary outputs 1, 2 The E5GC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) wil occur if the input type setting does not agree with the temperature sensor. Check the input type.
E5GC Terminal Block Appearance E5GC-@C Controllers with Screwless Clamp Terminal E5GC-@6 Controllers with Screw Terminal (M3 Screws) Controllers with Screw Terminal Controllers with Screwless Clamp Terminals • Terminal type: Forked or round crimped terminals • Tightening torque for all terminals: 0.43 to 0.58 N·m • Wire stripping length: 8 to 12 mm • Ferrules: 8 to 12 mm 0.8 to 1.4 mm 5.8 mm max. 8 to 12 mm 8 to 12 mm 5.8 mm max. Wires:AWG24 to AWG18 (equal to a cross-sectional area of 0.21 to 0.
E5GC Dimensions (Unit: mm) Controllers E5GC-@6 Controllers with Screw Terminal Waterproof Packing (Accessory) 63.6 48 Mounting Adapter (Accessory) Terminal Cover (Accessory) 4 90 44.8 1 22 40.8 24 22 • Use two Mounting Adapters, either on the top and bottom or on the right and left. • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller.
E5GC Accessories (Order Separately) USB-Serial Conversion Cable (2110) E58-CIFQ2 263 250 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110) (1510) 250 263 1510 E58-CIFQ2 (Order separately) Note: Always use this product together with the E58-CIFQ2. Conversion Cable Current Transformers E54-CT1 21 15 Thru-current (Io) vs.
E5GC Mounting Adapter Y92F-53 (Two provided.) One pair is provided with the Temperature Controller. Order this Adapter separately if it becomes lost or damaged. 34.7 12 11.8 9.4 Waterproof Packing Y92S-P12 The Waterproof Packing is provided with the Temperature Controller. Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection.
Digital Temperature Controller E5CC/E5CC-B/E5CC-U Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. Models with Push-In Plus Terminal Added to Lineup. (48 48 mm) * (E5CC/-U) (E5CC-B) * CSA conformance evaluation by UL. • The white PV display with a height of 15.2 mm improves visibility. • High-speed sampling at 50 ms.
E5CC/E5CC-B/E5CC-U Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal E5CC-@@ 3 @ 5 M -@@@ (Example: E5CC-RX3A5M-000) A B C D E F A Model Control outputs 1 and 2 B C D No.
E5CC/E5CC-B/E5CC-U Model Number Legend Models with Push-In Plus Terminal E5CC-@@ 2 @ B M -@@@ (Example: E5CC-RX2ABM-000) A B C D E F A Model Control outputs 1 and 2 B C D No.
E5CC/E5CC-B/E5CC-U Model Number Legend Plug-in Models E5CC-@@ @ @ U M -000 A B C D E (Example: E5CC-RW0AUM-000) F A B C D Control No.
E5CC/E5CC-B/E5CC-U Optional Products (Order Separately) Front Covers USB-Serial Conversion Cable Model E58-CIFQ2 Type Hard Front Cover Soft Front Cover Terminal Covers (for E5CC) CX-Thermo Support Software Model E53-COV17 E53-COV23 (3pcs) Note: The E53-COV10 cannot be used. Refer to page 31 for the mounted dimensions. Waterproof Packing Model Y92S-P8 Note: The Waterproof Packing is provided only with E5CC/E5CC-B Controllers. The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.
E5CC/E5CC-B/E5CC-U Specifications Ratings Power supply voltage Operating voltage range Power consumption Sensor input Input impedance Control method Relay output Control output Voltage output (for driving SSR) Linear current output *2 A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85% to 110% of rated supply voltage Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC All other models: 6.5 VA max.
E5CC/E5CC-B/E5CC-U Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type Platinum resistance thermometer Sensor specification Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 120 165 140 to 260°C 2300 2300 1800 1800 1700 1700 1700 1600 1500 Temperature range (°C) 1400 1300 1300 1300 1300 1200 1100 1000 900 850 850 850 800 700 600 600 500.0 500 500.0 500.
E5CC/E5CC-B/E5CC-U Alarm Types Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1.
E5CC/E5CC-B/E5CC-U *1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm Case 2 Case 1 Case 3 (Always ON) H<0, L<0 L H SP H<0, L>0 |H| < |L| H SP L H H>0, L<0 |H| > |L| SP L H<0, L>0 |H| ≥ |L| L SP H SP H L H>0, L<0 |H| ≤ |L| *3.
E5CC/E5CC-B/E5CC-U Characteristics E5CC/E5CC-B Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1 Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max. Analog input: 0.2% FS 1 digit max. Indication accuracy CT input: 5% FS 1 digit max. (at the ambient temperature of 23°C) E5CC-U Thermocouple: (1% of indication value or 2°C, whichever is greater) 1 digit max. *1 Platinum resistance thermometer: (0.
E5CC/E5CC-B/E5CC-U cULus: UL 61010-1/CSA C22.2 No.61010-1 *7, KOSHA (S Mark) certification (Some models only.) *8, Korean wireless regulations (Radio law: KC Mark) (Some models only.
E5CC/E5CC-B/E5CC-U Windows XP/Vista/7/8/10 *1 CX-Thermo version 4.5 or higher (Version 4.61 or higher is required for the Applicable software E5CC-U, Version 4.65 or higher is required for the E5CC-B.) Applicable models E5@C-T Series, E5@C Series, and E5CB Series USB interface standard Conforms to USB Specification 2.0. DTE speed 38400 bps Computer: USB (type A plug) Connector Digital Temperature Controller: specifications Special serial connector Power supply Bus power (Supplied from USB host controller.
E5CC/E5CC-B/E5CC-U External Connections E5CC (Screw Terminal) Control output 1 Relay output 250 VAC, 3A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
E5CC/E5CC-B/E5CC-U E5CC-B (Push-In Plus Terminal) E5CC-@@ 2 @ B M - @ @ @ (1) (2) (3) (4) (5) ↑ Terminal type Control output 1 Relay output 250 VAC, 3A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Auxiliary outputs 1, 2 (6) The E5CC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
E5CC/E5CC-B/E5CC-U E5CC-U (Plug-in Models) E5CC- UM-000 The E5CC-U is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
E5CC/E5CC-B/E5CC-U Nomenclature E5CC E5CC-B E5CC-U Front panel Temperature unit Top View of E5CC Top View of E5CC-B Top View of E5CC-U No. 1 display Operation indicators PV or specified parameter No. 2 display SP or specified parameter value Use the U D Keys to set the parameter. Top-panel Setup Tool port Press O Key once to go to Adjustment Level. Use S Key to change the digit (default setting). Press O Key for at least 3 seconds to go to Initial Setting Level.
E5CC/E5CC-B/E5CC-U E5CC-U 76.8 58.6 4 48 × 48 14.2 44.8 × 44.8 58 Mounting Adapter (Accessory) The Setup Tool port is on the top of the Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
E5CC/E5CC-B/E5CC-U Waterproof Packing The Waterproof Packing is provided only with the E5CC/E5CC-B. It is not included with the E5CC-U. Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66.
E5CC/E5CC-B/E5CC-U Adapter Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel. 4. You cannot use it together with the Y92F-49 Adapter that is enclosed with the Controller. Fixture (Accessory) 76 4.7 69.6 to 77.
E5CC/E5CC-B/E5CC-U Watertight Cover Mounting Adapter Y92A-48N Y92F-49 21.9 14 The Mounting Adapter is provided with the Temperature Controller. Order this Adapter separately if it becomes lost or damaged. (2) 87.7 69 79.2 12 67.6 Protective Cover Y92A-48D Protective Cover Y92A-48H Note: This Protective Cover cannot be used if the Waterproof Packing is installed. This Protective Cover is hard type. Please use it for the mis-operation prevention etc. This Protective Cover is soft type.
Digital Temperature Controller E5EC/E5EC-B/E5AC Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. Models with Push-In Plus Terminal Added to 48 × 96-mm Lineup. (48 96 mm/96 96 mm) * (E5EC/AC) (E5EC-B) * CSA conformance evaluation by UL. • A white LCD PV display with a height of approx. 18 mm for the E5EC/E5EC-B and 25 mm for the E5AC improves visibility. • High-speed sampling at 50 ms.
E5EC/E5EC-B/E5AC Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal E5EC-@@ 4 @ 5 M -@@@ (Example: E5EC-RX4A5M-000) A B C D E F E5AC-@@ 4 @ 5 M -@@@ (Example: E5AC-RX4A5M-000) A B C D E F A Model Control outputs 1 and 2 B No.
E5EC/E5EC-B/E5AC Model Number Legend Models with Push-In Plus Terminal E5EC-@@ @ @ B M -@@@ (Example: E5EC-RX4ABM-000) A B C D E F Model A Control outputs 1 and 2 B No.
E5EC/E5EC-B/E5AC Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2 Communications Conversion Cable Model E58-CIFQ2-E Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the front-panel Setup Tool port. Terminal Covers (for E5EC/E5AC) Model E53-COV24 (3pcs) Note: The Terminal Covers E53-COV24 are provided with the Digital Temperature Controller. Current Transformers (CTs) Hole diameter 5.8 mm 12.
E5EC/E5EC-B/E5AC Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85 to 110% of rated supply voltage Models with option selection of 000: 6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or E5EC/ 2.3 W max. at 24 VDC E5EC-B All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC Power consumption Models with option selection of 000: 7.0 VA max. at 100 to 240 VAC, and 4.
E5EC/E5EC-B/E5AC Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type Platinum resistance thermometer Sensor specification Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 120 165 140 to 260°C 2300 2300 1800 1800 1700 1700 1700 1600 Temperature range (°C) 1500 1400 1300 1300 1300 1300 1200 1100 1000 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.
E5EC/E5EC-B/E5AC Alarm Types Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1.
E5EC/E5EC-B/E5AC *1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm Case 2 Case 1 Case 3 (Always ON) H<0, L<0 L H SP H<0, L>0 |H| < |L| H SP L H H>0, L<0 |H| > |L| H SP L H<0, L>0 |H| ≥ |L| L SP SP H L H>0, L<0 |H| ≤ |L| *3.
E5EC/E5EC-B/E5AC Characteristics Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1 Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max. Analog input: 0.2% FS 1 digit max. CT input: 5% FS 1 digit max. Potentiometer input: 5% FS 1 digit max. Transfer output accuracy 0.3% FS max. Remote SP Input Type 0.2% FS 1 digit max.
E5EC/E5EC-B/E5AC USB-Serial Conversion Cable Windows XP/Vista/7/8/10 *1 E5EC/E5AC:CX-Thermo version 4.5 or higher E5EC-B:CX-Thermo version 4.65 or higher Applicable models E5@C-T Series, E5@C Series, and E5CB Series USB interface standard Conforms to USB Specification 2.0. DTE speed 38,400 bps Computer: USB (type A plug) Connector Digital Temperature Controller: specifications Special serial connector Power supply Bus power (Supplied from USB host controller.
E5EC/E5EC-B/E5AC External Connections E5EC/E5AC (Screw Terminal) E5AC-@@ 4 @ 5 M - @ @ @ E5EC-@@ 4 @ 5 M - @ @ @ (1) (2) (3) (4) (5) ↑ Terminal type Control output 1 Control output 2 Relay output 250 VAC, 5 A (resistive load) Voltage output (for driving SSR) 12 VDC, 40 mA When There Is a Control Output 2: 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
E5EC/E5EC-B/E5AC E5EC-B (Push-In Plus Terminal) E5EC-@@ @ @ B M - @ @ @ (1) (2) (3) (4) (5) ↑ Terminal type Control output 1 Auxiliary outputs 1, 2, 3, 4 Relay output 250 VAC, 5 A (resistive load) Voltage output (for driving SSR) 12 VDC, 40 mA Relay output Model with 2 auxiliary outputs: 250 VAC, 3 A (resistive load) Models with 4 auxiliary outputs: 250 VAC, 2 A (resistive load) (6) The E5EC is set for a K-type thermocouple (input type = 5) by default. An input error (s.
E5EC/E5EC-B/E5AC Isolation/Insulation Block Diagrams Models with 2 Auxiliary Outputs Models with 4 Auxiliary Outputs Sensor input, CT inputs, and remote SP input Sensor input, CT inputs, potentiometer input, and remote SP input Communications and event inputs Communications and event inputs Voltage output (for driving SSR) and transfer output Power Supply Power Supply Voltage output (for driving SSR), linear current output, and transfer output Relay output Relay output Auxiliary output 1 Auxil
E5EC/E5EC-B/E5AC Dimensions (Unit: mm) Controllers E5EC (64) 60 4 1 48 44 96 91 110 Waterproof Packing (Accessory) E5EC-B Mounting Adapter (Accessory) 4 (1) 48 (71.4) 67.4 44 110 96 Waterproof Packing (Accessory) 91 Mounting Adapter (Accessory) • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the top panel.
E5EC/E5EC-B/E5AC E5AC (64) 60 4 1 96 x 96 91 x 91 110 Waterproof Packing (Accessory) 91 Mounting Adapter (Accessory) • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the top panel. The E58-CIFQ2 USB-Serial Conversion Cable and E58CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel.
E5EC/E5EC-B/E5AC Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ2 (2110) 263 250 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110) (1510) 250 263 E58-CIFQ2 (Order Separately) 1510 Conversion Cable Note: Always use this product together with the E58-CIFQ2. Waterproof Packing Terminal Covers E53-COV24 (Three Covers provided.) 2 3.
E5EC/E5EC-B/E5AC Watertight Cover Watertight Cover Y92A-49N (48 96) Y92A-96N (96 96) 21.9 21.9 (2) (2) 131.7 131.7 67.6 115.6 28.9 28.9 Current Transformers E54-CT1 21 15 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1 2.8 5.8 dia. 7.5 25 Maximum continuous heater current: Number of windings: Winding resistance: 3 Output voltage (Eo) V (r.m.s.) 10.5 40 Two, 3.5 dia.
MEMO 53
Digital Temperature Controller E5DC (22.5 mm Wide, and DIN Track-mounting Type) The E5DC Mounts to DIN Track and Is Ideal for Connections to HMIs and PLCs. It provides the Same Easy Operation and Advanced Performance as the Rest of the E5@C Series. • A slim body at 85 22.5 mm (D W) that fits into narrow control panels and mounts to DIN Track. • Removable terminal block for easy replacement to simplify maintenance. • High-speed sampling at 50 ms for applications with high-speed temperature increases.
E5DC Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal E5DC-@@ @ @ @ M-@@@ (Example: E5DC-RX0ASM-015) A B C D E F A Model B No. of Control auxiliary output 1 outputs C Power supply voltage D E F Terminal type Input type Options Meaning E5DC *1. *2. *3. *4. *5. 22.
E5DC Optional Products (Order Separately) Terminal Unit End Plate Model E5DC-SCT1S Model PFP-M USB-Serial Conversion Cable Spacer Model E58-CIFQ2 Model PFP-S Communications Conversion Cable Model E58-CIFQ2-E Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the front-panel Setup Tool port. DIN Tracks Model PFP-100N PFP-50N Unit Labels Current Transformers (CTs) Hole diameter 5.8 mm 12.
E5DC Specifications Ratings Power supply voltage Operating voltage range Power consumption Sensor input Input impedance Control method Relay output Control output Voltage output (for driving SSR) Linear current output Number of outputs A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC 85 to 110% of rated supply voltage 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max.
E5DC Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type Platinum resistance thermometer Sensor specification Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 120 165 140 to 260°C 2300 2300 1800 1800 1700 1700 1700 1600 1500 Temperature range (°C) 1400 1300 1300 1300 1300 1200 1100 1000 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.
E5DC Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.) Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1.
E5DC *1. With set values 1, 4, and 5, the upper- and lower-limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm Case 3 (Always OFF) Case 2 Case 1 H<0, L<0 L H SP H<0, L>0 |H| < |L| H SP L H H>0, L<0 |H| > |L| H SP L H<0, L>0 |H| ≥ |L| L SP SP H L H>0, L<0 |H| ≤ |L| *3.
E5DC Characteristics Indication accuracy (when mounted individually, ambient temperature of 23C) Simple transfer output accuracy Influence of temperature *3 Influence of voltage *3 Influence of EMS.
E5DC Windows XP/Vista/7/8/10 *1 CX-Thermo version 4.6 or higher E5@C-T Series, E5@C Series, and E5CB Series Conforms to USB Specification 2.0 38,400 bps Computer: USB (Type A plug) Connector Digital Temperature Controller: Special serial specifications connector Power supply Bus power (Supplied from the USB host controller) *2 Power supply voltage 5 VDC Current consumption 450 mA max. 4.70.2 VDC (Supplied from USB-Serial Output voltage Conversion Cable to the Digital Temperature Controller.) 250 mA max.
E5DC External Connections E5DC Control output Auxiliary outputs 1, 2 Relay output 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max. The E5DC is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type.
E5DC Nomenclature E5DC Front panel Bottom View of E5DC No. 1 display PV or specified parameter Operation indicators No.2 display SP or specified parameter value Press O Key once to go to Adjustment Level. Use the M Key to change to another parameter. Press O Key for at least 3 seconds to go to Initial Setting Level. Use the U D Keys to set the parameter. Use S Key to change the digit (default setting).
E5DC Accessories (Order Separately) Terminal Unit E5DC-SCT1S 22.5 30.7 91 35 4 USB-Serial Conversion Cable E58-CIFQ2 (2110) 263 250 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110) (1510) 250 Note: Always use this product together with the E58-CIFQ2.
E5DC ● Current Transformers E54-CT1 21 15 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1 2.8 5.8 dia. 7.5 25 3 Output voltage (Eo) V (r.m.s.) 10.5 40 Two, 3.5 dia. 10 30 E54-CT3 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 4002 Winding resistance: 182 2.36 dia. 100V Frequency: 50 Hz ∞ 1kΩ 10 Distortion factor 10% 1 3% 1% 100mV 100Ω 10 30 12 dia. RL=10Ω 1 9 100μV 40 × 40 10 1 10 100mA 1 10 100 1,000A Thru-current (Io) A (r.m.s.
E5DC Mounting Adapters Short Bars Y92F-53 (Two included.) Y92S-P11 (Four included.) This accessory is not included with the product. Order it separately to mount the product to a panel. Use this product to connect between terminals (for power supplies, communications, etc.) when you use multiple E5DC Controllers. 27.5 34.7 2.4 22.5 12 24.8 11.8 9.4 0.8 3 5 End Plate DIN Tracks PFP-M PFP-100N PFP-50N 10 6.2 M4×8 pan head screw 1.8 1 50 35.5 35.3 1.8 11.5 10 M4 spring washer 7.3±0.15 1.
Programmable Temperature Controller (Digital Controller) E5CC-T (48 48 mm) Programmable Controllers Join the E5C Series! Program up to 256 segments can handle a wide variety of applications. • Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each • The white PV display with a height of 15.2 mm improves visibility. • High-speed sampling at 50 ms. • Models are available with up to 3 auxiliary outputs, up to 4 event inputs, and a transfer output to cover a wide range of applications.
E5CC-T Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal E5CC-T @@3 @5 M -@@@ (Example: E5CC-TRX3A5M-000) A BC D E F A Model Control outputs 1 and 2 B C D No.
E5CC-T Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2 Type Hard Front Cover Soft Front Cover Terminal Covers Model E53-COV17 E53-COV23 (3pcs) Note: The Terminal Covers E53-COV23 are provided with the Digital Temperature Controller. The E53-COV10 cannot be used. Refer to page 79 for the mounted dimensions. Waterproof Packing Model Y92S-P8 Note: The Waterproof Packing is provided with the Digital Temperature Controller. Current Transformers (CTs) Hole diameter 5.8 mm 12.
E5CC-T Specifications Ratings Power supply voltage Operating voltage range Power consumption Sensor input Input impedance Control method Relay output Control output Auxiliary output Voltage output (for driving SSR) Linear current output Number of outputs Output specifications Number of inputs Event input External contact input specifications Transfer output Number of outputs Output specifications Setting method Indication method Bank switching Other functions Ambient operating temperature Ambient op
E5CC-T Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type Platinum resistance thermometer Sensor specification Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 120 165 140 to 260°C 2300 2300 1800 1800 1700 1700 1700 1600 Temperature range (°C) 1500 1400 1300 1300 1300 1300 1200 1100 1000 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.
E5CC-T Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1.
E5CC-T *1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm Case 2 Case 1 Case 3 (Always ON) H<0, L<0 L H SP H<0, L>0 |H| < |L| H SP L H H>0, L<0 |H| > |L| SP L H<0, L>0 |H| ≥ |L| L SP H SP H L H>0, L<0 |H| ≤ |L| *3.
E5CC-T Characteristics Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1 Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max. Analog input: 0.2% FS 1 digit max. CT input: 5% FS 1 digit max. Transfer output accuracy 0.3% FS max. Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10°C, whichever is greater) 1 digit Influence of temperature *2 max.
E5CC-T Program Control Number of programs (patterns) Number of segments (steps) Segment setting method Segment times Alarm setting Reset operation Startup operation PID sets Number of sets Setting method Alarm SP function Program status control Wait operation Time signals Segment operation Program operation Wait method Wait width setting Number of outputs Number of ON/OFF Operations Setting method Program status output PV start Program startup operation Operation end operation Program SP shift 76 Sta
E5CC-T Windows XP/Vista/7/8/10 *1 CX-Thermo version 4.61 or higher E5@C-T Series, E5@C Series, and E5CB Series Conforms to USB Specification 2.0. 38400 bps Computer: USB (type A plug) Connector Digital Temperature Controller: specifications Special serial connector Bus power (Supplied from USB host Power supply controller.) *2 Power supply voltage 5 VDC Current consumption 450 mA max. 4.70.2 VDC Output voltage (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.) 250 mA max.
E5CC-T External Connections E5CC-T Control output 1 Relay output 250 VAC, 3 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 20 mA DC 4 to 20 mA DC Load: 500 Ω max.
E5CC-T Nomenclature E5CC-T Front panel Temperature unit Operation indicators No. 1 display PV or specified monitor/setting parameter Top View of E5CC-T No. 2 display Press O Key once to go to Program Setting Level. SP or specified monitor/parameter value Top-panel Setup Tool port Press O Key for at least 3 seconds to go to Initial Setting Level. Use the UD Keys to set the parameter.
E5CC-T Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ2 (2110) 263 250 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Terminal Covers 48 E53-COV17 Terminal Covers E53-COV23 (Three Covers provided.) 2 3.8 48.8 10 Terminal Cover (E53-COV23) 22 44.8 9.1 Waterproof Packing Y92S-P8 (for DIN 48 48) 80 The Waterproof Packing is provided with the Temperature Controller. Order the Waterproof Packing separately if it becomes lost or damaged.
E5CC-T Current Transformers E54-CT1 21 15 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1 2.8 5.8 dia. 7.5 25 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 4002 Winding resistance: 182 3 Output voltage (Eo) V (r.m.s.) 10.5 40 Two, 3.5 dia. 10 30 100V Frequency: 50 Hz ∞ 1kΩ 10 Distortion factor 10% 1 3% 1% 100mV 100Ω 10 E54-CT3 2.36 dia. 30 RL=10Ω 1 12 dia. 9 100μV 10 1 40 × 40 10 100mA 1 10 100 1,000A Thru-current (Io) A (r.m.s.
E5CC-T Adapter Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel. 4. You cannot use this Adapter together with the Y92F-49 Adapter that is provided with the E5CC-T Temperature Controller. Fixture (Accessory) 76 4.7 69.
E5CC-T Watertight Cover Mounting Adapter Y92A-48N Y92F-49 21.9 14 The Mounting Adapter is provided with the Temperature Controller. Order this Adapter separately if it becomes lost or damaged. (2) 87.7 69 79.2 12 67.6 28.9 Protective Cover Y92A-48D Protective Cover Note: This Protective Cover cannot be used if the Waterproof Packing is installed. This Protective Cover is soft type. It is able to operate the controller with using this cover. Y92A-48H This Protective Cover is hard type.
Programmable Temperature Controller (Digital Controller) E5EC-T/E5AC-T (48 96 mm/96 96 mm) Programmable Controllers Join the E5C Series! Program up to 256 segments can handle a wide variety of applications. • Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each • A white LCD PV display with a height of approx. 18 mm for the E5ECT and 25 mm for the E5AC-T improves visibility. • Tool ports are provided both on the top panel and the front panel.
E5EC-T/E5AC-T Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal E5EC-T@@ 4 @ 5 M -@@@ (Example: E5EC-TRX4A5M-000) A BC D E F E5AC-T@@ 4 @ 5 M -@@@ (Example: E5AC-TRX4A5M-000) A BC D E F A Model Control outputs 1 and 2 B No.
E5EC-T/E5AC-T Optional Products (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ2 Communications Conversion Cable Model E58-CIFQ2-E Note: Always use this product together with the E58-CIFQ2. This Cable is used to connect to the front-panel Setup Tool port. Terminal Covers Model E53-COV24 (3pcs) Note: The Terminal Covers E53-COV24 are provided with the Digital Temperature Controller.
E5EC-T/E5AC-T Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85 to 110% of rated supply voltage E5EC-T 8.7 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC Power consumption E5AC-T 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max.
E5EC-T/E5AC-T Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor type Platinum resistance thermometer Sensor specification Pt100 Infrared temperature sensor Thermocouple JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 120 165 140 to 260°C 2300 2300 1800 1800 1700 1700 1700 1600 Temperature range (°C) 1500 1400 1300 1300 1300 1300 1200 1100 1000 900 850 850 850 800 700 600 600 500.0 500 500.0 500.0 400.
E5EC-T/E5AC-T Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1.
E5EC-T/E5AC-T *1. With set values 1, 4 and 5, the upper and lower limit values can be set independently for each alarm type, and are expressed as “L” and “H.” *2. Set value: 1, Upper- and lower-limit alarm Case 2 Case 1 Case 3 (Always ON) H<0, L<0 L H SP H<0, L>0 |H| < |L| H SP L H H>0, L<0 |H| > |L| SP L H<0, L>0 |H| ≥ |L| L SP H SP H L H>0, L<0 |H| ≤ |L| *3.
E5EC-T/E5AC-T Characteristics Indication accuracy (at the ambient temperature of 23°C) Transfer output accuracy Influence of temperature *2 Influence of voltage *2 Influence of EMS. (at EN 61326-1) Input sampling period Thermocouple: (0.3% of indication value or 1°C, whichever is greater) 1 digit max. *1 Platinum resistance thermometer: (0.2% of indication value or 0.8°C, whichever is greater) 1 digit max. Analog input: 0.2% FS 1 digit max. CT input: 5% FS 1 digit max.
E5EC-T/E5AC-T Program Control Number of programs (patterns) Number of segments (steps) Segment setting method Segment times Alarm setting Reset operation Startup operation PID sets Number of sets Setting method Alarm SP function Program status control Wait operation Time signals Segment operation Program operation Wait method Wait width setting Number of outputs Number of ON/OFF Operations Setting method Program status output PV start Program startup operation Operation end operation Program SP shift
E5EC-T/E5AC-T Windows XP/Vista/7/8/10 *1 CX-Thermo version 4.61 or higher E5@C-T Series, E5@C Series, and E5CB Series Conforms to USB Specification 2.0. 38400 bps Computer: USB (type A plug) Connector Digital Temperature Controller: specifications Special serial connector Power supply Bus power (Supplied from USB host controller.) *2 Power supply voltage 5 VDC Current consumption 450 mA max. 4.70.2 VDC Output voltage (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.
E5EC-T/E5AC-T External Connections E5EC-T/E5AC-T 4 E5EC T (1) 5M (2) (3) (4) (5) 4 E5AC T (6) (1) Terminal type 5M (2) (3) (4) (5) (6) Terminal type Control output 1 Control output 2 Relay output 250 VAC, 5A (resistive load) Voltage output (for driving SSR) 12 VDC, 40 mA 21 mA if there are two control outputs Linear current output 0 to 20 mA DC 4 to 20 mA DC Auxiliary outputs Relay output 250 VAC, 5 A (resistive load) Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 0 to 2
E5EC-T/E5AC-T Nomenclature E5EC-T Front panel No. 1 display Temperature unit Top View of E5EC-T PV or specified monitor/parameter Operation indicators No. 2 display Top-panel Setup Tool port SP or specified monitor/parameter value No. 3 display Use S Key to change the digit (default setting). Program No., segment No., remaining segment time, or MV (valve opening). Use the U D Keys to set the parameter.
E5EC-T/E5AC-T Dimensions (Unit: mm) Controllers E5EC-T 48 (64) 60 4 1 44 96 91 110 • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the top panel. The E58-CIFQ2 USBSerial Conversion Cable and E58CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel.
E5EC-T/E5AC-T E5AC-T (64) 60 4 1 96 x 96 91 x 91 110 Waterproof Packing (Accessory) Mounting Adapter (Accessory) • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58-CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the top panel. The E58-CIFQ2 USB-Serial Conversion Cable and E58CIFQ2-E Communications Conversion Cable are required to connect to the port on the front panel.
E5EC-T/E5AC-T Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ2 (2110) 263 250 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110) (1510) 250 263 E58-CIFQ2 (Order Separately) 1510 Conversion Cable Note: Always use this product together with the E58-CIFQ2. Waterproof Packing Terminal Covers E53-COV24 (Three Covers provided.
E5EC-T/E5AC-T Watertight Cover Watertight Cover Y92A-49N (48 96) Y92A-96N (96 96) 21.9 21.9 (2) (2) 131.7 131.7 67.6 115.6 28.9 28.9 Current Transformers E54-CT1 21 15 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) E54-CT1 2.8 5.8 dia. 7.5 25 Maximum continuous heater current: 50 A (50/60 Hz) Number of windings: 4002 Winding resistance: 182 3 Output voltage (Eo) V (r.m.s.) 10.5 40 Two, 3.5 dia.
E5@C/E5@C-T Operation Setting Levels Diagram E5C This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level. Press the O + M Keys for at least 1 s Only when Manual Mode was used just before power OFF Used to set protection for operations.
E5@C/E5@C-T E5C-T This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Press O and M Keys for at least 1 s. Protect Level Used to set protection for operations. Starting in manual mode Power ON Press O and M Keys for at least 3 s.*2 Operation in progress Level changes automatically.
E5@C/E5@C-T Operation Parameters E5@C The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top parameter in that level. Some parameters may not be displayed depending on the model and other settings. Press the S Key*2 Power ON Starting in Manual Mode. Manual Control Level Press the S Key for at least 1 s. *1 C Press the O Key or the S Key for at least 1 s. *1 PID Control only 25 0 PV/MV Adjustment Level l.
E5@C/E5@C-T Monitor/Setting Item Level 25 0 Monitor/Setting Item Display 1 S Monitor/Setting Item Display 2 S Monitor/Setting Item Display 3 Monitor/Setting Item Display 4 S S Monitor/Setting Item Display 5 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). Press the O Key for at least 1 s. Advanced Function Setting Level alt3 Alarm 3 Type 2 M alh3 0.
E5@C/E5@C-T E5@C-T Some parameters may not be displayed depending on the model and other settings. Starting in manual mode Monitor/Setting Item Level 25 PF Monitor/ Power ON Manual Control Level 25 Setting Item 0 S PF Monitor/Setting Item display 2 to 5 display 1 * The monitor/setting items to display are set in the Monitor/Setting Item 1 to 5 parameters (Advanced Function Setting Level). PV/Manual MV 50.0 Press S Key.*2 Press S Key.*2 Press O or S Key for at least 1 s.
E5@C/E5@C-T Press O Key for at least 1 s. Protect Level Press O + M Key for at least 3 s. M pmov oapt 0 0 Operation/Adjustment Protect pfpt Initial Setting/ Communications Protect pmsk Setting Change Protect prlp M Move to Protect Level icpt Press O + M Key for at least 3 s. (The key pressing time can be changed in the Move to Protect Level Time parameter (Advanced Function Setting Level).) 1 M M 0 off Press O + M Key for at least 1 s.
E5@C/E5@C-T Advanced Function Setting Level init off Parameter Initialization mant Program End ON Time mani Standby Time Unit Standby Sequence Reset n-o Auxiliary Output 1 to 4 Open in Alarm hsh Heater Burnout Latch lba Heater Burnout Hysteresis α Integral/Derivative Time Unit o 1 AT Calculated Gain none 0.8 M 0.8 alm1 alm2 M 0.
E5@C/E5@C-T Error Displays (Troubleshooting) When an error occurs, the No. 1 display or No. 2 display shows the error code. Take necessary measure according to the error code, referring the following table. Display s.err Name Input error [[[[ Display range exceeded ]]]] Meaning The input value exceeded the control range.* The input type is not set correctly. The sensor is disconnected or shortcircuited. The sensor is not wired correctly. The sensor is not wired.
E5@C/E5@C-T Safety Precautions Be sure to read the precautions for all E5@C/E5@C-T models in the website at: http://www.ia.omron.com/. Warning Indications CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely.
E5@C/E5@C-T Precautions for Safe Use Be sure to observe the following precautions to prevent malfunction or adverse affects on the performance or functionality of the product. Not doing so may occasionally result in faulty operation. Do not handle the Digital Temperature Controller in ways that exceed the ratings. 1. This product is specifically designed for indoor use only. Do not use this product in the following places: • Places directly subject to heat radiated from heating equipment.
E5@C/E5@C-T 23.Do not disconnect the Communications Conversion Cable or the USB-Serial Conversion Cable while communications are in progress. Damage or malfunction may occur. 24.Do not touch the external power supply terminals or other metal parts on the Digital Temperature Controller. 25.Do not exceed the communications distance that is given in the specifications and use the specified communications cable. Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No.
E5@C/E5@C-T Measurement Accuracy Mounting 1. When extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types. 2. When extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep the resistance of the three lead wires the same. 3. Mount the product so that it is horizontally level. 4. If the measurement accuracy is low, check to see if input shift has been set correctly.
E5@C/E5@C-T E5EC/E5EC-B/E5AC/E5EC-T/E5AC-T Mounting to and Removing from DIN Track E5DC Adapter Adapter Panel Terminal Cover (E53-COV24) • Mounting a Unit Pull down the DIN Track hook on the Terminal Unit and catch the top hook on the DIN Track. Press the Unit onto the DIN Track until the DIN Track hooks are locked in place. 2. Catch the top hook on the DIN Track. Terminal Cover (E53-COV24) Water Proof Packing 1.
E5@C/E5@C-T Mounting the DIN Track Attach the DIN Track to the inside of the control panel with screws to at least three locations. • DIN Track (sold separately) PFP-50N (50 cm) and PFP-100N (100 cm) Attaching the End Cover E5DC 1. Install the E5DC in a panel. Install the DIN Track vertically to the ground. 2. Peel off the release paper from the double-sided tape on the End Cover.
E5@C/E5@C-T Removing the Digital Temperature Controller from the case E5GC Removing the draw-out jig when only one hook is caught in the draw-out jig insertion hole You can use the Y92F-55 Draw-out Jig to remove the interior body of the Digital Temperature Controller from the case to perform maintenance without removing the terminal wiring. This is possible only for the E5GC.
E5@C/E5@C-T • If you use crimp terminals for the E5DC, use crimp terminals with insulation sleeves. If you use a bare crimp terminal with no insulation, the terminal may short with the terminal above or below it. If you use bare crimp terminals, cover the crimped sections with insulating marking tubes. Secure the marking tubes so that they do not move. Checking Connections • After insertion, pull gently on the wire to make sure that it will not come out (i.e.
E5@C/E5@C-T E5@C-B (Controllers with Push-In Plus Terminal) 1. Connecting Wires to the Push-In Plus Terminal Block Part Names of the Terminal Block Release hole 2. Removing Wires from the Push-In Plus Terminal Block Use the following procedure to remove wires from the terminal block. The same method is used to remove stranded wires, solid wires, and ferrules. 1. Hold a flat-blade screwdriver at an angle and insert it into the release hole. 2.
E5@C/E5@C-T Recommended Flat-blade Screwdriver Use a flat-blade screwdriver to connect and remove wires. Use the following flat-blade screwdriver. The following table shows manufacturers and models as of 2015/Dec. Side Front 2.5 mm dia. 0.4 mm 2.5 mm Model XW4Z-00B Manufacturer Omron ESD0.40✕2.5 Wera SZF 0.4✕2.5 Phoenix Contact 0.4✕2.5✕75 302 Wiha AEF.2.5✕75 Facom 210-719 Wago* SDI 0.4✕2.
MEMO 118
Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron).
OMRON Corporation Industrial Automation Company Authorized Distributor: Kyoto, JAPAN Contact: www.ia.omron.com Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A. Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 OMRON ASIA PACIFIC PTE. LTD. No.