Datasheet
E5CB
4
Characteristics
Note: 1. The indication accuracy of K and T thermocouples at a temperature of 100C max. is 2C 1 digit maximum. The indication accuracy
of the R and S thermocouples at a temperature of 200C max. is 3C 1 digit max.
2. Conditions: Ambient temperature: 10 to 23 to 55C, Voltage range: 15% to 10% of rated voltage
3. R, and S sensors: 0.2C/ max. (100 max.)
Electrical Life Expectancy Curve for
Relays (Reference Values)
USB-Serial Conversion Cable
Specifications
Note: 1. A high-power port is used for the USB port.
2. A driver must be installed on the computer. Refer to the Instruction
Manual included with the Cable for the installation procedure.
Indication accuracy
Thermocouple: (See note 1.)
(0.5% of indicated value or 1C, whichever is greater) 1 digit max.
Platinum resistance thermometer:
(0.5% of indicated value or 1C, whichever is greater) 1 digit max.
Influence of temperature (See note 2.) R and S thermocouple inputs: (1% of PV or 10C, whichever is greater) 1 digit max.
K, J, and T thermocouple inputs: (1% of PV or 4C, whichever is greater) 1 digit max.
Platinum resistance thermometer inputs: (1% of PV or 2C, whichever is greater) 1 digit max.
Influence of voltage (See note 2.)
Hysteresis 0.1 to 999.9 (in units of 0.1) C/F
Proportional band (P) 0.1 to 999.9 (in units of 0.1) C/F
Integral time (I) 0 to 3999 s (in units of 1 s)
Derivative time (D) 0 to 3999 s (in units of 1 s)
Control period 0.5, 1 to 99 s (in units of 1 s)
Alarm setting range 1999 to 9999 (decimal point position depends on input type)
Input sampling period 250 ms
Affect of signal source resistance
Thermocouple: 0.1C/ max. (100 max.) (See note 3.)
Platinum resistance thermometer: 0.6C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
Vibration resistance
Malfunction
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
Destruction
10 to 55 Hz, 20 m/s
2
for 2 hrs each in X, Y, and Z directions
Shock resistance
Malfunction
200 m/s
2
, 3 times each in X, Y, and Z directions
Destruction
300 m/s
2
, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 100 g, Mounting Bracket: Approx. 10 g
Degree of protection
Front panel: IP66
Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 100,000 times)
Conformed standards
Certified standards UL 61010-1, CSA C22.2 No. 1010-1
Applicable standards
EN61326, EN61010-1, IEC61010-1
VDE0106, Part 100 (Finger protection), when the terminal cover is mounted.
EMC
EMI EN61326
Emission Enclosure: EN55011 Group1 Class A
Emission AC Mains: EN55011 Group1 Class A
EMS EN61326
Immunity ESD: EN61000-4-2
Immunity RF-interference: EN61000-4-3
Immunity Burst: EN61000-4-4
Conduction Disturbance Immunity EN61000-4-6
Immunity Surge: EN61000-4-5
Immunity Voltage Dip/Interrupting: EN61000-4-11
Contact current (A)
No. of operations (x 10
4
)
100
50
30
10
5
3
1
01234 5
E5CB
250 VAC, 30 VDC
(resistive load)
Applicable OS Windows 2000, XP, Vista, or 7
Applicable software Thermo Mini
Applicable models E5CB Series
USB interface standard USB specification 1.1
DTE speed 38,400 bps
Connector Specifications
Computer: USB (Type A plug)
Temperature Controller: Special serial connector
Power supply Bus power (supplied from the USB host controller)
Power supply voltage 5 VDC
Current consumption 450 mA max.
Output voltage
4.70.2 VDC (Supplied from USB-Serial Conversion Cable
to the Temperature Controller.)
Output current
250 mA max. (Supplied from USB-Serial Conversion Cable
to the Temperature Controller.)
Ambient temperature 0 to 55C (with no condensation or icing)
Ambient humidity 10% to 80%
Storage temperature 20 to 60C (with no condensation or icing)
Storage humidity 10% to 80%
Altitude 2,000 m max.
Weight Approx. 120 g
H09E-EN-01+E5CB+Datasheet.fm Seite 4 Freitag, 21. Januar 2011 12:03 12