Datasheet

E5CB
5
External Connections
A voltage output (control output) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect
any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured
temperature values as a result of leakage current.
Nomenclature
E5CB
Dimensions (Unit: mm)
E5CB
E5CB
+
A
B
B
Pt input
Alarm Output
• Relay output: 250 VAC, 1 A
(resistive load)
Input power supply
100 to 240 VAC, 50/60 Hz
DO NOT
USE
Control output
+
TC input
1
Control Output
• Relay output: 250 VAC, 3 A (resistive load)
Voltage output (for driving SSR): 12 VDC, 21 mA
2
3
4
5
7
8
9
10
24 VAC, 50/60 Hz
24 VDC(no polarity)
(9)
Up Key: Increases the setting.
(10)
+
(11)
+
Press these keys for at least 2 seconds to start or stop autotuning.*1
(12)
+
Press these keys for at least 2 seconds to start or stop operation.*2
(1) Display No. 1 Displays the process value (PV) or parameter.
(2) Display No. 2 Displays the set point (SP) or parameter setting.
(3) ALM Lit while the alarm is ON. Not lit while the alarm is OFF.
(4) OUT
(5) STOP Not lit during operation. Lit while operation is stopped.
(6)
Level Key: Changes the setting level.
(7)
Mode Key: Changes the parameter within the setting level.
(8)
Down Key: Reduces the setting.
(10)
(11)
(12)
(9)
(8)
(2)
(1)
(4)
(5)
(7)
(3)
(6)
*1: These keys are disabled when starting and stopping autotuning has been disabled
with operation control key protection.
*2: These keys are disabled when starting and stopping operation has been disabled
with operation control key protection.
Lit while the control output is ON.
Not lit while the control output is OFF.
Press these keys for at least 3 seconds in Operation Level or Adjustment Level
to go to Protect Level.
Press these keys for at least 1 second in Protect Level to return to Operation Level.
Individual Mounting
Package Contents
• Temperature Controller
• Adapter
• Instruction Manual
Adapter
(Y92F-45)
45
45
60 min.
45
• Waterproof packing
Panel
60
5
65
1.5
48×48
44.8×44.8
Waterproof
packing
(Y92S-P6)
58
Solderless terminal size: M3.5
Terminal Cover: E53-COV19
(sold separately)
USB-Serial Conversion Cable: E58-CIFQ2
(sold separately)
Side-by-side Mounting
Panel Cutout
+0.6
0
+0.6
0
+0.6
0
(48 × number of Controllers − 2.5)
+1.0
0
Recommended panel thickness is 1 to 5 mm.
Do not vertically mount Controllers side by
side. (Allow mounting clearance between the
Controllers.)
To install the Controller so that it is waterproof,
insert the Waterproof Packing.
When two or more Controllers are mounted,
make sure that the surrounding temperature
does not exceed the ambient operating
temperature given in the specifications.
Use a control panel thickness of 1 to 2.5 mm if
a USB-Serial Conversion Cable is used when
mounting the Controller to a control panel.
The Support Software port is on the top of the Temperature Controller.
This port is used to connect the Temperature Controller to a personal computer.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
For details on connection methods, refer to the E58-CIFQ2 USB-Serial Conversion Cable Instruction Manual.
*Do not leave the USB-Serial Conversion Cable connected while using the Temperature Controller.
H09E-EN-01+E5CB+Datasheet.fm Seite 5 Freitag, 21. Januar 2011 12:03 12